1. After heating for a period of time, it is found that the temperature has not changed, and the temperature has been displayed at the time of the ambient temperature.
In this case, you need to check whether the SV value setting value is set, whether the OUT value indicator of the meter is not lit, and whether the No. 3 and No. 4 segments of the universal meter have 12VDC output. If the light is on, and the No. 3 and No. 4 terminals also have 12VDC output, the problem is that the control part of the heating element is to check whether there is an open circuit during the control, the device specification is not correct (for example, the 220V circuit is connected to the 380V device), whether the line connection is wrong, etc. At the same time, it is also necessary to see if there is a short circuit problem with the sensor, when the thermocouple is short-circuited, the temperature control instrument will always display the room temperature!
2. After heating, the temperature is getting lower and lower
In this case, the positive and negative poles of the sensor are generally reversed, and you need to check the input terminal wiring of the instrument sensor, thermocouple: 8 to the positive pole, 9 to the negative pole; PT100 thermal resistance: 8 to monochrome wire, 9 to negative electrode; PT100 RTD: 8 to monochrome wires, 9 and 10 to two wires of the same color
3. After heating for a period of time, the temperature displayed by the thermostat is quite different from the actual temperature of the heating element, such as about 100 degrees
For example, the temperature control meter is a K-type thermocouple input, but the J-type thermocouple is actually installed to measure the temperature.
4. The PV window of the meter displays HHH or LLL characters.
In this case, there is a problem with the signal measured by the instrument, the meter measurement temperature Du Yu -19 °C is to display LLL, and HHH is displayed when it is higher than 849 °C. If the temperature sensor is a thermocouple, you can remove the sensor, directly use the wire to short the thermocouple input terminals (8 and 9 terminals) of the instrument, after powering on, if the meter can display the room temperature normally (on-site ambient temperature such as: 30 °C), then the problem lies in the temperature sensor, use a multimeter tool to detect whether the temperature sensor (measuring thermocouple or PT100 thermal resistance) has an open circuit (disconnection), whether the sensor wire is reversed, wrong, or the specifications of the sensor are inconsistent with the instrument.
If all of the above problems are ruled out, the internal temperature measurement circuit of the meter may be burned due to leakage of the sensor.
5. The control is out of control, the temperature exceeds the set value, and the temperature has been rising.
In case of such a fault, first check whether the OUT indicator of the meter is lit at this time, and whether the No. 3 and No. 4 terminals of the DC voltage level measuring instrument with the "multimeter" have 12VDC output. If the lights are not on, there is no 12VDC output at terminals 3 and 4. This indicates that the problem is with the control device of the heating element (e.g.; AC contactors, solid state relays, relays, etc.). It is necessary to check whether the control device has a short circuit, the contact cannot be opened, and the wrong line is connected in real time.
|
More on that
|
RRKC thermostat – the main function of the thermostat
In most cases, in Europe, the thermostat is a necessary accessory for the wall-hung boiler, and the two are delivered to the user at the same time, and most of the thermostats equipped are intelligent thermostats. In China, nearly 95% of the wall-hung boilers that have been installed in operation and are being installed and debugged and ready to be put into use are not equipped in advance.
|
|
Steps for the correct adjustment of the thermostat
1. First of all, determine the set temperature of the thermostat and make sure that it is the same as the temperature you need.
2. Recognize the operating form of the thermostat, usually there are two forms of cooling and heating, and choose the corresponding form according to the demand.
3. Acknowledging the operating condition of the thermostat, usually with active ...
|
|
RRKC thermostat wiring installation and some precautions
The rkc controller was developed by Japan and is mainly used in plastics and stoves. Of course, it is also widely used in China's industry, there are many people who do not know much about the rkc controller, and some even feel unfamiliar.
|
|
How to set the parameters of RKC thermostat CD901?
1. Lower limit deviation alarm setting: press the SET key to select and display "SLP", the green display screen displays the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. This parameter indicates the difference between the alarm point and the master setpoint.
2. The upper limit deviation alarm is set ...
|
|
RRC thermostat - the principle of sudden jump thermostat, how to judge the good or bad?
1. What is the principle of the sudden jump thermostat?
The sudden jump thermostat is a kind of thermostat, which is a series of automatic control elements that are physically deformed inside the switch according to the temperature change of the working environment, resulting in some special effects and on-off action. Sudden jump ...
|
|
RKC Level Gauge - Preservation and storage of float level gauges in daily use
1. To avoid damage to the instrument, pay attention to the correct protection method: in order to ensure the accuracy of the instrument and avoid damage to the instrument, try not to use the protection instrument of isolator or other isolation devices. If you have to do it, you should also pay attention to the careful selection, determine the isolation solution, and wash the isolation film correctly, ...
|
|
RLC thermostat – the wiring method of the thermostat
1. Prepare the thermostat, wires, and thermal resistance, and print out the wiring diagram of the thermostat
2. Use wire strippers to strip off the wire skin, use crimping pliers, and press the wire end to the cold-pressed terminal.
3. Connect the 220V power supply to the inlet terminal of the thermostat, and connect the thermal resistance to the thermostat ...
|
|
RKC Level Gauge – Installation of a pontoon level gauge
When transporting and unpacking, it is necessary to avoid excessive shock and vibration;
The installation should be firm and reliable, and the pontoon should be installed vertically to prevent the pontoon from colliding with the interior wall of the pontoon;
When the pontoon is hooked, it should not swing or pull and compress sharply, so as not to damage the sensor and reduce the accuracy of the instrument;
...
|
|
RKG thermostat - an introduction to the relevant knowledge of temperature controllers
The temperature controller is an electrical switchgear that controls the temperature of an air-conditioned room. The temperature range in the air-conditioned room controlled by the temperature controller is generally 18°C--28°C. The temperature controller commonly used in window air conditioners uses the principle of pressure to push the contacts on and off. Its structure consists of bellows ...
|
|
Initialization parameter setting of the rkc thermostat
1. Press the ISET) button for 2 seconds to enter the parameter setting mode, press ISET until "LCK" is displayed, press the [] key to move the cursor to the thousands, and press the [] button to change the number of thousands from "0" to "1" to display "1000" to unlock.
2. Press the ISET button for 3 seconds to return to SV/PV display mode
3. Press [SET]+ ...
|
|
Introduction and wiring method of Japan physical and chemical RKC thermostat
The core control algorithm of the temperature regulator is PID control, P (Proportional) ratio + I (Integral) point + D (Differential) differential control. In addition to the traditional PID control algorithm, RKC also has ON-OFF control, custom parameter control, adaptive parameter control and other algorithms, ...
|
|
Wiring method and control method of RKC thermostat
1. Wiring method
Take CD901 as an example,
L(1) pin to 220 volt live wire,
N(2) pin 220 volt neutral wire,
3,4 pins for the first output,
5,6 pins for the second output,
7, 8, 9 pins are alarm output,
The last three legs are connected to ...
|
|
RRC thermostat - introduction to the working principle and classification of electronic thermostats
Principle of electronic thermostat:
The electronic temperature controller (resistive type) is measured by the method of resistance temperature sensing, and generally uses platinum wire, copper wire, tungsten wire and semiconductor (thermistor, etc.) as the temperature measurement resistor, which has its own advantages and disadvantages. Household Air Conditioner Temperature Controller ...
|
|
RLC thermostat - a classification introduction of floor heating thermostats
Floor heating thermostats can be divided into digital thermostats and analog thermostats according to different input and output forms. Digital thermostats generally have liquid crystal display or digital tube display panels, and set and control the temperature through buttons, while analog thermostats generally use knobs or slider band wave wheels to set ...
|
|
What should I pay attention to when wiring the RKG thermostat?
1. For thermocouple input, the corresponding compensation wire should be used.
2. For RTD input, 3 wires with low resistance and no difference should be used
3. The input signal line should be far away from the power line of the instrument. Power supply and load lines to avoid noise interference
4. The instrument power cord is usually ...
|
|
RK Thermostat - The working principle and device precautions of liquid expansion thermostat
How liquid expansion thermostats work
Liquid expansion thermostat is a physical phenomenon (volume change) that causes the material (generally liquid) in the temperature sensing part of the thermostat to undergo corresponding thermal expansion and cold contraction when the temperature of the controlled object changes, and the diaphragm box connected with the temperature sensing part expands or ...
|
|
RKC thermostat operation attention and its main features
RKC thermostat operation attention
· Clean the instrument only after the power is off;
· Please use a soft cloth or cotton paper to remove stains on the monitor;
· The display is easy to be scratched, it is forbidden to use hard object to operate the panel buttons, otherwise the keys will be damaged or scratched.
Key features:
...
|
|
RHK thermostat - the use of electronic thermostat and its classification introduction
First, the use of electronic temperature controller
The electronic temperature controller (resistive type) is measured by the method of resistance temperature sensing, and generally uses platinum wire, copper wire, tungsten wire and semiconductor (thermistor, etc.) as the temperature measurement resistor, and these resistors have their own advantages and points. Home Air Conditioner ...
|
|
RKC thermostat – the correct way to adjust the thermostat
1. Set temperature: Press the SET button to set or view the temperature set point. Press the SET key digital tube character start flashing, indicating that the appearance has entered the setting state, press the △ key to increase the set value, press the ▽ key to decrease the set value, press and hold the △ key or ▽ key The data will change rapidly, press the SET key again The appearance will return ...
|
|
RKC Thermostat - How to Choose a Hot Spot Couple?
The selection of thermocouples should be based on comprehensive considerations such as the scale of the operating temperature, the required accuracy, the atmosphere of the application, the performance of the measurement target, the response time and the economic benefits.
1. Selection of measurement accuracy and temperature measurement scale
1) The operating temperature is 1300-1800 °C, and the accuracy is required to be more accurate than ...
|
|