The selection of thermocouples should be based on comprehensive considerations such as the operating temperature range, the required accuracy, the operating atmosphere, the performance of the measured object, the response time and the economic benefits.
1. Selection of measurement accuracy and temperature measurement range
1) When the operating temperature is 1300-1800 °C, and the accuracy is relatively high, type B thermocouple is generally selected;
2) The operating temperature is higher than 1800°C, the accuracy is not high, and the atmosphere is allowed to use tungsten-rhenium thermocouples, and tungsten-rhenium thermocouples are generally selected;
3) When the operating temperature is 1000-1300°C, and the accuracy is relatively high, S-type thermocouple and N-type thermocouple can be used;
4) K type thermocouple and N type thermocouple are generally used below 1000°C;
5) Below 400°C, E-type thermocouple is generally used;
6) T-type thermocouple is generally used for 250°C and negative temperature measurement, and the T-type thermocouple is stable and high accuracy at low temperature.
2. The choice of atmosphere
Type S, Type B and Type K thermocouples are suitable for use in strong oxidation and weak reducing atmosphere;
Type J and Type T thermocouples are suitable for weak oxidizing and reducing atmospheres, and if a protective tube with good air tightness is used, the requirements for the atmosphere are not too strict.
3. Selection of durability and thermal response
Thermocouples with large wire diameters have good durability but have a slower response, and for thermocouples with large heat capacity, the response is slow, and when measuring temperatures with large gradients, the temperature control is poor in the case of temperature control. It is more appropriate to choose an armored puppet if the response time is fast and a certain durability is required.
4. The selection of thermocouples for the nature and state of the measurement object
The temperature measurement of moving objects, vibrating objects and high-pressure vessels requires high mechanical strength, the atmosphere with chemical pollution requires protective pipes, and the insulation is relatively high in the case of electrical interference.
|
More on that
|
Common faults and solutions of intelligent temperature controllers - RTC
Master the common problems of several common intelligent temperature controllers, and solve them by yourself when you encounter problems, and you don't need to spend time and effort to find someone to repair, the common problems are as follows:
1. Heating for a period of time, the temperature does not change. Ambient temperature (e.g., room temperature 25°C) is displayed at all times
...
|
|
Common faults and analysis of thermostats
Common faults of thermostats
1. There is no display when the power is on. This type of problem first determines whether the power supply is available and whether the power supply matches the power supply required by the thermostat, and then checks whether the wiring is secure. The problem is still there, then it is the problem of the thermostat itself.
2. There is a display, and the control is wrong. This...
|
|
RRKC Thermostat – The solution to the failure of the jump thermostat switch
1. The cleanliness and finish of the contact surface have a great impact on the working state of the contact. When the appearance of the contact is rough or there is residue on the contact, it is easy to cause arcing and reduce the life of the contact. Therefore, the parts cleaning process should be improved to eliminate the residues; Add the process of residue selection, ...
|
|
What are the rich functions of RRKC thermostats – wall mounted thermostats?
The wall-mounted thermostat is an ultra-thin intelligent thermostat that integrates measurement, display, control, alarm, recording and other functions, which can realize accurate measurement and control of temperature, pressure, flow and other parameters. Available in three sizes of 5 inches, 7 inches and 9 inches, a total of 12 models are available ...
|
|
Steps for the correct adjustment of the thermostat
1. First of all, determine the set temperature of the thermostat and make sure that it is the same as the temperature you need.
2. Recognize the operating form of the thermostat, usually there are two forms of cooling and heating, and choose the corresponding form according to the demand.
3. Acknowledging the operating condition of the thermostat, usually with active ...
|
|
RLC Level Gauge - Classification and construction of pontoon level gauges
1. Classification of pontoon level gauges
The pontoon level gauge is also divided into two types: inner pontoon and outer pontoon, the so-called internal and external division refers to the place where the pontoon is installed, in the container of the liquid to be measured is the inner pontoon, and the outer pontoon is called the outer pontoon outside the liquid container to be measured.
|
|
RLC Thermostat – Precautions for Thermostat Operation
1) Measure the function
Its temperature measurement scale is mainly between -20 °C and 80 °C, and the humidity measurement scale is mainly between 20% RH and 99% RH. In addition, it has a temperature resolution of 1°C and a humidity of 1%RH.
2) Parameters and data display functions
Temperature and humidity control ...
|
|
What should I pay attention to when wiring the RKG thermostat?
1. For thermocouple input, the corresponding compensation wire should be used.
2. For RTD input, 3 wires with low resistance and no difference should be used
3. The input signal line should be far away from the power line of the instrument. Power supply and load lines to avoid noise interference
4. The instrument power cord is usually ...
|
|
RLC thermostat - common faults and solutions of intelligent temperature controllers
1. Heating for a period of time, the temperature does not change. Displays the ambient temperature of the site at all times (e.g. room temperature 25°C)
In case of such failures, first check whether the SV value setting value is set, whether the instrument OUT indicator is lit, and whether the No. 3 and 4 terminals of the "multimeter" measuring instrument have 12VDC output.
|
|
RRKC thermostat - five common faults and solutions of smart thermostats
After heating for a while, the temperature does not change. Displays the ambient temperature of the site at all times (e.g. room temperature 25°C)
In case of such a fault, first check whether the SV value setting value is set, whether the OUT indicator of the meter is lit, and whether the No. 3 and No. 4 terminals of the meter are 12VDC output with the "multimeter". ...
|
|
RKC converter - an introduction to the classification of converters
Analog-to-digital converters
The analog-to-digital converter comprises a first transmission circuit, which receives an input voltage and an output clock signal, which is phase-shifted, depending on the input voltage, and a second transmission circuit receives a reference voltage and an input clock signal, and outputs a reference clock signal, which ...
|
|
How to set the parameters of RKC thermostat RH900
1. Lower limit deviation alarm setting: press the SET key to select and display "SLP", the green display screen displays the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. This parameter indicates the difference between the alarm point and the master setpoint.
2. The upper limit deviation alarm is set ...
|
|
Classification of thermostats and their brief introduction
Pop-up thermostat
Bimetal Disc Jump Thermostat is a kind of bimetal sheet after constant temperature as a heat-sensitive reaction component, when the temperature of the main part of the product rises, the heat generated is transferred to the bimetal disc, and when the operating temperature is set, it acts quickly, and acts through the mechanism to act as a contact ...
|
|
RKC converter – the design essentials of the power converter
In the design of power converter, firstly, the circuit topology is determined according to the load requirements, and the composition and backup mode of the power converter are determined, and the main parameters of the power converter are input voltage range, output voltage accuracy, load stability, voltage stability, output ripple, efficiency and dynamic.
|
|
RRKC thermostats – the commissioning steps of mechanical thermostats
1. Confirm the angle sample first. See where the angle of the sample is today.
2. Pick up the thermostat, first confirm whether the switch of the thermostat is tight, stuck, whether the white dot falls off, whether there is sound when the thermostat contacts are in contact, and if there is no sound, there should be two possibilities!
...
|
|
RK Thermostat - 5 Common Faults of Thermostat and Solutions
1. After heating for a period of time, it is found that the temperature has not changed, and the temperature has been displayed at the time of the ambient temperature.
In this case, you need to check that the SV value setting value is set, whether the OUT value indicator of the meter is not lit, and whether the No. 3 and 4 segments of the universal meter are 12VD ...
|
|
RKC thermostat - what should be paid attention to when maintaining the thermostat?
1. Do not wipe with acidic, alkaline and other corrosive liquids and water-containing rags when cleaning, so as not to damage the temperature controller and affect its normal use.
2. Do not decorate and cover the temperature controller. The thermostat has a built-in temperature sensor to sense the outside temperature. Therefore, Wen ...
|
|
RKC Thermostat – Teach you how to choose a thermostat
(1) Size selection
When replacing the thermostat, choose according to the original size; The newly added thermostat should take into account the overall coordination of the cabinet installed, too large to fit, too small to see the display, the same function of the thermostat, the price of large volume will be more expensive, small size may function expansion...
|
|
RRKC Thermostat – Questions and Precautions About Thermostat Expansion Modules
1. Under what circumstances should I use a thermostat to expand the module?
The gradual development of the heating field is now very well recognized, and more and more users have begun to install electric heating, of course, when installing electric heating for users, they have also encountered some headaches.
For example, a large area ...
|
|
RK thermostat - common problems and solutions of electric floor heating stand-alone thermostat
Fault 1: The thermostat does not turn on (the screen does not display)
Analyze the causes
1. Wrong wiring;
2. The voltage of the input terminal is not enough or the input terminal is damaged by the empty leakage guarantee;
3. Whether the cable between the panel and the power board is broken or plugged incorrectly;
4. Load short circuit or broken ...
|
|