Selection and tuning of circuit breakers

Create Date: 2024-8-30 12:03:23|Source: Eaton/Eaton

The selection of circuit breakers should be based on the specific use conditions to select the use category, select the rated working voltage, rated current, tripper setting current and other parameters, refer to the protection characteristic curve provided by the product sample to select the protection characteristics, and need to verify the short-circuit characteristics and sensitivity coefficient.

Classification of circuit breakers

(1) Frame type circuit breaker (ACB)

Frame circuit breaker, all its parts are installed in an insulated metal frame, often open, can be installed with a variety of accessories, it is more convenient to replace contacts and components, and is mostly used in the main switch at the power end. There are several types of overcurrent trippers, such as electromagnetic, electronic and intelligent trippers. The circuit breaker has four stages of protection: long delay, short delay, instantaneous and ground fault, and the setting value of each protection is adjusted within a certain range according to its shell level.

The frame circuit breaker is suitable for AC 50Hz, rated voltage 380V, 660V, rated current of 200A-6300A in the distribution network, mainly used to distribute electric energy and protect lines and power equipment from overload, undervoltage, short circuit, single-phase grounding and other faults. Under normal conditions, it can be used for infrequent conversion of lines. Circuit breakers below 1250A can be used to protect the overload and short circuit of the motor in the network with AC 50Hz voltage and 380V.

Frame circuit breakers are also often used in transformer 400V side outlet main switches, bus contact switches, high-capacity feeder switches and large motor control switches.

(2) Molded Case Circuit Breaker (MCCB)

The molded case circuit breaker, also known as the device circuit breaker, is housed in a plastic shell with the outer contact of the grounding wire terminal, the arc extinguisher, the tripper and the operating mechanism. Auxiliary contacts, undervoltage trippers and shunt trippers are mostly modular, very compact in structure, generally do not consider maintenance, and are suitable for protection switches used as branches. Molded case circuit breakers usually contain a thermomagnetic trip unit, while larger molded case circuit breakers are equipped with a solid-state trip sensor.

There are two kinds of overcurrent trippers of molded case circuit breakers: electromagnetic and electronic, and the general electromagnetic molded case circuit breaker is a non-selective circuit breaker, with only two protection methods: long delay and instantaneous; The electronic molded case circuit breaker has four protection functions: long delay, short delay, instantaneous and ground fault. Some of the new products of electronic molded case circuit breakers also have a region-selective interlocking function.

Molded case circuit breakers are generally used for distribution feeder control and protection, low-voltage side outlet main switch of small distribution transformer, power distribution terminal control, and can also be used for power switch of various production machinery.

(3) Miniature Circuit Breaker (MCB)

Miniature circuit breaker is a kind of terminal protection appliance widely used in building electrical terminal power distribution devices. It is used for short-circuit, overload, overvoltage and other protection of single-phase and three-phase below 12, including single-pole 1P, two-pole 2P, three-pole 3P, and four-pole 4P.

The miniature circuit breaker is composed of an operating mechanism, a contact point, a protective device (various trippers), an arc extinguishing system, etc. The main contact is either manually operated or electrically closed. After the main contact is closed, the free trip mechanism locks the main contact in the closing position. The coil of the overcurrent tripper and the thermal element of the thermal tripper are connected in series with the main circuit, and the coil of the undervoltage tripper and the power supply are connected in parallel.

In the electrical design of civil buildings, miniature circuit breakers are mainly used for overload, short circuit, overcurrent, loss of voltage, undervoltage, grounding, leakage, automatic switching of dual power supplies and protection and operation of infrequent start of the motor.

Basic characteristics of circuit breaker:

(1) Rated working voltage Ue

The rated operating voltage refers to the nominal voltage of the circuit breaker, which can be operated continuously under the specified normal use and performance conditions.

China stipulates that at the voltage level of 220kV and below, 1.15 times of the rated voltage of the system is the high working voltage, and the voltage level of 330kV and above is 1.1 times of the rated voltage as the high working voltage. The circuit breaker can maintain insulation at the high operating voltage of the system, and can be closed and broken under specified conditions.

(2) Rated current In

The rated current refers to the current that can pass through the tripper for a long time at an ambient temperature of 40°C or less. In the case of circuit breakers with adjustable trippers, this is the current that can be passed through the trippers for a long time.

When used at an ambient temperature of more than 40°C, but not higher than 60°C, it is allowed to work with a reduced load for a long time.

(3) The current setting value of the overload tripper is Ir

If the current exceeds the current setting value of the tripper Ir, the circuit breaker will trip with a delay. It also represents the current that the circuit breaker can withstand if it does not trip. This value must be greater than the load current Ib, but less than the allowable current Iz of the line.

The thermal release relay Ir can usually be adjusted in the range of 0.7 - 1.0 In, but if electronic devices are used, the adjustment range is even larger, usually 0.4 - 1.0 In. For circuit breakers equipped with non-adjustable overcurrent off relays, Ir=In.

(4) The current setting value of the short-circuit tripper is Im

Short-circuit trip relays (transient or short-delayed) are used to trip the circuit breaker quickly in the presence of high fault current values with a trip threshold of Im.

(5) Rated short-term withstand current Icw

Refers to the value of the current that is allowed to pass through within an agreed time. This current value passes through the conductor within the agreed time and will not cause damage to the conductor due to overheating.

(6) Breaking capacity

The breaking capacity of the circuit breaker refers to the ability of the circuit breaker to safely cut off the fault current, which is not necessarily related to its rated current, and there are specifications such as 36KA and 50KA before. Generally, it is divided into limit short-circuit breaking capacity Icu and operating short-circuit breaking capacity Ics.

General principles for circuit breaker selection:

Firstly, the type and number of poles of the circuit breaker are selected according to the application; Select the rated current of the circuit breaker according to the high working current; Select the type of tripper, the type of accessory, and the size of the attachment as needed. The specific requirements are as follows.

1) The rated working voltage of the circuit breaker ≥ the rated voltage of the line.

2) The rated short-circuit on-off capacity of the circuit breaker calculates the load current ≥ the line.

3) The rated short-circuit on-off capacity of the circuit breaker ≥ the short-circuit current that may occur in the line (generally calculated according to the effective value).

4) The single-to-ground short-circuit current at the end of the line ≥ 1.25 times the instantaneous (or short-delay) tripping setting current of the circuit breaker.

5) The rated voltage of the circuit breaker undervoltage tripper is equal to the rated voltage of the line.

6) The rated voltage of the shunt tripper of the circuit breaker is equal to the control power supply voltage.

7) The rated working voltage of the electric transmission mechanism is equal to the control power supply voltage.

8) When the circuit breaker is used in the lighting circuit, the instantaneous setting current of the electromagnetic tripper is generally 6 times of the load current.

9) When the circuit breaker is used as the short-circuit protection of a single motor, the setting current of the instantaneous trip device is 1.35 times (DW series circuit breaker) or 1.7 times (DZ series circuit breaker) of the motor starting current.

10) When the circuit breaker is used as the short-circuit protection of multiple motors, the setting current of the instantaneous tripper is 1.3 times the starting current of one motor plus the working current of the rest of the motors.

11) When the circuit breaker is used as the main switch on the low-voltage side of the distribution transformer, its breaking capacity should be greater than the short-circuit current value of the low-voltage side of the transformer, the rated current of the tripper should not be less than the rated current of the transformer, and the setting current of short-circuit protection is generally 6-10 times of the rated current of the transformer; The setting current for overload protection is equal to the rated current of the transformer.

12) After the type and grade of the circuit breaker are preliminarily selected, it should be coordinated with the protection characteristics of the upper and lower switches to avoid skipping the level and expanding the scope of the accident.

Selectivity of the circuit breaker:

The circuit breakers used in the power distribution system can be divided into two categories: selective and non-selective according to their protection performance. Selective low-voltage circuit breaker with two-stage protection and three-stage protection. The instantaneous and short-delay characteristics are suitable for short-circuit operation, while the long-delay characteristics are suitable for overload protection. Non-selective circuit breakers are generally instantaneous and only used for short-circuit protection. Some of them are long-delay actions and are only used for load protection. In the power distribution system, if the upper circuit breaker adopts a selective circuit breaker, and the next circuit breaker adopts a non-selective circuit breaker or a selective circuit breaker, it is mainly to use the difference in the delay action or delay action time of the short delay trip device to obtain selectivity. When delaying the operation of the upper circuit breaker, please pay attention to the following issues.

1) Regardless of whether the next level is a selective circuit breaker or a non-selective circuit breaker, the setting current of the instantaneous overcurrent tripper of the upper circuit breaker shall generally not be less than 1.1 times of the large three-phase short-circuit current at the outlet end of the next level circuit breaker.

2) If the next stage is a non-selective circuit breaker, in order to prevent the short-circuit current from occurring in the circuit protected by the next level circuit breaker, the upper stage short-delay overcurrent tripper will act first because the instantaneous action sensitivity of this stage is not enough, so that it will lose its selectivity. Generally, the setting current of the short-delay overcurrent tripper of the upper circuit breaker is not less than 1.2 times that of the instantaneous overcurrent tripper of the next stage.

3) If the next stage is also a selective circuit breaker, in order to ensure selectivity, the short-delay action time of the higher-level circuit breaker is at least 0.1s longer than that of the next-level circuit breaker. Generally speaking, in order to ensure the selective action between the upper and lower low-voltage circuit breakers, the upper circuit breaker should choose an overcurrent tripper with a short delay, and its action current should be greater than the action current of the next level of overcurrent tripper, and at least the action current Iop.1 of the upper level is not less than 1.2 times of the action current Iop.2 of the next level, that is, Iop1≥1.2Iop.2.

Cascade protection of circuit breakers

In the design of the power distribution system, the selective coordination between the upper and lower stages of the circuit breaker must be "selective, fast and sensitive".

Selectivity is related to the coordination between the upper and lower circuit breakers, while rapidity and sensitivity are related to the characteristics of the protection appliance itself and the operation mode of the line, respectively.

If the upper and lower circuit breakers are properly coordinated, the fault circuit can be selectively removed to ensure that the other fault-free circuits of the power distribution system continue to work normally. On the contrary, it affects the reliability of the power distribution system.

Cascade protection is the specific application of the current limiting characteristics of the circuit breaker, and its main principle is to use the current limiting effect of the upper circuit breaker, and when selecting the lower circuit breaker, the circuit breaker with lower breaking capacity can be selected to achieve the purpose of reducing costs and saving costs. The upper current limiting circuit breaker QF1 can break the expected short-circuit current at its installation place, because the circuit breakers of the upper and lower levels in the power distribution system are installed in series, when a short circuit occurs at the outlet of the lower stage and the circuit breaker QF2, the actual value of the short-circuit current is much smaller than the expected short-circuit current at the upper level due to the current limiting effect of the upper circuit breaker QF1, that is to say, the breaking capacity of the lower circuit breaker QF2 is greatly enhanced with the help of the upper circuit breaker QF1, which exceeds its rated breaking capacity. There are also certain conditions for this cascade protection, such as the adjacent circuits must not have important loads (because once QF1 trips the QF3 circuit, there will also be a power outage), and the instantaneous setting value of QF1 and the instantaneous setting value of QF2 must also be properly matched. The cascade data can only be determined experimentally, and the mating selection of the upper and lower circuit breakers can only be determined by the circuit breaker manufacturer.
Selection and tuning of circuit breakers

More on that
Eaton introduces battery disconnect with the latest Breaktor circuit protection technology Eaton introduces battery disconnect with the latest Breaktor circuit protection technology

According to foreign media reports, power management company Eaton announced that its electric mobility (eMobility) business unit has launched a battery disconnect device (BDU), which can be combined with the upgraded Breaktor circuit protection technology to protect the electric vehicle (EV).

Superiority of power supply performance Superiority of power supply performance

Surge: Defined as an output voltage rms greater than 110% of the rated current and with a delay of one or more cycles. Power surges are mainly caused by the shutdown of large and medium-sized electrical equipment connected to the power grid, and the high voltage caused by the sudden unloading of the power grid. High pressure tip pulse: refers to the highest ...

Eaton's UPS Product Experience Center in Asia Pacific is newly unveiled, with four highlights revealed! Eaton's UPS Product Experience Center in Asia Pacific is newly unveiled, with four highlights revealed!

Recently, Eaton's UPS Product Experience Center in Asia Pacific was grandly opened at its BA1 facility in Shenzhen. As a global power management company with more than 100 years of accumulation, Eaton has always been committed to continuous innovation in "electrification + digitalization" technology. In the all-new UPS sub...

Eaton Completes $3.3 Billion Sale of Hydraulics Business Eaton Completes $3.3 Billion Sale of Hydraulics Business

Dublin, Ireland – Eaton (NYSE: ETN), a global power management company, announced on August 2, 2021 that it has closed the sale of its hydraulics business to Danfoss, a Denmark industrial company, for $3.3 billion. Eaton Hydraulics reported sales of $1.8 billion in 2020 ...

For the 15th consecutive year, Eaton has been named to the Top 100 Best Corporate Citizens For the 15th consecutive year, Eaton has been named to the Top 100 Best Corporate Citizens

CLEVELAND, United States — Eaton (NYSE: ETN), a global power management company, has been named to 3BL Media's Top 100 Best Corporate Citizens list for the 15th consecutive year. The list ranks companies in the Russell 1000 Index to recognize those who have demonstrated a strong track record in environmental, social and governance ( ...

Full of honors! Eaton has won four awards in China's electrical appliance industry Full of honors! Eaton has won four awards in China's electrical appliance industry

On June 9th, the "2023 China Electrical Appliance Industry Series White Paper" conference hosted by Gewu Zhisheng was held in Shanghai under the guidance of China Electrical Equipment Industry Association.

Eaton attended the 2021 Asian Women Leaders Summit to continue to promote women's development Eaton attended the 2021 Asian Women Leaders Summit to continue to promote women's development

SHANGHAI, China — Eaton, a global power management company, recently attended the 2021 Asia Women in Leadership Summit. Due to the impact of the epidemic, the venue of the summit was changed from Singapore to an online conference, and senior businessmen from various countries in the Asia-Pacific region ...

Eaton's E-Cube Gen II creates a new future of green and efficient data centers Eaton's E-Cube Gen II creates a new future of green and efficient data centers

If we compare the network to a pipe, and data to a stream of water, with the advent of the era of data explosion, the pipeline is getting wider and wider, and the water flow is getting bigger and bigger; On the other hand, a large number of use scenarios require local water intake and water storage, and how can the data center as a reservoir continue to provide a solid guarantee, ...

How to select Eaton AC contactors How to select Eaton AC contactors

Eaton contactor as a power supply equipment, the selection of contactors should be carried out according to the requirements of the controlled equipment, in addition to the rated working voltage and the rated working voltage of the controlled equipment is the same, the load power, use category, control mode, operating frequency, working life of the controlled equipment ...

Open innovation cooperation, Eaton signed a strategic cooperation agreement with Hainan Future Industrial Park Open innovation cooperation, Eaton signed a strategic cooperation agreement with Hainan Future Industrial Park

Shanghai, China — Recently, Eaton (China) Investment Co., Ltd. and Hainan Future Industrial Park Investment and Operation Holding Co., Ltd., with the great attention and strong support of the Hainan Provincial Party Committee, the Provincial Government and the Haikou Municipal Party Committee and Municipal Government, have reached a strategic agreement on building a zero-carbon smart park and serving the Hainan Free Trade Port.

Embracing the future, Eaton Aerospace provides a leading-edge power distribution system for Airbus CityAirbus Embracing the future, Eaton Aerospace provides a leading-edge power distribution system for Airbus CityAirbus

Eaton Corporation today announced that its Aerospace Group will provide products and services for the electrical power distribution system of CityAirbus, the world's leading aircraft manufacturer's next-generation electric vertical take-off and landing vehicle (e-VTOL). Eaton Aerospace's extensive experience in power management will help ...

Eaton Announces New Power Management Solution Eaton Announces New Power Management Solution

Eaton, a global power management company, today announced the launch of new power management solutions to support the green energy transition in the Asia Pacific (APAC) region. This includes an EV Charging Infrastructure (EVCI) solution suite, as well as a unique business and operational environment for the Asia-Pacific region.

Eaton Electric signed a strategic cooperation agreement with Shenergy Investment to help achieve the "dual carbon" goal Eaton Electric signed a strategic cooperation agreement with Shenergy Investment to help achieve the "dual carbon" goal

On October 13, 2022, Eaton Electric and Shenergy Investment (Shanghai Shenergy Investment and Development Co., Ltd.) signed a strategic cooperation agreement in Shanghai, under which the two parties will go deep into the fields of power distribution, microgrid and energy storage to build a new power system with new energy as the main body, and promote China's low-carbon transformation in the future.

Interference and treatment methods of frequency converters Interference and treatment methods of frequency converters

Methods to eliminate common-mode interference include: 1. Shielded twisted pair wire is used and effectively grounded. 2. Where there is a strong electric field, galvanized pipe shielding should also be considered. 3. Keep away from high-voltage wires when wiring, and do not bundle high-voltage power cables and signal wires together. 4 Don't share the same ...

Eaton proposes a total solution for cybersecurity Eaton proposes a total solution for cybersecurity

Shanghai, China – On October 28, 2019, Eaton, the global power management company, announced the launch of its "Current Thinking" radio series to examine emerging cyber threats in today's connected era. Among them, the radio program "Total Cybersecurity Solution" has been launched in ...

Test Methods for UPS Power Supplies (Unconventional) Test Methods for UPS Power Supplies (Unconventional)

The purpose of UPS switching power supply test is to meet the actual technical index requirements of UPS switching power supply, people usually carry out steady-state, dynamic and routine testing for UPS switching power supply test, in addition, there are other types of UPS switching power supply test content. UPS ...

Eaton's dual-brand UPS products ranked No. 1 in the Chinese market in 2019-2020 Eaton's dual-brand UPS products ranked No. 1 in the Chinese market in 2019-2020

Recently, in the "2019-2020 China UPS Market Research Annual Report" released by CCID, and the "2019-2020 China UPS Product Market Annual Report" released by ICTresearch, Eaton, a global power management company, relied on the outstanding performance of Eaton's dual-brand strategy of Eaton and Shante...

Eaton participated in the second annual Asian Women Leaders Summit to continue advocating for women's leadership Eaton participated in the second annual Asian Women Leaders Summit to continue advocating for women's leadership

Eaton attended the 2nd Asian Women Leaders Summit in China in 2019 Ms. Cally Wu, Vice President of Human Resources for Asia Pacific, represented the company at the summit and participated in the roundtable discussion Championing women's leadership is not about change, it's about continuous improvement Eaton Corporation is committed to ...

Eaton's CEO Releases 100th Anniversary Open Letter: Committed to Innovation, the Future Looks Bright Eaton's CEO Releases 100th Anniversary Open Letter: Committed to Innovation, the Future Looks Bright

2023 marks the 100th anniversary of Eaton's (ETN) listing on the New York Stock Exchange. At this momentous moment, Craig Amold, chairman and chief executive officer, released an open letter in which he reflected on Eaton's 100-year history and said: Eaton's employees have forged ...

What is a UPS power supply? What is the function of a UPS power supply? Let's take a quick look together What is a UPS power supply? What is the function of a UPS power supply? Let's take a quick look together

1. What is UPS power supply? UPS power supply is the abbreviation of UPS uninterruptible power supply, UPS is a kind of power protection equipment containing energy storage device, with inverter as the main component, voltage and frequency stabilization output. It is mainly composed of several parts, such as rectifier, battery, inverter and static switch.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top