The role of the "communication input reactor" of the inverter input device is mainly to improve the power factor of the communication power supply on the communication side of the input side; It is useful to eliminate the higher harmonics on the input side to avoid damage to other electrical equipment caused by voltage distortion; Eliminate the input current imbalance caused by the imbalance between the phases of the three-phase communication power supply.
Generally, when adding a communication input reactor, an "EMC input filter" should be installed on the input side of the inverter, which is primarily to reduce the external conduction and radiation of the inverter itself to the greatest extent.
Domestic inverters are basically adapted to the motor capacity of 37kw (50HP), the power input capacity of 114kvA, the input current of 157A, and the output current of more than 150A inverter, all of which are equipped with standard external DC reactors, and the models of the DC reactors equipped with them need to be adapted according to different powers.
The user needs to remove the short-circuit copper bar between the main circuit terminal P and (+) of the inverter when installing, and then connect the DC reactor between P and (+), and there is no polarity between the reactor terminal and the terminal O (+) of the inverter. When a DC reactor is installed, the short-circuit copper bar between P and (+) is no longer used.
The DC reactor is connected in series inside the inverter between the rectifier module and the filter capacitor. It works to improve the power factor on the input side; Improve the efficiency and thermal temperature of the inverter; It is useful to eliminate the influence of higher harmonics on the input side on the inverter, and reduce the external conduction and radiated electromagnetic disturbance of the inverter itself.
The "communication reactor" is close to the inverter device between the output side of the inverter and the drag motor. Its primary function is to filter the inrush current of the input side circuit to weaken the overcurrent impact of the power supply voltage imbalance on the inverter; Generally, the distance between the inverter and the motor is more than 100 meters, and it is recommended to install an output communication reactor. Because the output side of the inverter generally contains more higher harmonics. When the motor and the inverter are far apart, because there is a large distributed capacitance in the cable wire, a certain harmonic may resonate in the circuit, which will cause great damage to the insulation performance of the motor, and the motor will be damaged for a long time. In addition, because the line is long, a large leakage current will occur, which will cause frequent protection shutdown of the inverter.
|
More on that
|
Problems in the inverter application – Delta inverters
1. Harmonic problems
The equipment that plays the role of switching in the main circuit of the inverter must generate harmonics in the process of turning on and off the circuit. The lower harmonics generally have a greater impact on the motor load and cause torque ripple; The higher harmonics increase the leakage current of the inverter's output cable, making ...
|
|
Precautions for Delta inverter C2000 series
1. Precautions for choosing a communication motor driver
When using a large-capacity current transformer (more than 600kVA) and a phase-entering capacitor, the surge current on the input side of the power supply is too large, which may destroy the input side of the communication motor driver.
|
|
The principle structure of low-voltage circuit breaker - Delta
Low-voltage circuit breakers, commonly known as active air switches, are one of the primary electrical switches in low-voltage distribution networks. It can not only turn on and off normal load current, motor operation current and overload current, but also turn on and off short circuit current.
It is mainly used as a low-voltage distribution line or a switch cabinet that is not often operated ( ...
|
|
A brief description of the selection of Delta inverters
Delta's inverter series are as follows:
1:VFD-EL,VFD-S,VFD-L,VFD-C200
Voltage 220V, 380V, power scale 100W-7.5kw
The above series are Delta's simple inverters, commonly known as economical inverters, which are used for small fan pumps, food and medical ...
|
|
When the Delta inverter is powered on, the uptube drive voltage is established
One is hardware, similar to the CPU reset circuit, which gives the downtube a short high-level drive pulse during the initial power-up, and then the voltage drops to 0 to cut off the downtube.
The second is the software, when the CPU is operating normally, it outputs a square wave pulse that only needs to be turned on by the lower three tubes, so that the upper tube ...
|
|
Delta's inverter is automatically changed to manual setting
The converter is capable of manual and active switching:
1. The switching between the manual operating system and the DCS operating system is done by the transfer switch SA installed on the field operation tower, which has active, manual and ...
|
|
TIMTOS x TMTS 2022 - Delta's Exhibit Highlights
Intelligent machining solution plan
Intelligent machinery is an important step towards intelligent manufacturing, in order to help manufacturers improve productivity or complete a few diverse forms of production, Delta will exhibit the intelligent processing solution plan at TIMTOS x TMTS 2022, which will be used to communicate with industrial-grade managed Ethernet networking.
|
|
Voltage regulator selection method - Delta inverter
1. Capacity safety factor
The AC regulated power supply is based on the output apparent power (kVA) as the nominal rated capacity, and the load is not purely resistive under normal circumstances, that is, the power factor COS¢≠1, and the active power that the regulator can output in practice kW = capacity (kVA) × COS¢. So in the real ...
|
|
Introduction to Delta's PLC maintenance knowledge
1. Delta's PLC power on running light does not light up, and the ERROR flashes, the reason may be: no program
2. Delta's PLC cannot communicate with the computer, which may be: RS23 port is broken
3. Delta's PLC power light does not light up: The power supply is bad
...
|
|
Misunderstandings of power-saving and energy-saving use of inverters
Industrial control automation products inverters are depicted as power-saving, energy-saving control automation products, therefore, many people will think that as long as the equipment is installed with inverters, it will be able to save energy, but this is not the case.
The inverter of industrial automation products itself produces energy-saving ...
|
|
Tips and methods for using PLC - Delta PLC
First, the selection of output module
The output modules are divided into transistors, triacs, and contact types:
(1) The switching speed of the transistor type is fast (generally 0.2ms), but the load can be small, about 0.2-0.3A, 24VDC, suitable for fast switching, signal contact...
|
|
Debugging Delta's inverter method
In order to ensure the reliability of production, when Delta's inverter is planned to be equipped with power drive, in addition to meeting the power drive requirements, the remaining torque increases the consumption of active power. When using cost-effective Delta inverters to regulate the speed, if the flow requirements are reduced, by reducing the rotation of the pump or fan...
|
|
Post-inverter shutdown maintenance project – Delta
1. Use a vacuum cleaner with a plastic nozzle to completely clean the inside and outside of the inverter cabinet to ensure that there is no excessive dust around the equipment.
2. Check the ventilation and lighting of the inverter room, and the ventilation equipment can work normally.
3. Check the inverter ...
|
|
Inverter optocoupler device type - Delta
1. One is a triode type photocoupler, such as PC816, PC817, 4N35, etc., which is commonly used in the output voltage sampling and error voltage amplification circuit of the switching power supply circuit, and is also used in the digital signal input loop of the inverter control terminal. The structure is the simplest, and the input side consists of a light-emitting two...
|
|
Delta servo system composition
The servo system is mainly composed of a servo controller, a drive circuit, a servo motor and the corresponding reaction testing equipment.
(1) Servo motor
Servo motor refers to the motor that controls the mechanical components in the servo system, and the servo motor has an encoder inside, which can respond to the movement in real time.
|
|
Brand inverter modifies the power method - Delta
What are the benefits of inverter power correction? Many brands of inverter power boards, driver boards, and motherboards can be universal, as long as the type, volume, and hardware are the same, and the desired power and voltage value can be obtained by correcting the manufacturer's parameters.
|
|
Precautions for initial installation of Delta inverters
Delta's inverters should be thoroughly inspected for the first time or after long-term installation. The items and methods of inspection are as follows:
1) Check whether the Delta inverter is damaged, whether the metal parts are rusty, and whether there is frost. If there is frost and condensation, it should be dried for 4 hours (60°C) or ...
|
|
Wind turbine inverter speed regulation effect - Delta
What is the effect of speed regulation of fan inverter? According to the query materials, in industrial production, the throttling loss of the damper, baffle and other related equipment of the fan, as well as the protection and maintenance costs account for 7%-25% of the production cost.
|
|
Analysis of abnormal operation of Delta inverter
There are many setting parameters of the inverter, each parameter has a certain selection range, and the phenomenon that the inverter can not operate normally is often encountered in the application due to the improper setting of a single parameter, so the relevant parameters must be set correctly.
...
|
|
The impact of grid quality on the life of the inverter – Delta
Inverter is a high-tech product, mainly composed of power electronic equipment and microelectronic equipment. The three-phase communication grid is connected to the input of the frequency converter. The input end of the inverter is a rectifier circuit, and the output end is a frequency conversion circuit. As a result, the voltages and currents on the input and output sides include abundant ...
|
|