Introduction to Constant Power and Constant Torque in Frequency Conversion Speed Regulation - Delta

Create Date: 2024-8-30 12:03:23|Source: Delta/Delta

In general, factory motors are based on the additional speed values obtained at a given power frequency voltage (380 V, 50 Hz). If 380V is not reached under actual operating conditions, e.g. as long as 300V, 50 Hz, the voltage is significantly undervoltaged. Fundamentally, it cannot reach the extra speed value, because depending on the design of the motor, it must have a voltage of 380 V and a frequency of 50 Hz. To exciter, under the additional voltage, the magnetic field strength is not reached, and the magnetic flux is very small, so it will definitely affect the rotational speed, not due to the 60f/p formula to see the change in rotational speed. For example, in the case of 380V 40Hz input, according to the formula E=K*F*Q, E insists on the same, F decreases, then the Q magnetic flux becomes larger, which is an overvoltage situation, too much excitation, the magnetic flux for a long time, will make the motor heat up and may be incinerated for a long time. Therefore, the value of the magnetic flux should not be too large, which is determined by the bearing capacity of the motor at the time of design. Usually at constant torque regulation (below 50 Hz), the magnetic flux at this moment is the additional magnetic flux, also known as the total magnetic flux. If the voltage/frequency increases, the magnetic flux value will be exceeded, causing the motor to heat up.

                               Introduction to Constant Power and Constant Torque in Frequency Conversion Speed Regulation - Delta

Constant torque speed regulation:

In other words, let the magnetic flux stick to a stable value, and v/f=q (magnetic flux) is the stable value. Why is it called constant torque speed regulation? In other words, the load torque is a fixed value, and the motor output torque is also a fixed value. See the formula: t=k*i*q, at this moment q is constant, then the motor output torque is proportional to i, because the value of q can be calculated by nameplate V (additional power supply voltage)/50 Hz, so when q is constant, the additional current of the coil (regardless of whether there is a load, after confirming the maximum penetrating current, you can also confirm the maximum torque output of the motor (you can also confirm the stable load of how much torque the motor can drive), so the overcurrent capacity of the motor reflects the overload (torque) capacity of the motor.

Under the speed of providing a stable torque, only it needs to pass through the inverter to pass through the inverter through a voltage modulated at a certain frequency (ratio of magnetic flux, predetermined value) to be delivered, and the load torque is also a fixed value, then the constant N, T and, of course, the input power P is therefore fixed. If F increases and the speed N increases, the power P will become larger, and the torque T will not become larger due to the increase in speed (this is also known as a constant torque load, such as a conveyor belt). Constant torque characteristics are independent of load torque and speed, and the torque at any speed is stable or fundamentally stable for general applications such as conveyor belts, mixers, or extruder type friction loads and cranes, lifting potential energy loads, etc.)

Another point is that the extra speed is the value obtained when the motor is idling. For the significance of this value, the higher the value and the smaller the output torque when the additional voltage and additional power are reached. This is a feature of constant power speed regulation. Formula T=9550*P/N (extra speed). Therefore, in the case of 50Hz of F-type (the output power is the highest at the moment), when n is large, it is necessary to pay attention to the fact that T is small to prevent accidents caused by T being too small and less than the load torque. In constant power speed regulation, speed regulation is done by decreasing the magnetic flux to reduce the output torque and then increasing the speed, so it is also called weak magnetic speed regulation.

More on that
Workarounds for industrial tablet PC disk failures Workarounds for industrial tablet PC disk failures

  After the long-term operation of the industrial tablet, there is a lot of dust in the chassis and the temperature of the chassis is high. At this time, it is very simple to cause the disk failure of the industrial tablet computer, the product quality problems of the hard disk itself and the failure problems caused by the working environment. ...

Debugging method of Delta servo motor Debugging method of Delta servo motor

1. Initialize parameters Before wiring, initialize the parameters. On the control card: select the control method; Reset the PID parameter to zero; When the control card is powered on, the enable signal is closed by acquiescence; Save this condition to make sure that the control card ...

Voltage regulator selection method - Delta inverter Voltage regulator selection method - Delta inverter

1. Capacity safety factor The AC regulated power supply is based on the output apparent power (kVA) as the nominal rated capacity, and the load is not purely resistive under normal circumstances, that is, the power factor COS¢≠1, and the active power that the regulator can output in practice kW = capacity (kVA) × COS¢. So in the real ...

Misunderstandings of power-saving and energy-saving use of inverters Misunderstandings of power-saving and energy-saving use of inverters

Industrial control automation products inverters are depicted as power-saving, energy-saving control automation products, therefore, many people will think that as long as the equipment is installed with inverters, it will be able to save energy, but this is not the case. The inverter of industrial automation products itself produces energy-saving ...

A number of Delta's new high-end power supply products were unveiled at CMEF A number of Delta's new high-end power supply products were unveiled at CMEF

Delixi Electric's newly launched CDQ1F series PC-level excitation active transfer switch, with more complete specifications and stronger functions, the power-off time can be shortened to less than 0.1s, escorting the continuous use of electricity in important places! CDQ1F Active ...

The key point to pay attention to when choosing a UPS power supply - Delta The key point to pay attention to when choosing a UPS power supply - Delta

(1) About the synchronous switching function. Now, in addition to the off-line UPS power supply with an additional output power of less than 500VA, the off-line UPS power supply with square wave output is still selected for conversion control without mains synchronization function, and all UPS power supplies with an output power of 1KVA and above are performing the conversion operation of mains power supply to inverter power supply.

Inverter maintenance and accessories should be replaced regularly – Delta inverters Inverter maintenance and accessories should be replaced regularly – Delta inverters

1. Before the inverter is energized The temperature and humidity of the surrounding environment should be detected first. Too high a temperature will cause the inverter to overheat the alarm. When severe, it will directly lead to damage to the power supply device of the inverter and short circuit of the circuit; Excessive humidity of the air can lead to a direct short circuit inside the inverter. When the inverter is in operation ...

Delta inverter failure and maintenance Delta inverter failure and maintenance

Delta's inverter problem 1: Communicate with the motor driver to explore the formation of overvoltage conditions on the internal DC high-voltage power supply side Check whether the keyed operating voltage is in the field of the additional value of the communication motor driver keying operating voltage, and detect whether there is a surge operating voltage formation If it is due to ...

Delta's M300 series inverters are used in primary and auxiliary frequency applications Delta's M300 series inverters are used in primary and auxiliary frequency applications

I. Introduction Some devices will have many transmission organizations, and it is impossible for the transmission organization to achieve 100% speed synchronization, so it is necessary to introduce ------ The final motor speed of the pendulum roller is *** := main speed + (+-auxiliary correction change) Use the site ...

Consider the timing of increasing the capacity of the inverter - Delta inverter Consider the timing of increasing the capacity of the inverter - Delta inverter

1. The rated current of the inverter is low As mentioned above, when the rated current of some inverters is less than the rated current of the motor of the same capacity, the inverter with a larger gear should be considered according to the load condition of the motor. 2. The motor may be overloaded for a short time Since the electric motor ...

Regular diagnosis and repair method of Delta servo motor Regular diagnosis and repair method of Delta servo motor

1. Common faults of motor heating up too high or smoke motor Causes: 1. Excessive load; 2. Two-phase operation; 3. Blocked air duct; 4. The working temperature is too high; 5. Interphase or inter-turn short circuit fault of motor stator winding; 6. Motor stator winding grounding device; 7. The power supply voltage is too high or too low; Overhaul...

Delta servo system composition Delta servo system composition

The servo system is mainly composed of a servo controller, a drive circuit, a servo motor and the corresponding reaction testing equipment. (1) Servo motor Servo motor refers to the motor that controls the mechanical components in the servo system, and the servo motor has an encoder inside, which can respond to the movement in real time.

Delta unveiled the ASDA-A2 series of AC servo motors and drives Delta unveiled the ASDA-A2 series of AC servo motors and drives

New Delhi, September 2, 2010 – Delta Group, the world's largest supplier of switching power supplies and brushless DC fans, is committed to innovation, energy efficiency and environmental protection, and has launched a new and advanced high-performance ASDA-A2 series of servo motors and servo drives for motion control and networking in India.

Whether the inverter needs to be added to the line - Delta Whether the inverter needs to be added to the line - Delta

The role of the "communication input reactor" of the inverter input device is mainly to improve the power factor of the communication power supply on the communication side of the input side; It is useful to eliminate the higher harmonics on the input side to avoid damage to other electrical equipment caused by voltage distortion; Eliminate the three-phase AC power phase ...

Inverter Fault Repair Test Method - Delta Inverter Fault Repair Test Method - Delta

Static quizzes 1. Test the rectifier circuit Find the P and N ends of the DC power supply inside the inverter, adjust the multimeter to the resistance X10 gear, connect the red watch rod to P, and separate the black watch rod to R, S, T. Instead, connect the black watch rod to the P...

Excessive inverter capacity poses a hazard to electrical equipment – Delta Excessive inverter capacity poses a hazard to electrical equipment – Delta

(1) The harmonic current will directly cause the additional heating of the motor, so that the stator of the motor will exceed the rated temperature rise of the motor itself, so that the rated output capacity of the motor will be greatly reduced. ​ (2) The current wave output of the inverter ...

Requires an inverter speed control application – Delta Requires an inverter speed control application – Delta

Inverter is a kind of speed regulation equipment, where is there a place to use motor speed regulation, especially asynchronous motor speed regulation, will use inverter, now it is mainly used in industrial equipment on a large scale, because the motor is the heart of industry, and three-phase asynchronous motor occupies the vast majority of the share, ...

Common problems of VFD control motors - Delta Common problems of VFD control motors - Delta

Question 1. Why use a VFD to control the motor? Speaking of this question, let's first take a brief look at these two devices. The motor is a rational load, which hinders the change of current, and a large change in current will occur when it is started. VFD, which is actually made up of a rectifier inverter circuit, ...

Common knowledge points of Delta inverters Common knowledge points of Delta inverters

1. How to set the acceleration and deceleration time of Delta inverter? Solution(s): The acceleration time of Delta's inverter is the time it takes for the driver to accelerate from 0.0Hz to "high operating frequency". Deceleration time refers to the deceleration time required for the inverter to decelerate from "high operating frequency" to 0.00Hz.

The benefits of using an inverter – Delta inverter The benefits of using an inverter – Delta inverter

1. Speed regulation of general motor: By changing the input voltage and frequency of the three-phase asynchronous motor, its speed can be controlled. Generally, when the motor is at low speed, the temperature rise becomes larger due to the decrease in the power of the cooling fan, and the motor load should be reduced according to the frequency. 2 ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top