What are the common cable management methods for Rittal cabinets – network cabinets?

Create Date: 2024-8-30 12:03:23|Source: Rittal/Rittal

1. The network cabinet distribution frame is fixed in place, the panel paper is loaded into the distribution frame on the front, and the tray is installed on the back.

2. Positioning of the management board, the direction of the management board should be determined before threading, so that the management board does not need to twist the direction in the process of cable management, and can be positioned.

3. Wire management board threading, next to the inlet in the computer room, adjust the direction of the board according to the direction determined by 2, and thread the double hinge wire into the cable management board in turn according to the line number, but we should pay attention to the fact that even if all the twisted pair wires pass through the cable management board, the cable management board should be close to the wire inlet, the purpose of this is actually to ensure that the twisted pair in the computer room can be all sorted.

4. Routing cable management first tie the twisted pair of twisted pair wires on the outer root of the cable management board with nylon cable ties through the management board, and then translate the cable management board in its own direction along the specified route, about 100mm, and then wrap the line on the outer root of the management board around the management board, continue to translate the management board about 200mm, and tie it with nylon cable ties at the root of the outer side of the management board, pay attention to the fact that each wire should be kept in the same position as the previous binding, and some lines are not allowed to be transferred from the outer layer to the inner layer, and the inner layer line is not allowed to be transferred to the outer layer; Pan in turn until you reach the patch panel.

5. The wiring harness is fixed, too heavy in the cable management, if you encounter the cable tie hole on the bridge or the cable tie board in the cabinet, you should tie the wire harness to the bridge or cabinet at the same time as the wiring harness, so as to avoid the wiring harness slipping;

6. Curved angle management: When a turn is encountered in the process of translation, the cable management board must be close to the turning angle, and the corner must be turned along the side, and the corner can not be tied and then pasted on the corner, which requires all the wiring harnesses to be tied on the spot, and can not be moved to the scene after binding in advance;

7. Bracket cable management: When the cable management board arrives at the bracket behind the distribution frame, first tie the wiring harness to the bracket, then pan forward, and bind the wiring harness once when it reaches the front of a module, and then separate the corresponding wire number of the module. This process should be equipped with 2 people: 1 person to divide the line, 1 person to pull the wire from the back of the distribution frame to the front of the distribution frame (if the module can be removed, then the line from the module hole to the front), and at the same time, 2 people to check whether the line number is consistent with the panel number on the distribution frame.

8. Complete the cable management: When the last wire is threaded to the front of the distribution frame, there is no longer a line in the cable management board, and the cable management of the cable is declared to be over.

9. Take the exited cable management board back to the inlet, use the cable management table of the next 24-port distribution frame, repeat 1-8 in turn, and complete the cable management of the next bundle of wires until all the multi-bundle cable management (branch cable management) is completed.
What are the common cable management methods for Rittal cabinets – network cabinets?

More on that
Rittal's new Maxi-PLS busbar system is launched! Rittal's new Maxi-PLS busbar system is launched!

In electrical switchgear, the external connection of high-current frame circuit breakers (ACBs) is usually achieved by connecting multiple cables per phase in parallel. When the conventional flat copper bar scheme is adopted, it is necessary to cut a number of bolt fastening holes on the standard copper bar to complete the connection of the cable.

Rittal Cables - Causes and countermeasures of line faults of power cables Rittal Cables - Causes and countermeasures of line faults of power cables

External damage: In the process of storage, transportation, laying and operation of cables, they may suffer external damage, especially the directly buried cables that have been run, and are prone to damage in the ground construction of other projects. Such accidents often account for 50% of cable accidents. In order to avoid such accidents, in addition to strengthening the cable ...

What you need to pay attention to when choosing a Rittal-like cabinet and a Rittal-like electrical cabinet What you need to pay attention to when choosing a Rittal-like cabinet and a Rittal-like electrical cabinet

In recent years, Rittal cabinets have been increasingly used in important equipment and projects at home and abroad. This brand from Germany Rittal cabinet has always been a tall image in the industry, the fine quality is fascinating, and the high price makes us prohibitive. With the agility of China's manufacturing industry...

Rittal cabinet - knowledge quiz of high and low voltage distribution cabinet (11-20) Rittal cabinet - knowledge quiz of high and low voltage distribution cabinet (11-20)

11. What is the definition and classification of secondary circuits? Answer: The secondary circuit is used to monitor the measuring instrument, control the operation signal, all the low-voltage circuits of the relay and automatic devices are called the secondary circuit, and the secondary circuit can be divided into (1) current circuit according to the power supply and use; (2) Electricity ...

What are the classifications of Rittal cabinets? What is the difference with a general cabinet? What are the classifications of Rittal cabinets? What is the difference with a general cabinet?

1. What are the classifications of Rittal cabinets? 1. According to the function, it can be divided into: fireproof and anti-magnetic cabinet, power cabinet, monitoring cabinet, shielding cabinet, safety cabinet, waterproof cabinet, safe, multimedia console, file cabinet, wall-mounted cabinet. 2. According to the scope of application, it can be divided into: outdoor cabinets, ...

Rittal Cables - What are the main contents of cables? Rittal Cables - What are the main contents of cables?

1. SYV: solid polyethylene insulated RF coaxial cable, coaxial cable, radio frequency signal transmission in wireless communication, broadcasting, monitoring system engineering and related electronic equipment (including comprehensive coaxial cable) 2. SYWV(Y): Physical Foamed Polyethylene Insulated Cable TV System Cable, Video ...

An introduction to the features of Rittal cabinet fans An introduction to the features of Rittal cabinet fans

Wide air volume range: 20-900m3/h Innovative diagonal flow fan and brushless DC EC motor technology for higher air flow and uniform distribution of cold air Comes with an interface module for controlling and monitoring fans The standard degree of protection is IP54, up to IP56 with a water spray cover ...

What are the advantages of Rittal enclosure processing – sheet metal cabinets? What are the advantages of Rittal enclosure processing – sheet metal cabinets?

1. The cabinet and chassis products provide space for power supplies, motherboards, various expansion boards, floppy disk drives, optical disk drives, hard disk drives and other storage devices, and these spare parts are firmly fixed through the internal supports, brackets, various chassis screws or clips and other connectors inside the cabinet and chassis.

How to set the temperature of the Rittal cabinet air conditioner SK 3332540 How to set the temperature of the Rittal cabinet air conditioner SK 3332540

1. Press and hold the H4 button for 5 seconds to enter programming mode and ST will be displayed on the screen. 2. Click the H4 button to display 35 on the screen, then click the H2 button to display Cod on the screen, and then click the H2 button continuously to display from 0 to 22 on the screen. 3. Click H2/H3 and press ...

A detailed presentation of Rittal's new smart electronic lock A detailed presentation of Rittal's new smart electronic lock

With the development of data centers in the direction of more intelligent and high reliability, the information stored in the servers in the IT cabinet is becoming more and more important, and the operation and maintenance of the data center needs to be able to manage the door opening of the cabinet more effectively to avoid server downtime caused by human factors. Traditional Mechanical Cabinet Locks ...

Rittal cabinets – judgment and handling of high-voltage switchgear closing faults Rittal cabinets – judgment and handling of high-voltage switchgear closing faults

Closing faults can be divided into electrical faults and mechanical faults. There are two types of closing methods: manual and electric. Failure to close manually is generally a mechanical failure. Manual can be closed, electric can not close is an electrical fault. 1. Protection action: The protection action has been analyzed in front to trip the switch. ...

What is the difference between a control cabinet and a distribution box? What is the difference between a control cabinet and a distribution box?

One. The nature is different Distribution box: There is a large amount of parameter data in the distribution box. It generally constitutes a low-voltage distribution box. Control cabinet: The control cabinet is to assemble the switch cabinet, measuring instruments, protection devices and auxiliary equipment in a closed or semi-enclosed metal cabinet or screen according to the requirements of electrical wiring.

Rittal Blue e+ cooling unit in the cooling of the Airbus A320 test plant Rittal Blue e+ cooling unit in the cooling of the Airbus A320 test plant

A new A320 Airbus aircraft must pass rigorous testing before it can be put into service, so to ensure a smooth flight, not only the aircraft itself needs to be protected from overheating, but also the test hardware needs to be properly protected. Airbus uses Rittal Blue e+ cooling units to make it ...

Rittal cabinets – heat dissipation and dust protection for electrical cabinets Rittal cabinets – heat dissipation and dust protection for electrical cabinets

1. Built-in air conditioner for heat dissipation The cabinet is equipped with a refrigeration system, the evaporator and power devices are installed inside the cabinet in a closed manner, and the condenser and compressor are placed in the external circulation air duct or outside the cabinet. Since the power unit is sealed in the cabinet, as long as the appropriate sealant is used ...

Rittal cabinets - judgment and handling of common faults in high-voltage switchgear Rittal cabinets - judgment and handling of common faults in high-voltage switchgear

1. Judgment and treatment of sudden tripping fault of high-voltage switchgear during operation 1) Fault phenomenon: The cause of this failure is the protection action. The high-voltage cabinet is equipped with protection against overcurrent, quick cut-off, gas and temperature. 2) Judgment method: judging the cause of the fault can be based on the relay off, remote ...

What are the main classifications of Rittal cables – power cables? What are the main classifications of Rittal cables – power cables?

Classified by voltage level According to the voltage level, it can be divided into medium and low voltage power cables (35 thousand volts and below), high-voltage cables (above 110 thousand volts), ultra-high voltage cables (275-800 thousand volts) and ultra-high voltage cables (1000 thousand volts and above). In addition, it can also be divided into AC ...

What are Rittal cabinets used for? What are Rittal cabinets used for?

1. The cabinet is generally made of cold-rolled steel plate or alloy to store the computer and related control equipment, which can provide protection for the storage equipment, shield electromagnetic interference, arrange the equipment in an orderly and neat manner, and facilitate the maintenance of the equipment in the future. Cabinets are generally divided into server cabinets, network machines, etc.

Rittal enclosures – what are the functions of the enclosure? Rittal enclosures – what are the functions of the enclosure?

The function of the cabinet is security Packing mission-critical IT equipment into lockable cabinets makes it easier for network administrators to limit the number of people who can flip out the cabinets. The function of the cabinet is heat dissipation Estimate how much heat your device is ...

Rittal cabinet - judgment and treatment of sudden trip fault in operation of high-voltage switchgear Rittal cabinet - judgment and treatment of sudden trip fault in operation of high-voltage switchgear

1) Fault phenomenon: The cause of this failure is the protection action. The high-voltage cabinet is equipped with protection against overcurrent, quick cut-off, gas and temperature. 2) Judgment method: The cause of the fault can be judged according to the relay card drop, remote signaling information, etc. After the action of gas and temperature protection in the high-voltage cabinet ...

Rittal cabinets – the cause of moisture in electrical cabinets Rittal cabinets – the cause of moisture in electrical cabinets

(1) The cause of moisture in the cabinet 1) Environment shutdown. The ring main unit or the opening and closing station itself is a closed environment, because of the poor ventilation conditions, it is easy to gather moisture and generate condensation, and there are many large buildings today in order to reduce the occupied area, the opening and closing station, the power distribution room is built in the basement. Cause...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top