Inverter parameter setting method - Senlan

Create Date: 2024-8-30 12:03:23|Source: Hope Sunland

1. Control method:

i.e. speed control, rotation control, PID control, or other methods. After the control method is adopted, it is generally necessary to carry out static or dynamic identification according to the control accuracy.

2. Minimum operating frequency:

That is, the minimum speed of motor operation, when the motor is operating at low speed, its heat dissipation performance is very poor, and the motor will be incinerated when the motor is operated at low speed for a long time. And at low speeds, the current in the cable will also increase, which will also cause the cable to heat up.

                               Inverter parameter setting method - Senlan

3. Highest operating frequency:

The maximum frequency of the general inverter is 60Hz, and some even to 400 Hz, and the high frequency will make the motor work at high speed, which is for the general motor, its bearing can not be operated at extra speed for a long time, and whether the rotor of the motor can withstand such centrifugal force.

4. Carrier frequency:

The higher the carrier frequency setting, the larger the higher harmonic component, which is closely related to the length of the cable, the heating of the motor, the heating of the cable and the heating of the inverter.

5. Motor parameters:

The inverter sets the power, current, voltage, speed, and maximum frequency of the motor in the parameters, and these parameters can be obtained directly from the motor nameplate.

6. Frequency hopping:

At a certain frequency point, resonance may occur, especially when the whole device is relatively high; When operating the compressor, avoid the surge point of the compressor.

7. Acceleration and deceleration moments

The acceleration time is the time it takes for the output frequency to rise from 0 to the maximum frequency, and the deceleration time is the time it takes to drop from the maximum frequency to 0. Usually, the acceleration and deceleration time is determined by the rise and fall of the frequency setting signal. When the motor accelerates, the rise rate of the frequency setting must be constrained to avoid overcurrent, and when the motor is decelerating, the fall rate must be constrained to avoid overvoltage.

Speed up the time setting requirements: the acceleration current is constrained below the overcurrent capacity of the inverter, so that the overflow will not cause the inverter to trip; The key to setting the deceleration time is to avoid excessive voltage of the smoothing circuit, and not to cause the regenerative overvoltage to stall and trip the inverter. The acceleration and deceleration time can be calculated according to the load, but in the debugging, it is often taken to set a longer acceleration and deceleration time according to the load and experience, and observe whether there is an overcurrent and overvoltage alarm after starting and stopping the motor; Then, the acceleration and deceleration time is gradually shortened, and the optimal acceleration and deceleration time can be determined by repeating the operation several times in the principle that no alarm occurs during the operation.

8. Torque increase

Also known as torque compensation, it is a method to increase the low frequency range f/V in order to compensate for the decrease in torque at low speed caused by the resistance of the stator winding of the motor. When set to active, the voltage at the time of acceleration can be actively increased to compensate for the starting torque, so that the motor can be accelerated smoothly. If manual compensation is selected, the best curve can be selected according to the load characteristics, especially the starting characteristics of the load. For variable torque loads, if the selection is not appropriate, the output voltage at low speed will be too high, and the phenomenon of wasting electric energy, and even the phenomenon that the motor will start with a load and the current will be large, and the speed will not go up.

9. Electronic thermal overload maintenance

This function is set to maintain the overheating of the motor, which is that the CPU in the inverter calculates the temperature rise of the motor according to the operating current value and frequency, so as to carry out overheating maintenance. This function is only applicable to the occasion of "one to one", and in the case of "one to many", thermal relays should be installed on each motor.

Electronic Thermal Maintenance Setpoint (%) = [Motor Extra Current (A) / Inverter Extra Output Current (A)]× 100%.

10. Frequency Constraints

That is, the upper and lower amplitudes of the output frequency of the inverter. Frequency constraint is a maintenance function to avoid misoperation or external frequency setting signal source problems, and the output frequency is too high or too low, so as to prevent damage to the equipment. You can set it according to the actual situation in the app. This function can also be used as a speed limit, such as a belt conveyor, because the material is not too much, in order to reduce the wear and tear of machinery and belts, you can choose to use the inverter to drive, and the upper limit frequency of the inverter is set to a certain frequency value, so that the belt conveyor can operate at a fixed, lower operating speed.

11. Bias frequency

Some are also called error frequency or frequency error setting. It is used to adjust the output frequency when the frequency is set by an external analog signal (voltage or current), and the output frequency is at the lowest when the frequency is set. When the frequency setting signal is 0%, the error value can be in the range of 0 - fmax, and some inverters (such as Mingdianshe and Sanken) can also set the bias polarity. If the output frequency of the inverter is not 0Hz but xHz when the frequency setting signal is 0% in the debugging, then the bias frequency can be set to negative xHz to make the output frequency of the inverter 0Hz.

12. Frequency setting signal gain

This function is only useful when setting the frequency with an external analog signal. It is used to compensate for the inconsistency between the externally set signal voltage and the internal voltage (+10V) of the inverter; When the analog input signal is the maximum (such as 10v, 5v or 20mA), find the frequency percentage that can output the f/V graph and set it as a parameter. If the external setting signal is 0 - 5V, if the output frequency of the inverter is 0 - 50Hz, the gain signal can be set to 200%.

13. Torque constraint

There are two types of driving torque constraint and brake torque restraint. It is based on the output voltage and current values of the inverter, and the torque is calculated by the CPU, which can significantly improve the shock load recovery characteristics during acceleration and deceleration and constant speed operation. The torque restraint function enables active acceleration and deceleration control. Assuming that the acceleration and deceleration time is less than the load inertia time, the motor can also be guaranteed to actively accelerate and decelerate according to the torque set value.

The driving torque function provides a strong starting torque, and in the steady-state operation, the torque function will control the motor to deviate, and the motor torque is constrained within the maximum set value, when the load torque suddenly increases, and even when the acceleration time is set too short, it will not cause the inverter to trip. If the acceleration time is set too short, the motor torque will not exceed the maximum set value. A large drive torque is good for starting, so it is better to set it to 80 - 100%.

The smaller the braking torque setting value, the greater the braking force, which is suitable for the occasion of rapid acceleration and deceleration, such as the overvoltage alarm phenomenon when the braking torque setting value is set too much. If the braking torque is set to 0%, the total amount of regeneration applied to the main capacitor can be close to 0, so that the motor can be decelerated to a stop without using a braking resistor when decelerating. However, on some loads, such as when the braking torque is set to 0%, the phenomenon of short time and idle will appear when decelerating, resulting in repeated start of the inverter, and the current will fluctuate greatly, and the inverter will trip when it is severe, which should be noted.

14. Selection of acceleration and deceleration forms

It is also called acceleration and deceleration curve selection. Generally, there are three kinds of curves for inverters: linear, nonlinear and S, and most of them usually select linear curves; The nonlinear curve is suitable for variable torque loads, such as fans, etc.; The S-curve is suitable for constant torque loads, where the acceleration and deceleration changes more slowly. Punctuality can be based on the load torque characteristics, select the corresponding curve, but there are exceptions, the author in the debugging of a boiler inverter fan inverter, the acceleration and deceleration curve selection of nonlinear curve, together with the operation of the inverter tripped, adjustment and change of many parameters have no effect, and then changed to the S curve after the normal. The reason is: the induced draft fan rotates by itself because of the flue gas flow before starting, and reverses and becomes a negative load, so that the S curve is selected, so that the frequency rise speed at the beginning of the start is slower, so as to avoid the occurrence of the inverter tripping, of course, this is the method selected for the inverter without starting DC braking function.

15. Torque vector manipulation

Vector control is based on the theoretical belief that asynchronous motors and DC motors have the same torque generation mechanism. The vector control method is to decompose the stator current into the specified magnetic field current and torque current, control them separately, and output the stator current after the synthesis of the two to the motor. Therefore, in principle, the same handling performance can be obtained as that of a DC motor. With the torque vector control function, the motor can output the maximum torque under various working conditions, especially in the low-speed working area.

At present, almost all inverters are controlled by non-response vectors, because the inverter can compensate for the slip according to the load current and phase, so that the motor has very hard mechanical characteristics, and can meet the requirements for most occasions, without setting the speed response circuit outside the inverter. The setting of this function can be based on the actual situation, and it is enough to choose one of the useful and ineffective.

The related function is the slip compensation control, which is used to compensate for the speed error caused by the load fluctuation, and the slip frequency corresponding to the load current can be added. This function is mainly used for positioning control.

16. Energy-saving control

Fans and pumps all belong to the reduced torque load, that is, with the decrease of speed, the square of the load torque and the speed decreases, and the inverter with energy-saving control function is designed with a special V/f form, which can improve the power of the motor and inverter, which can actively reduce the output voltage of the inverter according to the load current, so as to achieve the purpose of energy saving, and can be set to useful or ineffective according to the specific situation.

It should be clarified that the two parameters of nine and ten are very advanced, but there are some users who cannot enable these two parameters in the equipment transformation, that is, the inverter trips frequently after it is enabled, and everything is normal after it is deactivated. The reasons for this are:

(1) The parameters of the original motor are too different from the motor parameters required by the inverter.

(2) Insufficient understanding of the function of setting parameters, such as energy-saving control function can only be used in the V/f control method, not in the vector control method.

(3) The vector control method is enabled, but the manual setting and active reading of the motor parameters are not carried out, or the reading method is inappropriate.

More on that
Industrial control circuit board capacitor damage fault characteristics and maintenance - Senlan Industrial control circuit board capacitor damage fault characteristics and maintenance - Senlan

Capacitor damage is the highest problem in electronic devices, especially electrolytic capacitors. Capacitor damage is manifested in: 1. Capacity becomes smaller, 2. Capacity is completely lost, 3. Leakage, 4. Short circuit. Electricity...

Senlan inverter selection principle Senlan inverter selection principle

1. Select the inverter according to the load characteristics, such as the load is constant torque load, you can choose Siemens MM440 inverter, ABB ACS800 series inverter, etc.; If the load is a fan or pump load, you can choose Siemens MM430 inverter, ABB ACS510 series inverter, etc. 2、 ...

Introduction to the main series of Sunland inverter products Introduction to the main series of Sunland inverter products

SB150 SB150 is a delicate and practical inverter launched by Sunland, with exquisite and delicate appearance, exquisite and perfect circuit, simple and practical function, and clear and reasonable menu distinction. At the center of the SB150 is Sunland's high-performance optimized space vector ...

Motor encoder and rotor pole phase zero alignment repair - Sunland Motor encoder and rotor pole phase zero alignment repair - Sunland

1. Phase alignment method of incremental encoder The alignment between the phase of the UVW electronic transmutation signal and the phase of the rotor pole, or the phase of the TV spot, of the incremental encoder with the signal exchange is as follows: 1) Use a DC power supply to pass the UV winding of the motor to less than the amount of ...

The reason for the low output voltage of the inverter - Senlan inverter The reason for the low output voltage of the inverter - Senlan inverter

1. The power supply voltage is low The solution is to preset the active voltage adjustment function of the inverter, so that when the frequency is low and the rated frequency is dry, the inverter has the function of active voltage stabilization, and if the output voltage is low, the inverter will actively increase the output voltage ...

15 Inverter Definitions – Hope Sunland 15 Inverter Definitions – Hope Sunland

1. What is frequency conversion resolution? What's the point? In the case of digitally operated inverters, the output frequency is given in a given order, even if the frequency command is an analog signal. The smallest unit of this gradient is called the variable resolution. Change...

Sunland proposed a multi-machine parallel high-voltage shore power supply system solution Sunland proposed a multi-machine parallel high-voltage shore power supply system solution

Air pollution in port cities mainly comes from cargo loading and unloading operations and emissions from ships calling at ports; Shore power connection refers to the closure of the auxiliary engine during the port of the vessel, and the shore power is supplied by the port. At 9:08 on December 25, 2018, the world's first ...

Analysis of soft start technology of asynchronous motor - Senland Analysis of soft start technology of asynchronous motor - Senland

The thyristor communicates the voltage regulation and soft starts The communication and voltage regulation soft engine of the thyristor is mainly to change the connection method of the thyristor, and the traditional connection method is changed to connect to the three windings, so that the power supply of the thyristor is completed by the method of parallel connection. Thyristor soft starters have a strong ...

The key points of the use of inverter - Sunland inverter The key points of the use of inverter - Sunland inverter

In order to ensure the safe, efficient and reliable operation of the inverter, the following keys should be grasped when using the inverter: 1) It is necessary to reliably ground the grounding terminal of the inverter, so as to effectively press the radio frequency disturbance and enhance the reliability of the system.

Inverter line control mode - Senlan inverter Inverter line control mode - Senlan inverter

Each inverter (Variable-frequency Drive, VFD) is subject to different line control, and the methods of voltage control and current control can be divided into two categories, one is voltage type and the other is current type. The control mode can also be divided into voltage control and current type. The main circuit method and ...

Introduction to the wiring rules of Sunland inverter Introduction to the wiring rules of Sunland inverter

It is necessary to separate the signal line from the power line: when using analog signals for long-distance control of the inverter, in order to reduce the disturbance of the analog amount from the inverter and other equipment, please separate the signal line of the control inverter from the strong current circuit (main circuit and sequential control circuit). Inverter ...

Advantages of Sunland HOPE530 series inverter Advantages of Sunland HOPE530 series inverter

Sunland HOPE530 series inverter is a high-performance, high-reliability intelligent controller, widely used in a variety of industrial occasions. It is easy to operate, diversified equipment and high quality, and has become one of the intelligent power control equipment trusted by users. ...

Introduction of Sunland inverter Introduction of Sunland inverter

1. Obtain accurate motor parameters from low to high parameters at different frequencies, and establish motor models of corresponding frequency bands in different frequency segments, so that the inverter can control the motor from low to high. 2. V/F control (1) It is possible to select 15 pre-set V/...

The reason for the increase of the torque of the inverter - Senlan inverter The reason for the increase of the torque of the inverter - Senlan inverter

It is important to set the torque to improve the function. When the power frequency of the motor decreases, the speed of the motor will also decrease, and if the load torque remains unchanged, the output power will also decrease. According to the principle of conservation of energy, if the rotation of the load ...

Inverter overcurrent treatment method - Senlan inverter Inverter overcurrent treatment method - Senlan inverter

Overcurrent or overload of the inverter is a common problem of the inverter, and overcurrent refers to the value of the current flowing through the inverter beyond its additional range. 1. If the power supply of the inverter is out of phase, the circuit at the output end is disconnected or the motor winding ...

Hope Sunland inverter fault code Hope Sunland inverter fault code

Hope Sunland inverter part of the fault code Er.ocb (1) Overcurrent at the moment of starting: There is a short circuit inside the motor There is a short circuit in the motor wiring The starting voltage is too high Check the motor and wiring Check the motor wiring Seek service Check the torque ...

The choice of inverter braking resistor - hope Senlan The choice of inverter braking resistor - hope Senlan

In addition to the limitation of the maximum promised current of the special energy consumption braking unit of the inverter, the selection of the braking resistor has no clear correspondence with the braking unit, and its resistance value is mainly selected according to the size of the required braking torque. Power...

Wiring specification of inverter control cabinet - Senland Wiring specification of inverter control cabinet - Senland

The signal line and the power line must be routed separately: when using the analog signal to remotely control the inverter, the signal line of the control inverter and the strong current circuit (main circuit and sequential control circuit) can be separated from the inverter and other equipment to the analog interference, and the interval should be more than 30cm. Signal ...

Sunland low-voltage inverter division series Sunland low-voltage inverter division series

1.HG1000 high-performance light-load intelligent inverter, the most cost-effective, the new series is widely used in medicine, food, packaging, cable, printing and dyeing, washing, centrifuge, dehydrator, sewage treatment, HVAC, constant pressure water supply, constant temperature control, flow control and other industries, such as fans and pumps, ...

Motor inspection and maintenance, motor problems - Senlan Motor inspection and maintenance, motor problems - Senlan

1: In the operation of the motor, if dust, water stains and other debris enter its interior, it will constitute a short-circuit medium, which can damage the wire insulation layer, form an inter-turn short circuit, increase the current, increase the temperature and incinerate the motor. Therefore, dust, water stains and other debris should be prevented from entering the motor.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top