Inverter selection and capacity matching - Schneider

Create Date: 2024-8-30 12:03:23|Source: Schneider/Schneider

In addition, it is unscientific to select the inverter body alone, without considering whether the inverter selection and capacity matching are appropriate.

                               Inverter selection and capacity matching - Schneider

So what exactly to do?

1. Select the inverter according to the load characteristics.

Second, when selecting the inverter, the current value of the practical motor should be used as the basis for the selection of the inverter, and the additional power of the motor can only be used as a reference. Secondly, it should be fully considered that the output of the inverter contains higher harmonics, which will form the power factor and power of the motor will deteriorate.

3. When the inverter wants to work with a long cable, the inverter should be expanded by one gear or the output reactor should be installed at the output end of the inverter.

4. When the inverter is used to control several motors connected in parallel, it must be considered that the sum of the length of the cable from the inverter to the motor is within the allowable range of the inverter.

5. For some special application occasions, such as high ambient temperature, high switching frequency, high altitude, etc., it will cause the derating of the inverter at this moment, and the inverter needs to be expanded by one gear.

6. When selecting the inverter for high-speed motors, it should be slightly larger than the inverter of ordinary motors.

7. When the inverter is used in a pole changing motor, full attention should be paid to selecting the capacity of the inverter, so that its maximum additional current is below the additional output current of the inverter.

8. When driving the explosion-proof motor, the inverter does not have an explosion-proof structure, and the inverter should be set up outside the dangerous place.

9. When the inverter is used to drive the gear reducer motor, the application range is limited by the smooth way of the gear rolling part. Do not exceed the maximum speed tolerance.

10. When the inverter drives the wound rotor asynchronous motor, most of the existing motors are used. It is easy to overcurrent tripping due to ripple current, so it is necessary to select an inverter with a slightly larger capacity than usual.

11. When the inverter drives the synchronous motor, the output capacity is reduced by 10%-20% compared with the power frequency power supply.

12. In the case of loads with large torque fluctuations such as compressors and vibrating machines and peak loads such as hydraulic pumps, the working conditions of the power frequency should be understood, and the inverter with additional output current greater than its maximum current should be selected.

13. When the inverter controls the roots blower, because its starting current is very large, we must pay attention to whether the capacity of the inverter is large enough when selecting the inverter.

14. When selecting the inverter, we must pay attention to whether its protection level matches the situation on site.

15. Single-phase motors are not suitable for inverter drive.

If there is only the high reliability of the inverter body, and the inverter selection and capacity matching are not appropriate, the frequency conversion speed regulation system composed of it is impossible to achieve high reliability, or even unable to work, so how to ensure the normal and efficient operation of the frequency conversion adjustment system?

We want to make sure that the capacity of the inverter is matched. First of all, according to the nature of the load, the correct selection of the type of inverter. The general principle is what nature of the load characteristics with what characteristics of the inverter.

(1) Constant torque production equipment - within the speed regulation range, the load torque is basically constant. A frequency converter with constant torque function should be selected. It can only be overloaded for 150% of the additional current to be held for 1 minute.

(2) Square torque production equipment - within the speed regulation range, the load torque is proportional to the square of the speed, that is, M∝n2, centrifugal fan, water pump is its typical representative. The inverter with M∝n2 characteristics can have a small overload, and the additional current of 110%-120% is overloaded for 1 minute.

(3) Constant power load production equipment - within the speed regulation range, the speed is low and the torque is large; The rotational speed is high and the torque is small. Typical equipment such as machine tools and winding mechanisms.

More on that
Schneider seizes the opportunity of e-commerce Schneider seizes the opportunity of e-commerce

Beijing, China, 24 August 2021 – Looking at the history of the logistics industry, the changes brought about by the development of e-commerce in recent years are rare. According to Digital Commerce 360, in 2020, United States customers spent $861.12 billion online, a year-on-year increase.

The difference between high voltage and low voltage of Schneider inverter The difference between high voltage and low voltage of Schneider inverter

1. What is the difference between high-voltage inverter and low-voltage inverter? Frequency converters can be broadly divided into two categories: high-voltage frequency converters and low-voltage frequency converters. In terms of use, the applicable objects are different, and the high-voltage motor is the same from the principle of speed regulation. From the topology ...

The inverter has a problem supplying power to the motor – Schneider The inverter has a problem supplying power to the motor – Schneider

A frequency converter is a device that converts power to other frequencies of power supply. The power frequency of our country is 50Hz, in the field of motors, in order to change the speed of the motor, or other performance changes, many motors choose inverter power supply. The inverter is a supporting operation with the inverter motor.

Introduction to the transformer connection group - Schneider Introduction to the transformer connection group - Schneider

In the transformer planning process, the choice of wiring method is often not paid attention to. The three-phase transformer has A/B/C three-phase winding on the 1/2 side. The connection between them has a great impact on the operation performance of transformers, especially distribution transformers, and directly affects the quality of power supply. Therefore, the wiring ...

Schneider AC contactor precautions Schneider AC contactor precautions

There are many series of contactors: LC1-SK series: below 6ALC1-K series: 6A-16ALC1-D series: 9A-150ALC1-F series: 115A-800ALC1-B series: 750A-1800A When installing, it should be in accordance with the regulations...

Schneider Electric inverter applications Schneider Electric inverter applications

Schneider inverter, the full name of "Schneider communication inverter governor", is a well-known inverter brand developed, manufactured and sold by Schneider Electric Group in France. It is mainly used to control and regulate the speed of three-phase communication asynchronous motor, with its stable performance, rich combination functions, outstanding ...

Schneider Lexium ILA all-in-one AC servo Schneider Lexium ILA all-in-one AC servo

The Schneider Lexium integrated drive consists of an electric motor and a control circuit that announces the control signal via a fieldbus, pulse/direction interface or I/O interface (for internal motion tasks). High compactness: motor and control circuits ...

Schneider XPS safety control module selection method Schneider XPS safety control module selection method

(1) Evaluate the safety control level that the machinery and equipment need to reach (2) Confirm the type of input signal to be monitored and (3) the number of input signals that need to be monitored (4) The number and type of channels that the module needs to output (5) Whether it is necessary to control the output device (such as ...

Precautions for the selection of Schneider foot switches Precautions for the selection of Schneider foot switches

The foot switch series is XPE, and it should be noted when selecting: 1) Raw materials: metal and plastic, which are used in heavy-duty, high-risk, light-duty, low-risk occasions. 2) Pedal: divided into single pedal and double pedal (type end plus D). 3) With or without maintenance cover ...

Schneider inverter ATV61 OPF failure analysis Schneider inverter ATV61 OPF failure analysis

Q: 250KW ATV61 with 250KW fan, when decelerating to low speed, OPF (motor missing three-phase) problem will be reported occasionally. There are no contactors or switches between the inverter and the motor. Answer: This situation seems to be a problem with the inverter, which is a false alarm. Not really! The fan is decelerating ...

How to choose a Schneider circuit breaker? How to choose a Schneider circuit breaker?

First, calculate the value of the current of each branch (1) Purely resistive loads, such as bulbs, electric heaters, etc., are directly divided by the indicated power by voltage, that is, the formula I = power/220v; For example, a 20w bulb, branch current I=20W/220=0.09A electric air ...

The protection function of the inverter - Schneider The protection function of the inverter - Schneider

Protective functions can be divided into the following two categories: (1) After detecting the abnormal situation, the correction action is automatically carried out, such as overcurrent loss speed avoidance, regeneration overvoltage stall avoidance. (2) After detecting the abnormality, the PWM control signal of the power semiconductor equipment is closed, so that the motor automatically stops. As...

Schneider Vijeo-Designer compilation error factor Schneider Vijeo-Designer compilation error factor

Q1833: Because you are using an older version of Runtime, the download does not last. Please use the Runtime Device program on the Vijeo Designer CD to upgrade the runtime. When you download to an older runtime ...

Circuit breaker mechanical characteristics tester operation steps - Schneider circuit breaker Circuit breaker mechanical characteristics tester operation steps - Schneider circuit breaker

Circuit breaker action time test. The closing and opening control lines of the circuit breaker mechanical characteristics tester are respectively connected to the secondary control line of the circuit breaker, and the lead wires of each break of the circuit breaker are connected to the mechanical characteristics of the circuit breaker with the test wiring.

The difference between the highest frequency and the basic frequency of the inverter - Schneider The difference between the highest frequency and the basic frequency of the inverter - Schneider

1. There are two ways to say the fundamental frequency: (1) The frequency corresponding to the maximum output voltage of the inverter is called the fundamental frequency; (2) When the output voltage of the inverter is equal to the additional voltage, the minimum output frequency is called the fundamental frequency. The fundamental frequency is expressed in fBA. ...

Features of Schneider explosion-proof inverter box Features of Schneider explosion-proof inverter box

1. Aluminum alloy shell or steel plate welding, surface spraying; 2. Built-in inverters, circuit breakers, signal lights and other components produced by domestic or Schneider and other companies; 3. It is mainly adjusted by changing its output frequency to adjust the speed of ordinary three-phase asynchronous motor, so as to reach the production process.

Schneider diode selection experience and substitution method Schneider diode selection experience and substitution method

1. Selection of detection diode Point-contact germanium diodes are generally used for detection diodes, such as 2AP series. When selecting, the detection diode with high operating frequency, small reverse current and large forward current should be selected according to the specific requirements of the circuit. Although the detection and rectification of ...

Dynamic phase angle tuning of inverter motors – Schneider Dynamic phase angle tuning of inverter motors – Schneider

1. The control cabinet, the main engine, and the brake connection line are correct, and the voltage is correct; 2. Safety circuit, door lock circuit is normal, limit switch, speed change switch and close; 3. The connection cable from the encoder to the PG card must be reliable and accurate; ...

Design and calculation method of inverter braking resistance - Schneider Design and calculation method of inverter braking resistance - Schneider

1. The number of braking resistor boxes is roughly calculated as: motor power (KW)/11.2 (take the upper limit of the integer). 2. The selection of the power of the braking unit is generally (1-2) times the power of the inverter; 3. The function of braking resistor ...

Calculation method of inverter capacity - Schneider Calculation method of inverter capacity - Schneider

1. Accounting of inverter capacity when the load is continuously changed periodically In many cases, the load of the motor changes periodically. Obviously, in this case, picking the capacity of the inverter according to the minimum load will be overloaded, and it will be uneconomical to select according to the maximum load.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top