For the dual requirements of anti-interference and galvanic isolation, the pre-circuit of the output current detection or voltage detection of the inverter usually uses the "matching" circuit of the linear optocoupler device and the differential amplifier to complete the transmission mission of the detection signal. The circuit of the differential amplifier takes the current detection circuit as an example, when R1 = R3, R2 = R4, and the differential input signal is zero (shutdown condition), the output is "virtual ground" at the moment, which is 0V, if it is not 0V, it means that there is a problem with the circuit at this stage, and the abnormal alarm after powering on may be here.
Inverter differential amplifier overhaul method
Example 1
The telegraph OC is faulty, and the 5, 6, and 7 pins of N1 are all 2V. Pin 7 is not 0V for the alarm reason.
1. The "imaginary short" rule of the amplifier is still established, and the N1 chip is good to judge, but the fault is in the bias circuit.
2. Further analysis, at this moment, the differential amplifier has been transformed into a voltage follower
It is judged that R3 is broken, virtual welding, or the resistance value is severe. One end of R3 was measured to be soldered, and the recovery was normal after repair welding.
Example 2
The problem is the same as above. Pin 5 is 2V, pin 6 is 2.5V, and pin 7 is -13V.
1. The "imaginary short" rule of the amplifier cannot be established, but it still conforms to the rule of voltage comparators.
2. Further analysis, at this moment, the differential amplifier is transformed into a voltage comparator
The N1 chip is judged to be good, but the fault is R4 open circuit or virtual soldering, which damages the closed-loop condition of the amplifier, so that the amplifier is transformed into a voltage comparator. The resistance value of the online detection R4 has become severely larger, and the circuit is now broken after removing the detection, and the recovery is normal after replacement.
Example 3
The problem is the same as above. Pin 5 is 0V, pin 6 is 0V, and pin 7 is -10V.
1. The "virtual short" of the amplifier and the "virtual ground" rule of the inverting amplifier are still established, and the N1 chip is good.
2. Further analysis, at this moment, the differential amplifier is transformed into an inverting amplifier
The fault is R1 open circuit or virtual welding, which causes the input signal voltage loss at the inverting input terminal, while the 2.5V at the inverting input terminal is amplified by four times the inverting phase. Check that R1 has a virtual welding phenomenon, and the fault is removed after the repair welding.
Example 4
The problem is the same as above. Pin 5, 6 and Pin 7 are all 2.5V.
1. The "virtual short" rule of the amplifier is still established, and the N1 chip is good.
2. Further analysis, at this moment, due to the abnormal voltage divider circuit at the inverting input terminal, the "output virtual ground" condition of the original differential amplifier is damaged. Therefore, the output voltage rises from 0V to 2.5V.
The fault is R2 open circuit or virtual welding, which causes the input voltage of the inverting input terminal to rise. The measurement is as discriminant, and the output of N1 is normal after replacing R2.
Example 5
The problem is the same as above. The pin voltage is 2V, pin 6 is 0.4V, and pin 7 is -8V.
1. The "imaginary short" rule of the amplifier cannot be established.
2. The N1 chip is no longer compatible with the principle of the comparator, and it becomes unreasonable to be completely "undutiful". No, the N1 chip is now broken, and there is no need to check the peripheral components to identify it. Replace the N1 chip and recover to work normally.
|
More on that
|
Inverter protection and braking force issues – Sunland
1. What is regenerative braking?
If the motor decreases the command frequency during operation, the motor becomes an asynchronous generator and works as a brake, which is called regenerative (electrical) braking.
2. Can you get more braking power?
Regenerated from the motor ...
|
|
Inverter with no-load operation and debugging - Hope Sunland
The following four steps are very important for the commissioning of the inverter with the machine (i.e., connected to the motor) and no-load (i.e., the motor without load).
(1) Set the power of the motor, the number of pole pairs, and check the operating current of the inverter.
( ...
|
|
Precautions for the selection of exhaust fan inverter - Senlan
1. Whether it has perfect maintenance function
There will be many problems in the production process of the equipment, and if you want to prevent accidents, the equipment must have a perfect maintenance function, so as to prevent the loss of the enterprise. Therefore, when buying an exhaust fan inverter, you need to understand the safety function of the equipment first.
|
|
I hope that Senlan will make a wonderful appearance at the 22nd (Shanghai) Industry Fair
From September 15th to 19th, the 22nd China International Industry Fair was held at the National Convention and Exhibition Center (Shanghai). As the first national industrial exhibition held under the normalization of epidemic prevention and control this year, the theme of this expo is "Intelligence, Interconnection: Enabling the New Development of Industries".
|
|
Sunland inverters are designed for environmental requirements
1. The ambient temperature ---- is generally "-10-+40°C"; Derating between 40 and 50°C, the additional output current must be reduced by 1% for every 1°C increase. If the ambient temperature is too high and the temperature changes greatly, the insulation of the inverter will be greatly reduced, which will affect the life of the inverter.
...
|
|
The main circuit of the inverter application - Sunland inverter
Between the power supply and the inverter, there is a circuit breaker QF and a communication touch device KM, when the inverter does not have to for a long time. or when the equipment is overhauled, the circuit breaker is used as an isolation switch, which can block the power supply and ensure the safety of maintenance. At the same time, the circuit breaker has maintenance functions such as overcurrent and undervoltage. The main circuit of the inverter can ...
|
|
Inverter-related knowledge - Senlan inverter
1. What does open-loop mean in the use of inverters?
The speed detector (PG) is installed on the motor equipment in operation, and the speed response of the actual speed is sent to the control equipment, which is called "closed loop", and the speed detector that does not use PG is called "open loop". Most general-purpose drives are open-loop ...
|
|
Frequency conversion speed regulation of several special motors - Senlan frequency converter
A. Wound rotor asynchronous motor
The rotor winding of the wound rotor asynchronous motor is a set of three-phase windings with star connection. The end points of the three-phase winding are connected to the three collector rings, which are connected to the brushes and the external resistor (for starting or speed regulation) through the collector rings. Select inverter ...
|
|
The servo motor is connected to the wrong wire and causes a problem - Senlan
If the three power cables of the servo motor (SM) are not connected correctly, there may be no alarm in the static state. But as soon as the motor is operated manually or actively, the motor jumps off or starts to flutter, such as jumping when the speed is added too high, the system will issue generalized faults, etc.
|
|
Sunland won the "well-known brand of China's domestic inverter" for the fifth time in a row
On April 15, 2011, the "Century Tour of China's Automation Industry (CAIE2011)" was held in Beijing, and Sunland inverter was once again re-elected as "China's well-known brand of domestic inverter". Dr. Chen Bin, President of Continental Hope Group and Chairman of Hope Sunland Technology Co., Ltd., personally ...
|
|
The inverter is regularly replaced with the device - Sunland inverter
1. Cooling fan
As a prerequisite for ensuring the normal operation of the inverter, efficient and fast in-line cooling fans have become an indispensable conversion configuration of the inverter. Because of the wear of the internal bearings of the cooling fan and the reduction of the grease function in the process of application, the cooling of the fan.
|
|
Wiring specification of inverter control cabinet - Senland
The signal line and the power line must be routed separately: when using the analog signal to remotely control the inverter, the signal line of the control inverter and the strong current circuit (main circuit and sequential control circuit) can be separated from the inverter and other equipment to the analog interference, and the interval should be more than 30cm. Signal ...
|
|
Precautions for inverter wiring - hope Senlan
1. The inverter itself has strong electromagnetic disturbance, which will disturb the operation of some equipment, so we can add a cable sleeve to the output cable of the inverter.
2. The control line in the inverter or control cabinet is spaced at least 100mm, and the power cable is at least 100mm.
3. In the purchase of inverter ...
|
|
Switching power supply failure maintenance - Senlan
In the process of repairing the switching power supply, the step-down method can be selected. The method is: by connecting the power plug of the display to a communication voltage regulator, and then adjusting the output voltage of the voltage regulator to about 100V, and then repairing it with electricity, and gradually improving the power supply voltage for repair. ...
|
|
The reason for adding a frequency converter to the crane control system - Senland
Prior to the introduction of frequency converters, overhead crane operators operated the cranes using contactor-based controls. For low-cycle cranes, the system is equipped with a single or two-speed motor. For cranes with higher load cycles, they use so-called wound rotor motors.
...
|
|
Measures to prevent overvoltage of inverter - Sunland inverter
Depending on the cause of overvoltage, the countermeasures adopted are different. Regarding the overvoltage phenomenon that occurs in the parking process, if there is no special requirement for the parking time or direction, then the extension inverter deceleration time or free parking method can be selected to solve it. The so-called free parking ...
|
|
The eight forbidden areas of inverter control loop wiring - Senlan
1. The wires of the inverter control circuit should be strictly distinguished from the main circuit cable (power line) and placed separately. This will help prevent the inverter's control circuit from being disturbed by harmonics in the inverter's main circuit.
2. To separate the connection of the inverter from the terminals or contacts of other control circuits, ...
|
|
The key points of the use of inverter - Sunland inverter
In order to ensure the safe, efficient and reliable operation of the inverter, the following keys should be grasped when using the inverter:
1) It is necessary to reliably ground the grounding terminal of the inverter, so as to effectively press the radio frequency disturbance and enhance the reliability of the system.
|
|
The reason for the low output voltage of the inverter - Senlan inverter
1. The power supply voltage is low
The solution is to preset the active voltage adjustment function of the inverter, so that when the frequency is low and the rated frequency is dry, the inverter has the function of active voltage stabilization, and if the output voltage is low, the inverter will actively increase the output voltage
...
|
|
Motor inspection and maintenance, motor problems - Senlan
1: In the operation of the motor, if dust, water stains and other debris enter its interior, it will constitute a short-circuit medium, which can damage the wire insulation layer, form an inter-turn short circuit, increase the current, increase the temperature and incinerate the motor. Therefore, dust, water stains and other debris should be prevented from entering the motor.
|
|