Rated current design of inverter leakage circuit breaker - Delta

Create Date: 2024-8-30 12:03:23|Source: Delta/Delta

1. Install AC reactor and DC reactor. When the capacity of the inverter is greater than 500kva in the distribution transformer, and the transformer capacity is more than 10 times the capacity of the inverter, an AC reactor is installed on the input side of the inverter. When the output voltage of the distribution transformer is unbalanced in three phases and the unbalance rate is greater than 3%, it needs to be installed at this moment

The output of the inverter is controlled by PWM (pulse width modulation, similar to high-speed switching), so a high frequency leakage current will be generated. It is recommended that each inverter should choose a sensitivity current of more than 200mA and the action time is more than 0.1 seconds, but do not ensure that the leakage disconnect will not trip, the following factors must be considered to determine the size of the leakage current of the system, and select the appropriate leakage circuit breaker switch and necessary measures to improve the phenomenon of leakage circuit breaker tripping after power transmission.

                                 Rated current design of inverter leakage circuit breaker - Delta

Generally, the rated current selection formula of the leakage disconnect switch is as follows:

  I△n≧10*〔Ig1+Ign+3*(Ig2+Igm)〕

Ig1, Ig2: The leakage current of the cable during commercial operation.

IGN: The leakage current of the noise filter on the input side of the inverter.

Igm: Leakage current of the motor during commercial operation.

From the relevant variation parameters of the above formula, it is known that the factors that will affect the size of the leakage current are:

(1) Leakage current of the cable (there are two parts)

The leakage current of the cable length of the leakage disconnect switch filter.

The leakage current of the cable length of the inverter motor.

(2) Leakage current of the filter (including the inverter).

(3) The leakage current of the motor.

Leakage current value of each part (unit: mA)

(1) Leakage current of the cable = A* (practice cable length/1000m); The cable manufacturer supplies the leakage current value A per 1000m of each wire diameter.

(2) The leakage current of the filter (including the inverter) - the inverter supplier supply. For example, Delta's VFD055B43B filter is 26TDT1W4B4 and its maximum leakage current is 70mA.

More on that
Delta inverter failure and maintenance Delta inverter failure and maintenance

Delta's inverter problem 1: Communicate with the motor driver to explore the formation of overvoltage conditions on the internal DC high-voltage power supply side Check whether the keyed operating voltage is in the field of the additional value of the communication motor driver keying operating voltage, and detect whether there is a surge operating voltage formation If it is due to ...

Common knowledge points of Delta inverters Common knowledge points of Delta inverters

1. How to set the acceleration and deceleration time of Delta inverter? Solution(s): The acceleration time of Delta's inverter is the time it takes for the driver to accelerate from 0.0Hz to "high operating frequency". Deceleration time refers to the deceleration time required for the inverter to decelerate from "high operating frequency" to 0.00Hz.

Precautions for initial installation of Delta inverters Precautions for initial installation of Delta inverters

Delta's inverters should be thoroughly inspected for the first time or after long-term installation. The items and methods of inspection are as follows: 1) Check whether the Delta inverter is damaged, whether the metal parts are rusty, and whether there is frost. If there is frost and condensation, it should be dried for 4 hours (60°C) or ...

Inverter setting method - Delta Inverter setting method - Delta

The first step is type recognition: acknowledging whether the type of inverter is common to the type of inverter purchased. If not, ask the agent to return the item. Step 2: Shipping Acknowledgement: After opening the package, check whether the inverter is damaged during transportation. If there is damage, let the agent return ...

Tips and methods for using PLC - Delta PLC Tips and methods for using PLC - Delta PLC

First, the selection of output module The output modules are divided into transistors, triacs, and contact types: (1) The switching speed of the transistor type is fast (generally 0.2ms), but the load can be small, about 0.2-0.3A, 24VDC, suitable for fast switching, signal contact...

Delta's inverter failure analysis Delta's inverter failure analysis

1. Fault code: SE1 parameter replication error Fault Description: Keypad replication function error correct Solution: Keypad replication action errors, including communication delays, communication errors (Keypad received FF86 errors), and parameter value errors ...

Use and maintenance of electric motors - Delta motors Use and maintenance of electric motors - Delta motors

The motor can be started after the work is completed before use, and attention should be paid to the investigation of the motor, transmission device, production machinery and line voltage and ammeter, if there is an abnormal phenomenon, it should be stopped immediately, the fault should be identified and swept away, and then it can be closed and started again. When the motor is running, ...

Inverter Troubleshooting Skills - Delta Inverter Troubleshooting Skills - Delta

(1) The inverter drives the motor to jitter When repairing an Yaskawa 616PC5-5.5kW inverter, the customer indicated that the motor was shaking when sending it for repair, and the output voltage was unbalanced. After checking the power equipment, it was found that there was no damage, the inverter was energized and the display was normal, the inverter was operated, and the measurement ...

How to choose Delta's servo motor How to choose Delta's servo motor

When selecting a Delta servo motor, in principle, the selection should be based on the load conditions. There are two types of loads on the motor shaft, namely damping torque and inertial load. Both loads should be calculated correctly and their values should meet the following criteria:   1) When the machine is running with no load, in the whole speed range, Delta ...

The basic control loop of Delta's inverter The basic control loop of Delta's inverter

There are two fundamental circuits for communicating with external signals: analog and digital: 1. 4-20mA current signal loop (imitation); 1 - 5V/0 - 5V voltage signal loop (imitation). 2. Switch signal circuit, inverter start and stop command, forward rotation command, etc.

Pulse control wiring method for Delta servo drives Pulse control wiring method for Delta servo drives

Parameter settings P1-XX are the basic parameters P1-00 pulse method selection, *** bit selection is 2, that is, pulse train + direction P1-00 signal logic picking, the third digit is selected as 0 or 1, which is the positive logic or anti-logic, X0XX or X1XX P1-01 Control form selection, pick ...

Delta's inverter process setting Delta's inverter process setting

1. Restore the inverter to factory settings, press the "ENTER" button to enter the parameter setting interface, and press it continuously until it is 00-00 and then stop. Press the number up button to change to 00-02. Press the "ENTER" key again, the panel value will show 0, press the number up key to change it to 9. Press the "ENTER" key, break ...

Introduction to Delta's DVPSCM52-SL communication module Introduction to Delta's DVPSCM52-SL communication module

Recently, Delta Group has made a big hit in the field of building automation with the launch of the DVPSCM52-SL, a slave communication module that supports BACnet MS/TP (Building Automation Control Network Communication Protocol). Building automation system is an indispensable part of intelligent building.

Delta's key steps in inverter maintenance Delta's key steps in inverter maintenance

First, the maintenance of the inverter must first check whether the sound in the operation of the motor is abnormal, including, whether the motor is in operation to form a sensation. ​ 2. Check whether the natural environment of the inverter installation has changed. ...

TIMTOS x TMTS 2022 - Delta's Exhibit Highlights TIMTOS x TMTS 2022 - Delta's Exhibit Highlights

Intelligent machining solution plan Intelligent machinery is an important step towards intelligent manufacturing, in order to help manufacturers improve productivity or complete a few diverse forms of production, Delta will exhibit the intelligent processing solution plan at TIMTOS x TMTS 2022, which will be used to communicate with industrial-grade managed Ethernet networking.

Delta UPS uninterruptible power supply R-2K series Delta UPS uninterruptible power supply R-2K series

With the increasing demand for system switching power supply by computer technology, Delta UPS uninterruptible power supply R-2K series products have been paid more and more attention, and gradually developed into a kind of electrical engineering with the effects of voltage stabilizer tube, frequency stabilization, filtration, anti-electromagnetic and frequency emission influence, anti-operation voltage swimming, etc.

In 2020, Delta once again won the Outstanding Human Resource Optimization Award In 2020, Delta once again won the Outstanding Human Resource Optimization Award

Not long ago, Delta was awarded the "2020 Excellence Award for Optimal Allocation of Human Resources Resources" by the Human Resource Management Service Project Organization "Future", which stood out from more than 5,000 companies. This is also the second time since 2018 that Delta has won this honor. Delta ...

DC governor overhaul method - Delta DC governor overhaul method - Delta

DC governor is a kind of motor speed regulation equipment, including motor DC governor, pulse width DC governor, thyristor DC governor, etc. Generally, it is a modular DC motor governor, which integrates power supply, control and drive circuits, selects three-dimensional structure layout, and selects micro-power consumption elements for control circuits.

Analysis of abnormal operation of Delta inverter Analysis of abnormal operation of Delta inverter

There are many setting parameters of the inverter, each parameter has a certain selection range, and the phenomenon that the inverter can not operate normally is often encountered in the application due to the improper setting of a single parameter, so the relevant parameters must be set correctly. ...

Delta's servo drive ASDA-B2-F motion control alarm Delta's servo drive ASDA-B2-F motion control alarm

Abnormal alarm indication Abnormal alarm title Abnormal alarm action content Sweeping method Indicate DO servo status Switch AL111 DMCNET Packet Receive Overfill Rx Buffer Overfill (more than two DMCNET packets received within 1 millisecond) ALM ON AL185 DMCNET Bus Hardware ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top