Take the Schneider PLC with model number TWDLCAA40DRF as an example:
The first PWR: is the meaning of power supply;
The second RUN: is the PLC operation indicator; Long dark: The application is not fulfilling; Shine: The controller is in a stay or a mistake in performance; Solid on: the controller is in running condition;
The 3rd ERR: is the application fulfillment indicator; long dark: normal; Shine: The application is not fulfilled, or the fulfillment is faulty (suspended); Solid light: internal fault (watchdog, etc.);
The fourth STAT: is the system bit control of the user or application; It is rarely used. Long dark: controlled by the user or application through the system bit %S69; Shine: Invalid; Solid: Controlled by the user or application through the system bit %S69; This function allows the PLC to be controlled with other controllers;
The 5th BAT: is the external battery indication of the PLC; Long dim: the external battery is normal or the LED is stopped (the user or system is controlled by the system bit %S66); Shine: Invalid; Solid on: no external battery or low battery power, can also be controlled by system bit %S66;
The 6th COM: is the communication indication of the PLC communication port. Long dark: serial/485 communication is not used; Shine, PLC is in the state of communication data exchange;
|
More on that
|
Frequency converter and PLC connection problems - Schneider
When the inverter is used to form an automatic control system for control, in many cases, the PLC and the inverter are used together, and how to correctly connect the PLC and the inverter together has become the key to the success of the system.
1.PLC switch ...
|
|
Methods to reduce the interference of Schneider inverters themselves
When there are high-frequency impact loads such as welding machines, electroplating power supplies, electrolytic power supplies, or slip ring power supply near the power supply system of Schneider inverter, the inverter itself is simply protected due to interference. It is recommended that users choose the following methods:
...
|
|
Schneider touch screen touch deviation causes
(1) Problem--: Contact deviation
Phenomenon 1: The direction of the finger does not coincide with the mouse arrow.
Reason 1: After installing the driver, there is no vertical contact with the bullseye center when calibrating the alignment. Deal 1: Correct the position from the beginning.
Phenomenon 2: Some districts ...
|
|
Schneider online UPS power supply is energy-saving
1. The need for stability
When choosing UPS products, the customer's focus must be stability. For UPS, higher power means lower calorific value. Of course, only one of the primary factors that affect the internal temperature of the UPS is also to consider the heat dissipation planning of the machine itself.
...
|
|
Factors influencing the differential thermal analysis of instrumentation - Schneider
The operation of differential thermal analysis is simple, but in practical work, it is often found that the same sample is measured on different instruments, or different measurements are measured on the same instrument, and the results of the differential thermal curve of industrial electrical appliances are different. The high temperature, shape, area, and size of the peaks will all change. ...
|
|
Schneider switch socket authenticity
1. In terms of logo, the logo of the product is a sign of identity, so the genuine products will be very exquisite. The imitation is not very well handled on the logo, the plane contrast above the letter "A" is narrow, and even the top is directly pointed. We must pay attention to this point.
2. From ...
|
|
The difference between Schneider UPS and EPS power supply
1. Different safety standards
UPS is mainly used to protect users' equipment or business from economic loss, and its product technical certification mainly includes Thiel certification, CQC certification, etc. The development of EPS power supply stems from the sudden failure of the power grid, in order to ensure the power safety and fire linkage needs, it can be supplied immediately.
|
|
Schneider miniature circuit breaker model and parameter difference
Schneider miniature circuit breakers are commonly used in C65, C120, EA9, INT125 and other products.
Parameter differences:
N -------- breaking ability, N is 6000A, H is 10000A, L is 15kA
...
|
|
Pay attention to the problem of false load connection method in inverter debugging - Schneider
There are many novices who are not familiar with the fake load when repairing the inverter, and the repair of the inverter saves many of their modules with the false load, because the novice repairer generally does not know how to do this, and now the light is on to make it clear that the module is going to be broken. A false load is a resistor with a few hundred ohms ( ...
|
|
Solutions to Schneider drive fault codes
PHF: 1. The power supply of the inverter is not right or the fuse is blown; 2. There is a transient problem in a certain phase. 1. Check the power connection and fuse; 2. Reset.
USF: 1. Power supply voltage undervoltage; 2. Instantaneous voltage drop; 3. The load resistor is damaged. 1 Check the power supply voltage; 2 Substitutions ...
|
|
Servo motor selection process – Schneider
1. Load organization (acknowledging the type of tissue and its specific data, such as ball screw length, ball screw diameter, stroke, pulley diameter, etc.)
2. Form of action (acknowledging the form of action of manipulating the target, the relationship between time and speed; Will manipulate ...
|
|
The reason for the frequent tripping of Schneider leakage switches
1. Defective device
The lead wire of each pile head is not firmly connected and loosened for a long time, which will cause the pile to heat and oxidize, burn out the outer insulation of the wire, and announce sparks and burnt smell, forming undervoltage of the line, and the air switch action.
2. The leakage switch does not match the load
The actual electricity load of the home is large ...
|
|
Schneider UPS power supply installation steps
UPS power supply is widely used in shopping malls, supermarkets, banks and other enterprises and institutions, the primary effect of the power supply is to provide continuous power supply for the unit in the state of power failure, so as to ensure the normal operation of the computer network system and other application systems, and effectively avoid data loss. In the power supply ...
|
|
Schneider introduces the new Lexium28S servo
The newly launched Lexium28S Sercos III bus servo with BCH2 servo motor is available as a pre-order product portfolio to meet the needs of motion control and optimize the function of the machine. Lexium28S servo drives, available in 4 sizes, 10 models, power mask 0.05KW to 4 ...
|
|
Turbine flowmeter selection factor - Schneider
Turbine flowmeter is a kind of speed appearance, it has high precision, good repeatability, no zero drift, high range ratio, simple structure, few moving parts, high pressure resistance, wide measurement scale, small size, light weight, small pressure loss, convenient repair and other advantages, turbine flowmeter has high quality ...
|
|
Schneider PLC failure steps
(1) If the signal is controlled on a counter, first look at the logic that controls the reset, then the counter signal. Follow steps 2 to 5 above.
(2) If Schneider PLC aborts in some places where the output is encouraged, generally in the middle of the situation, then look for the next step ...
|
|
Schneider Lexium ILA all-in-one AC servo
The Schneider Lexium integrated drive consists of an electric motor and a control circuit that announces the control signal via a fieldbus, pulse/direction interface or I/O interface (for internal motion tasks).
High compactness: motor and control circuits ...
|
|
Inverter maintenance inspection steps – Schneider
1. Check whether the appearance of the inverter is in good condition, including whether the indicator light is in normal operation, whether the task control function of the operation panel is complete, and carefully observe the appearance of the inverter in operation conditions, and do the corresponding recording operations; When repairing the inverter, check whether the voltage value and current value exceed the allowable ...
|
|
Is there still an output after the UPS power is turned off?
1. After the UPS power supply is shut down, the output terminal is still powered, but the UPS power supply does not play a role at this time, and it is in a bypass state.
2. The power supply will not be cut off after the UPS power supply is shut down, because the UPS power supply will go bypass after the shutdown, there is still a mains power input at this time, ...
|
|
Frequency converters and their control – Schneider
AC inverter is the result of the high development of microcomputer and modern power electronics technology. The microcomputer is the center of the inverter, and the power electronics form the main circuit of the inverter. As we all know, the frequency of communication electricity sent from power plants is stable and constant, in our country it is 50 weeks per second ...
|
|