Rittal cabinets – judgment and handling of high-voltage switchgear closing faults

Create Date: 2024-8-30 12:03:23|Source: Rittal/Rittal

Closing faults can be divided into electrical faults and mechanical faults. There are two types of closing methods: manual and electric. Failure to close manually is generally a mechanical failure. Manual can be closed, electric can not close is an electrical fault.

1. Protection action: The protection action has been analyzed in front to trip the switch. Before the switch is transmitted, the circuit has a fault protection circuit to make the anti-trip relay function. The switch trips immediately after closing. Even if the transfer switch is still in the closing position, the switch does not close again and jump continuously.

2. Protection failure: Now the high-voltage cabinet is set up with five anti-function, which requires the switch not to be in the running position or the test position can not be closed. That is, the position switch is not closed, and the electric cannot be closed. This kind of failure is often encountered during closing. At this time, the running position light or the test position light is not illuminated. Move the switch trolley slightly so that the limit switch can be closed to send power. If the limit switch is offset too far, it should be adjusted.

3. Electrical interlocking faults: In the high-voltage system, some electrical interlocks are set up for the reliable operation of the system. For example, in a single-bus segmentation system with two power supply inlets, it is required that only two switches can be combined between the two-way inlet cabinet and the bus connection cabinet. If all three are closed, there will be a danger of reverse power transmission. And the short-circuit parameters change, and the short-circuit current of parallel operation increases. (The interlocking circuit of the incoming cabinet is connected in series with the normally closed contact of the bus-linked cabinet, and the incoming cabinet can be closed in the open state of the bus-linked cabinet.) The interlocking circuit of the bus unit is connected in series with one normally open and one normally closed of the two incoming cabinets respectively, and then connected in parallel. In this way, it can ensure that the bus cabinet can only be powered when one of the two incoming cabinets is closed and the other is opened. When the high-voltage cabinet cannot be electrically closed, the first thing to consider is whether there is an electrical interlock, and it cannot be blindly closed manually. Electrical chain faults are generally improper operation and cannot meet the closing requirements. For example, although the incoming cabinet is divided and closed, the handcart in the opening cabinet is pulled out and the plug is not plugged in. If the interlocking circuit fails, you can use a multimeter to check the fault location. It is simple and convenient to use red and green lights to determine the fault of the auxiliary switch, but it is not very reliable. It can be determined with a multimeter check. The method of overhauling the auxiliary switch is to adjust the angle of the fixed flange, adjust the length of the connecting rod of the auxiliary switch, etc.

4. Control loop open circuit fault: In the control loop, the control switch is damaged, the line is broken, etc., so that the closing coil can not be powered. At this time, there is no sound of the closing coil moving. There is no voltage at either end of the measuring coil. The inspection method is to check the open path point with a multimeter.

5. Closing coil failure: Closing coil burning is a short circuit fault. At this time, there are peculiar smells, smoke, and shortening of insurance melting. The closing coil is designed for a short working time, and the power-on time should not be too long. After the failure of closing, the cause should be found in time, and the closing should not be repeated many times. In particular, the closing coil of the CD type electromagnetic operating mechanism is easy to burn out due to the large passing current and multiple closing. When repairing the fault that the high-voltage cabinet cannot be closed, the method of trial power transmission is often used. This method can eliminate line faults (except transformer temperature and gas faults), electrical chain faults, and limit switch faults. The fault site can basically be determined inside the handcart. Therefore, in the emergency treatment, it can be used to test the power transmission at the test position and replace the power transmission method of the spare handcart. This results in more with less and reduces the duration of power outages.
Rittal cabinets – judgment and handling of high-voltage switchgear closing faults

More on that
Rittal Cables – the principle of selection of power cables Rittal Cables – the principle of selection of power cables

1. Selection of wire and cable models When selecting wires and cables, it is necessary to consider the use, laying conditions and safety; For example, depending on the application, power cables, overhead insulated cables, control cables, etc. can be selected According to the different laying conditions, the general plastic insulated cable can be selected ...

The Rittal RiEDC series has been named the IT Solution of the Year 168 The Rittal RiEDC series has been named the IT Solution of the Year 168

The Rittal RiEDC series has been awarded Solution of the Year at the IT168 Technical Excellence Awards. The "Technical Excellence Award" is jointly judged by professional users of the big data industry, technical experts and the media, and its criteria are based on innovative solutions recognized by the market and customers, ...

Rittal cables – what are the types of industrial wires and cables commonly used? Rittal cables – what are the types of industrial wires and cables commonly used?

Industrial wires and cables include single-core wires and cables, rubber cables, shielded control cables, flame-retardant cables, fire-resistant cables, etc. Single-core wire and cable It means that there is only one conductor in the insulation layer, the common BV wire, and B represents the wiring; V stands for insulating polyvinyl chloride. Suitable for AC ...

Rittal cables – the meaning of the first letter in the number of the control cable Rittal cables – the meaning of the first letter in the number of the control cable

First of all, the number of the control cable often starts with the letter "C", which indicates that the control cable is specially designed to connect different sensors and control devices as a medium for signal transmission. This kind of cable can transmit data signals, and has a certain resistance to wear and chemical corrosion, so it is widely ...

Five hidden details you didn't know about Rittal cabinets and common Q&A Five hidden details you didn't know about Rittal cabinets and common Q&A

Five details that are easy to overlook: One of the hidden details: steel The most basic thing of a cabinet is to look at the steel, the Rittal standard cabinet is made of section steel, there are many masters who understand the cabinet to understand, the steel plate must be thick, just knock it with your fingers. General ...

What are the main problems in the practical application of Rittal cabinet air conditioners on the client? What are the main problems in the practical application of Rittal cabinet air conditioners on the client?

Through continuous big data analysis of 200,000 cabinet air conditioners installed and operated on the market, Rittal found that the main problems in the actual application of air conditioners on the client are as follows: 1. Lack of maintenance, resulting in clogged air conditioner filters, which in turn causes the air conditioner to stop running or ...

Reliability ceiling - Rittal and the maritime industry talk about China's "ship talk" Reliability ceiling - Rittal and the maritime industry talk about China's "ship talk"

The Age of Discovery, which began at the end of the 15th century, linked the world and was one of the most important historical steps in the process of human civilization. In the 21st century, in the development trend of global interconnection and China's intelligent manufacturing, the shipbuilding industry has ushered in high-energy development prospects.   Smart ships, low...

Rittal cabinets – the operation process of power outages in low-voltage distribution cabinets Rittal cabinets – the operation process of power outages in low-voltage distribution cabinets

1. Normal power transmission operation process of low-voltage distribution cabinet: 1. All load switches are disconnected, confirm that the switches have at least one breakpoint; 2. Confirm that the power switch is in the disconnected position; 3. Send the power supply to the operation circuit, and the status indication is normal; 4. The incoming switch is - isolated ...

Rittal air conditioner alarm code parsing Rittal air conditioner alarm code parsing

1. A01 system message: open the cabinet door Rittal air conditioner Cause: the position of the door opening and closing is incorrect; 2. A02 system message: the temperature in the cabinet is too high: the refrigeration capacity is too low or small; 3. A03 System Message: Filter Monitoring Cause: Dirty Filter Diagnosis ...

Rittal Cables – What do you need to pay attention to when wiring industrial control cables? Rittal Cables – What do you need to pay attention to when wiring industrial control cables?

1. The weight of the cable in the industrial control cable drag chain should be evenly distributed, so as to avoid accidents caused by uneven weight during operation, and the principle of distributing the cable is that the heavier one is located on both sides and the lighter one is located in the middle. All industrial control cables must be securely fastened to one end of the energy chain, so that ...

Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets

What is the role of a DC system in a substation? Answer: The DC system provides reliable DC power supply for control signals, relay protection, automatic devices and accident lighting in the substation, and also provides reliable operating power for operation. The reliability of the DC system has a significant impact on the ...

Rittal cables – measures to prevent or mitigate electrical interference Rittal cables – measures to prevent or mitigate electrical interference

1. One spare core of the control cable is grounded It has been proved in practice that when a spare core in the control cable is grounded, the amplitude of the interference voltage can be reduced to 25%-50%, and the implementation is simple, and the cost of the cable is increased very little. 2. Serious consequences will occur when electrical interference is generated.

Rittal enclosures – what are the functions of the enclosure? Rittal enclosures – what are the functions of the enclosure?

The function of the cabinet is security Packing mission-critical IT equipment into lockable cabinets makes it easier for network administrators to limit the number of people who can flip out the cabinets. The function of the cabinet is heat dissipation Estimate how much heat your device is ...

Rittal cabinets – what are the steps in the cabling of the cabinet? Rittal cabinets – what are the steps in the cabling of the cabinet?

1. The first is to measure how long the line is. According to the decision is to put the location of the distribution frame, and then combine the distance of the cable from the outside into the cabinet and so on to calculate how long the network cable needs to be put on the distribution frame and install the cabinet, so as to facilitate the overall cable management behind.

Rittal Blue e+ cooling unit in the cooling of the Airbus A320 test plant Rittal Blue e+ cooling unit in the cooling of the Airbus A320 test plant

A new A320 Airbus aircraft must pass rigorous testing before it can be put into service, so to ensure a smooth flight, not only the aircraft itself needs to be protected from overheating, but also the test hardware needs to be properly protected. Airbus uses Rittal Blue e+ cooling units to make it ...

Rittal Cables - Introduction to the performance characteristics of control cables Rittal Cables - Introduction to the performance characteristics of control cables

1. DC resistance: 20°C, 0.4mm copper wire, less than or equal to 148Ω/km, 0.5mm copper wire, less than or equal to 95Ω/km. 2. Insulation electrical strength: 1min 1kv between conductors does not break down, conductors and shields 1min 3kv do not break down 3. Insulation resistance: each core and the rest of the core ...

Rittal Cables – precautions for the installation and wiring of control cables Rittal Cables – precautions for the installation and wiring of control cables

Precautions for the installation and wiring of control cables: 1. Under the eaves. Cables can only be used if they are not directly exposed to sunlight or ultra-high temperatures, and it is recommended to use pipes. Ultraviolet (UV) – Do not apply cables without UV protection to direct sunlight rings ...

Rittal cables – the performance difference of control cables Rittal cables – the performance difference of control cables

The control cable has the characteristics of moisture-proof, anti-corrosion and anti-damage, and can be laid in tunnels or cable trenches. Power cables are used to transmit and distribute high-power electric energy in the main line of the power system, and the control cable transmits the electric energy directly from the distribution point of the power system to the power supply of various electrical equipment and appliances.

Rittal Cables – what are the ways to lay wires and cables? Rittal Cables – what are the ways to lay wires and cables?

1. Buried laying The laying method of laying the cable immediately underground is called buried laying. The buried cable must be armored cable and anti-corrosion coating protection cable, and the bare cable cannot be buried. Generally, the depth of the cable trench shall not exceed 0.9m, and the buried laying shall be paved ...

Rittal Cabinet - Knowledge Quiz of High and Low Voltage Distribution Cabinet (51-60) Rittal Cabinet - Knowledge Quiz of High and Low Voltage Distribution Cabinet (51-60)

51 What are the factors that affect the degree of harm to the human body caused by electric shock? Answer: Factors such as the magnitude of the current, the duration of the current, the path of the current, the resistance of the human body and the frequency of the current. 52 Types of electric shock? Answer: Direct electric shock, indirect electric contact, inductive ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top