The inverter needs to prepare the braking resistance condition - Delta

Create Date: 2024-8-30 12:03:23|Source: Delta/Delta

The preparation of the braking resistor of the inverter is mainly to consume part of the energy on the DC bus capacitor through the braking resistor to prevent the capacitor voltage from being too high. Theoretically, if the capacitor stores a large amount of energy, it can be used to release it to drive the motor and prevent energy waste. However, the capacitance of a capacitor is limited, and the withstand voltage of a capacitor is also limited. When the voltage of the bus capacitor reaches a certain level, the capacitor may be damaged, and some even damage the IGBT. Therefore, it is necessary to brake the resistor in time to release the electricity. This exculpation is wasted, and there is no way to do it.

After the three-phase alternating current is fully rectified, the capacitor is connected. When running at full load, the normal voltage of the bus is about 1.35 times, 380*1.35=513 volts. Of course, this voltage will fluctuate in real time, but the minimum voltage cannot be lower than 480 volts, otherwise it will give undervoltage alarm protection. The bus is generally composed of two sets of 450V electrolytic capacitors connected in series, and the theoretical withstand voltage is 900V. If the bus voltage exceeds this value, the capacitor will burst directly, so the bus voltage will not reach 900V anyway.

  ​                        The inverter needs to prepare the braking resistance condition - Delta

In fact, the withstand voltage of a 380 volt input three-phase IGBT is 1200 volts, and it is often required to operate within 800 volts. Considering that if the voltage rises, there will be an inertia problem, that is, if you let the braking resistor work immediately, the bus voltage will not drop quickly, so many VFDs go through the braking unit to let the braking resistor start working at about 700 volts, and then reduce the bus voltage to prevent it from rising.

Therefore, the core of braking resistor planning is to consider the withstand voltage of the capacitor and IGBT module to prevent these two important devices from being damaged by the high voltage of the bus. If these two components are broken, the VFD will not work properly.

Rapid parking requires braking resistance, and also requires instantaneous acceleration.

The reason why the voltage of the VFD bus becomes higher is that in many cases, the VFD is the reason. Let the motor work in the electronic braking condition, and let the IGBT go through a certain conduction sequence. By using the large inductance of the motor, the current does not change suddenly, and a high voltage is generated to charge the bus capacitor instantaneously. At this time, let the motor slow down quickly. At this moment, if there is no braking resistor to consume the energy of the bus in time, the bus voltage will continue to rise, threatening the safety of the VFD.

If the load is not heavy and there is no emergency stop required, there is no need to use a braking resistor in this case. Even if a braking resistor is installed, the operating threshold voltage of the braking unit is not triggered, and the braking resistor is not put into operation.

In addition to the need to add a braking resistor and a braking unit for rapid braking in the case of heavy load deceleration, in fact, if the requirements of the heavy-load starting time and the starting time are very fast, the braking unit and the braking resistor are also required to cooperate to start. I once tried to drive a special punch machine with a VFD, and I asked the VFD to speed up to 0.1 seconds. At this point, it starts at full capacity, although the load is not very heavy. However, due to the shortness of the acceleration time, the bus voltage fluctuates greatly at this moment, and there will also be overvoltage or overcurrent. Later, an external braking unit and braking resistor were added, and the VFD was able to operate normally. The analysis is because the starting time is too short, the bus capacitor voltage is instantly hollowed out, and the rectifier is instantly charged with a large current, which causes the bus voltage to suddenly become high, so that the bus voltage fluctuates too much, and it may exceed 700V in an instant. The addition of braking resistors can eliminate this fluctuating high voltage in time, and the VFD can operate normally.

There is also a special case, in the case of vector control, the torque of the motor is in the opposite direction to the speed, or the motor is operating at zero speed and outputs 100% torque. For example, the crane is stopped in mid-air, and torque control is required in the case of pay-off and pay-off, so that the motor needs to work in the generator condition, and the continuous current will be reversely charged into the bus capacitor. After braking resistance, it can consume energy in time and insist on the balance and stability of the bus voltage.

Many low-power VFDs, such as 3.7 kW, usually have a built-in braking unit and braking resistors. Considering the reduction of bus capacitance, the low-power resistor and braking unit is not so expensive.

More on that
Several common problems of Delta and their solutions Several common problems of Delta and their solutions

What is the stall prevention function of the inverter? If the given acceleration time is too short, the output frequency of the inverter changes much more than the change of speed, and the inverter will jump due to the flow of overcurrent, and the free operation is stopped, which is stalling. In order to prevent stalling and keep the motor working, ...

Basic conditions for Delta UPS uninterruptible power supply Basic conditions for Delta UPS uninterruptible power supply

1. Visually inspect the UPS and battery (or other energy storage) equipment for obstacles, and properly cool the surrounding area. 2. Ensure that there is no abnormal operation or positive warning on the UPS panel, such as: overload or overdischarge of the battery close to it. 3. Check if there is battery corrosion or other shortcomings ...

Delta's high-performance servo ASDA-A3 series is a new product Delta's high-performance servo ASDA-A3 series is a new product

With the rapid development of automation technology and shopping malls, customers have higher and higher requirements for the speed, accuracy and function diversification of servo products. In order to get used to the needs of shopping malls, recently, Delta launched the high-performance motion control high-end AC servo system ASDA-A3 series ...

Rated current design of inverter leakage circuit breaker - Delta Rated current design of inverter leakage circuit breaker - Delta

1. Install AC reactor and DC reactor. When the capacity of the inverter is greater than 500kva in the distribution transformer, and the transformer capacity is more than 10 times the capacity of the inverter, an AC reactor is installed on the input side of the inverter. And when the output voltage of the distribution transformer is unbalanced and uneven in three phases ...

How to use a PC to control Delta's inverter How to use a PC to control Delta's inverter

The communication interface of Delta's inverter is to use RS485 to cooperate with the ModBus communication format commonly used in the general industry for material handing, so as long as the general ModBus software is used, the PC can be used to read and write the materials of the drive. Furthermore...

Delta has always been the shipment champion in Taiwan's inverter market Delta has always been the shipment champion in Taiwan's inverter market

Based on trend forces, the sales market of solar power generation in Taiwan was analyzed. In the first half of 2019, AUO ranked second, while third-ranked Canada Solar entered the top three for the first time. Compared with the previous year, the sales market in Taiwan, China in the first half of 2019 was in the total delivery of common decoration ...

What are the problems of the inverter if it is not used for a long time - Delta What are the problems of the inverter if it is not used for a long time - Delta

Most inverter brand products can rely on the heat of internal electrical components to remove moisture during normal use. If you don't use it for a long time, it's easy to get wet. The chip pins, penetrating resistors, capacitors, and inductor pins of the DIP package will be severely rusted or desoldered, resulting in on-resistance ...

The principle, composition and function of Delta's inverter The principle, composition and function of Delta's inverter

1. What is a Delta inverter? Delta inverter is a device that converts the power supply (50Hz or 60Hz) into a communication power supply of various frequencies to realize the variable speed operation of the motor.

Introduction to Constant Power and Constant Torque in Frequency Conversion Speed Regulation - Delta Introduction to Constant Power and Constant Torque in Frequency Conversion Speed Regulation - Delta

In general, factory motors are based on the additional speed values obtained at a given power frequency voltage (380 V, 50 Hz). If 380V is not reached under actual operating conditions, e.g. as long as 300V, 50 Hz, the voltage is significantly undervoltaged. Fundamentally, it cannot reach the extra rev value, due to the ...

Precautions for long-term idle inverter - Delta inverter Precautions for long-term idle inverter - Delta inverter

If the inverter is to run the equipment again after being shelved for more than half a year, the probability of damage may be greatly increased due to many factors such as the placement environment, the service life of the inverter, and the load rate, and the failure usually presents the following problems: ...

The cause of inverter heating - Delta inverter The cause of inverter heating - Delta inverter

1. The problem of the inverter and the motor itself If the motor has been used for a long time, it is not good to clean the insulation function, or the bearing may be stuck, and it may show a large current and heat. The coupling between the motor and the load may also be worn, or the motor is unbalanced, the fixtures of the motor are loose, etc.

How the components of the inverter work – Delta How the components of the inverter work – Delta

1. Inverter element - rectifier Since it is difficult to change the frequency of the communication sine wave in the form of communication, the first operation of the inverter is to convert the waveform into direct current. To make it look like an AC, it is relatively easy to operate the DC. The most important component of all inverters is a ...

Intelligent thermostat adjustment method - Delta Intelligent thermostat adjustment method - Delta

1. Set temperature: Press the SET button to set or view the temperature set point. Press the SET key digital tube character beginning flash, indicating that the appearance has entered the setting state, press the △ key to increase the set value, press the ▽ key to decrease the set value, press and hold the △ key or ▽ key The data will change rapidly, press the SET key again The appearance back ...

The cause of the damage of the inverter - Delta inverter The cause of the damage of the inverter - Delta inverter

First, the heat dissipation of the inverter is not good In fact, we all know that too high a temperature has a damaging effect on any equipment, just like a human brain, too high a temperature will also burn out the brain, in fact, the same is true for inverters. When the temperature rises, because of the sensitivity of semiconductors to temperature, the inverter ...

Delta's inverter external positive and reverse operation mode Delta's inverter external positive and reverse operation mode

1. The external control panel is rotated and operated After selecting the upper or lower button on the panel, the Frd inverter will rotate forward if you select the inverter, and the rEu inverter will rotate 2. The external control terminal is rotated Access via external terminals ...

TIMTOS x TMTS 2022 - Delta's Exhibit Highlights TIMTOS x TMTS 2022 - Delta's Exhibit Highlights

Intelligent machining solution plan Intelligent machinery is an important step towards intelligent manufacturing, in order to help manufacturers improve productivity or complete a few diverse forms of production, Delta will exhibit the intelligent processing solution plan at TIMTOS x TMTS 2022, which will be used to communicate with industrial-grade managed Ethernet networking.

Delta's Ultron HPH provides power protection that meets the needs of green data centers Delta's Ultron HPH provides power protection that meets the needs of green data centers

Delta's Ultron HPH series UPS has an AC-AC efficiency of up to 96%, and can reach 99% in ECO mode, with significant energy savings. The flexible airframe provides a compact footprint (40kW / 0.15 m2) and reduces space waste. With an interface-friendly 5-inch colorful touch screen, ...

Delta launched the MZM, a high-power positional drive system Delta launched the MZM, a high-power positional drive system

Driven by consumption promotion and product diversification, the manufacturing industry's demand for automation and intelligent promotion in production and processing is also increasing. In the production process, the processing of "large and heavy" items is often difficult to control accurately, and the deviation of orientation is not as easy as that of "small" items. To this end ...

Introduction of high-power fan inverter - Delta Introduction of high-power fan inverter - Delta

High power means increased cost The use of high-power fan inverter can indeed meet the various production needs of enterprises, but high-power also means an increase in production costs. Because the more power, the more power will be consumed. Assuming that a 20KW fan inverter can ...

Delta's inverter process setting Delta's inverter process setting

1. Restore the inverter to factory settings, press the "ENTER" button to enter the parameter setting interface, and press it continuously until it is 00-00 and then stop. Press the number up button to change to 00-02. Press the "ENTER" key again, the panel value will show 0, press the number up key to change it to 9. Press the "ENTER" key, break ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top