Tubular busbar structure layout - Wienal

Create Date: 2024-8-30 12:03:23|Source: Woehner/Wiehner

1. The tubular bus is in the form of a split-phase fully insulated shielded copper tube bus.

2. The cylindrical capacitor structure is selected, and the voltage equalizing capacitor layer, the main insulation layer, and the bottom layer of the shielding street are set between the conductor and the insulating sheath, and the shielding grounding layer on the outside is connected to the grounding grid. The quantity of each tier is confirmed by the seller based on the existing successful experience. The principle of setting is to make the electric and magnetic fields of the tube bus uniform and the surface point of the tube bus bar to zero.

3. The conductor is an oxygen-free copper tube with a purity of not less than 99.99%.

4. The uniform capacitance layer is made of semiconductor paper and semi-coated.

                                 Tubular busbar structure layout - Wienal

5. The shielding grounding layer is half-coated with copper foil, and the thickness is not less than 0.05mm. It is necessary to reinforce the grounding point.

6. The grounding lead is made of copper wire, and the useful cross-sectional area is not less than 6mm2.

7. The main insulating material is solid insulating silica gel or PTFE oriented film.

8. The insulating sheath of the grounding layer should be able to reliably avoid the intrusion of moisture and moisture. Heat-shrinkable insulating sleeves can be used, and their color should be the same as the color (A yellow, B green, C red). Two layers of heat shrinkable insulating sleeve are selected, the total thickness (shortened) is not less than 3mm, the joint (if any) is necessary to be staggered, and the lap length of the joint is not less than 100mm.

9. The large span of the suspension shall not exceed 6m.

10. Conductor appearance requirements: the end of the copper tube should be rounded, and the connecting surface of the end of the copper tube should be silver-plated or tin-plated to ensure low contact resistance and anti-corrosion function.

11. Terminal joint requirements: the two ends of the purple weave are pressed with copper end plates, the end plates are lubricated, the appearance is lubricated, and there are no edges and corners. It is necessary to have a current margin of 150% of the rated value for the conductive plate. The temperature rise of this part is lower than the conduction body temperature rise, and a sampling test should be done before leaving the factory.

12. Grounding requirements: it is necessary to be reliable grounding at the bottom of the all-phase insulated copper tube bus street, including the shielding insulating sleeve at the central joint, and the grounding mode is one point grounding (each section can be grounded independently) to avoid the grounding of the insulated copper tube bus wire at multiple points, and the circulation current occurs, so as to ensure that the external grounding layer meets the requirements of human safety contact; It is also necessary to reliably ground the metal outer sheath, if any.

More on that
Introduction to the Wiener 3-pole adapter Introduction to the Wiener 3-pole adapter

1、32590 EQUES®30Compact Bus adapter 32 A 1 adjustable support rail 45 x 160 with conductor AWG 10 (6 mm²) 2、32591 EQUES®30Compact Bus adapter 63 A 1 ...

Dense busbar installation – Wiener Dense busbar installation – Wiener

1. Requirements for civil engineering before installation 1) The foundation, structure, reserved holes and embedded parts all meet the design requirements of electrical equipment. 2) After the construction of the roof and floor slab is completed, there shall be no leakage. 3) After the indoor ground construction is completed, mark the ground leveling line on the well wall. ...

Common Bus Application Considerations – Wiener Common Bus Application Considerations – Wiener

  In the common DC bus system of multiple inverters, especially the common DC bus of inverters of different power levels, it is very important that the connection between the bus bars is maintained by fuses. When one of the inverter power equipment in the common bus is damaged by short circuit breakdown, the other inverter bus ...

Aluminum alloy busway circuit continuity - Wiener Aluminum alloy busway circuit continuity - Wiener

The continuity of the aluminum alloy bus duct maintenance circuit is related to the PE line, and the crossover PE wire conductor bus of the maintenance conductor and the two-unit bus bar should reach 50% of the phase line, the equivalent cross-sectional area. The continuity resistance of the housing and PE line maintenance circuit is ≤ 0.005 ohm female, and the unit with jumper wire is not less than the maintenance conductor.

Uses and characteristics of detached closed busbar - Wiener Uses and characteristics of detached closed busbar - Wiener

Closing busbars include out-of-phase shut-off buss, co-box (including co-box phase isolation) shut-off busbars and cable busbars, which are used for power plants, substations, industrial and civil power supply leads. Phase-off busbar 1. Usefulness Out of phase ...

Application advantages of industrial busway - Wiener Application advantages of industrial busway - Wiener

1. It has a modern beauty; 2. Small dimensions; 3. Strong and light weight, simple operation; 4. The connection is very simple (just like connecting water pipes, connecting sections through tees, elbows and other joints to make them into a system; ...

Rectangular busbar, trough busbar, and tubular busbar analysis Rectangular busbar, trough busbar, and tubular busbar analysis

The rectangular bus has good heat dissipation performance and is easy to fix and connect. But its skin effect is quite large. In order to reduce the skin effect, the cross-sectional area of a single busbar should not exceed 1250 square millimeters. When the working current exceeds the promised current of a single bus, 2 to 4 rectangular buses can be used. Rectangular conductor a ...

Connector box features of the busbar system – Wiener Connector box features of the busbar system – Wiener

1. Rapid device Today, busway adapters cannot be flipped at the time of installation, and the two busway sections are not out of phase when flipped when connected. 2. High protection level The coupling box has a protective function, ...

The difference between metal busbar and closed busbar - EVOC The difference between metal busbar and closed busbar - EVOC

The nature is different Busbar: It is a common path on which multiple devices are connected in the form of side-by-side branches. Busway: It is a closed metal equipment composed of copper and aluminum busbars. Different uses Mother...

Frequently Asked Questions for the Installation of Closed Busbars – Vernal Frequently Asked Questions for the Installation of Closed Busbars – Vernal

1. The cable in and out of the bridge is not piping 2. The orientation of the bridge grounding and crossing is incorrect, and the special grounding line of the spray or painted bridge device is not equipped with a special disc gasket 3. The fireproof board of the electric well is not fixed, and the fireproof plugging is not perfect 4. The bridge is opened at will, and no standard accessories are used.

The use of busbar systems – Wiener busbars The use of busbar systems – Wiener busbars

 First, this kind of small electrical equipment is a novel concept, adopting the "non-hole lap technology", and the electrical equipment is directly installed on the confluence bus system to form a power distribution or control loop. The representative creations are busbar device fuses and fuse load disconnectors. ...

Vernal fuse core Siemens fuse alternative Vernal fuse core Siemens fuse alternative

Due to the long delivery time of the Wiener melt core, whether the Wiener fuse can be replaced by Siemens' fuse, the answer is yes, so it is recommended to use Siemens' Rong Xin, which corresponds to the following 3NA38012C NH-Fuse NH-,00(0 ...

What is the difference between a Wiener busbar and a cable What is the difference between a Wiener busbar and a cable

The difference between busbar and cable The busbar is used to gather current. Many power and power supply circuits are connected to the bus, through which the power is gathered and sent to each circuit. Therefore, the current carrying capacity of the bus bar is relatively large, and the current carrying capacity of the bus ...

What are the common types of fuses - Wiener What are the common types of fuses - Wiener

Plug-in fuse: It is commonly used at the end of the line at the voltage level of 380V and below, as a short-circuit maintenance for distribution branch lines or electrical equipment. Spiral fuse: The upper end of the melt is covered with a fuse indicator, once the melt is melted...

Wiener busway specification standard parameters Wiener busway specification standard parameters

1. The standard scale of the bus duct This specification regulates the terminology, skill requirements and test methods of the insulated bus trunk system (bus duct) and its plug-in feed box (hereinafter referred to as the feed box). This specification specification applies to additional voltage AC to 660V...

Advantages of busbar mounted electrical equipment - Wiener Advantages of busbar mounted electrical equipment - Wiener

The novelty, flexibility and originality of the busbar device appliance. It indicates the vitality of this skill and its broad market prospects. This is the real reason why we pay attention to it. First of all, this small electrical appliance set ...

The way in which the Wiener high-voltage busway is selected The way in which the Wiener high-voltage busway is selected

In the selection, the following elements should be fully considered: fire protection specifications, insulation layer to flame retardant, good temperature resistance, high temperature is not easy to release harmful gases, structure type to avoid chimney effect, should give priority to the use of aggregate insulation layer bus duct, such as the use of air insulation type, it must be in the electric ...

Wiener fixed and busbar mounting Wiener fixed and busbar mounting

Precautions for the device VDE 0660 Specification Section 107 / EN 60947-3 Specification / IEC 60947-3 Specification 3 poles are broken at the same time, double breakpoints. Operator-independent, safe opening/closing, in position ...

Advantages of Wiener aluminum busway Advantages of Wiener aluminum busway

1. Reliable insulation method There is an insulating layer on the conductive row, and there is a certain air yard between the phase and the phase, and there is an insulating pad block limited by DMC data between the conductive row and the shell, triple insulation, to ensure that the insulation of the bus duct is full of certainty, especially in the humid environment.

A detailed description of the Wiener comb busbar and connection terminals A detailed description of the Wiener comb busbar and connection terminals

The Wiener comb busbars and connection terminals are available with QUADRON®CrossLinkBreaker in size 000/00 Recommended installation: Wire entry at the lower end of the NH-fuse disconnector through the comb busbar. In the installation position and ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top