How to set the parameters of RKC thermostat RH900

Create Date: 2024-8-30 12:03:23|Source: RKC

1. Lower limit deviation alarm setting: press the SET key to select and display "SLP", the green display screen displays the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. This parameter indicates the difference between the alarm point and the master setpoint.

2. Upper limit deviation alarm setting: press the SET key to select "SHP", the green display screen will display the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. This parameter indicates that the alarm point is higher than the master setpoint.

3. Proportional range setting: press the SET key to select and display "P", the green display screen will display the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. The higher the "P" value, the lower the sensitivity of the thermostat's main relay output, and the smaller the "P" value, the higher the sensitivity of the thermostat's main relay output.

4. Integration time setting: press the SET key to select "I", the green display screen displays the value of the parameter, and select the shift, increment, decrement key to set or modify the parameter. The shorter the set integration time, the stronger the integration effect.

5. Differentiation time setting: press the SET key to select "D", the green display screen displays the value of the parameter, and select the shift, increment, decrement key to set or modify the parameter. The longer the differential time set by the instrument, the stronger the correction will be made by differentiation.

6. Proportional period setting: press the SET key to select and display "T", the green display screen displays the value of the parameter, and select the shift, increment, decrement key to set or modify the parameter.

7. Auto-tuning setting: press the SET key to select and display "Aτ", the green display screen displays the value of the parameter, and select the shift, increment, decrement key to set or modify the parameter; A setting of "00" indicates that autotuning is off, and a setting of "01" indicates that autotuning is started.

8. Lock parameter setting: press the SET key to select and display "OK", the green display screen shows the status of the lock, select the shift, increment, decrement key to set or modify the parameter; If this parameter is set to 00, it is not locked, if it is set to 01, if it is set to lock only parameters other than the master, and if it is set to 02, all parameters are locked. After the parameter is locked, others cannot modify it, and when it needs to be modified, it must be unlocked, that is, it is set to "00".

9. Main control temperature upper limit setting: press the SET button to select and display "SOH", the green display screen will display the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter; This parameter indicates that the operating temperature of the main control relay cannot be higher than this value, otherwise, the set temperature of the main control will be invalid

10. Temperature correction setting: press the SET key to select and display "SC", the green display screen displays the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter; This function can be used to correct the measurement deviation after a long period of operation of the thermostat. If the measured value is 2°C smaller, you can set this parameter to 02, and if the measured value is 2°C larger, you can set this parameter to -2. When in the second setting area, after pressing the SET button for more than 5 seconds, the system will save the setting parameters and exit the setting state, returning to the normal state. After the setting state is set, if you do not exit the setting state according to the correct operation, the system will automatically exit the setting state after 30 seconds
How to set the parameters of RKC thermostat RH900

More on that
RRKC thermostats – about output and control performance RRKC thermostats – about output and control performance

When using a temperature controller to control a heater, it is necessary to convert the control calculation results of the temperature controller into electricity and apply it to the heater. Electromagnetic relays, solid state relays or phase controllers are usually used for conversion. Depending on the conversion method, the output of the temperature controller is different ...

RRKC thermostat – the correct way to set up the thermostat RRKC thermostat – the correct way to set up the thermostat

Press the SET button to set or view the temperature set point, press the SET key digital tube characters to start flashing, indicating that the instrument has entered the setting state, press the △ key to increase the set value, press the ▽ key to decrease the set value, press and hold the △ key or ▽ key The data will change rapidly, press the SET key again The instrument returns to normal working condition ...

Wiring method of the RKG thermostat Wiring method of the RKG thermostat

Take CD901 as an example, L(1) pin to 220 volt live wire, N(2) pin 220 volt neutral wire, 3,4 pins for *** output, 5,6 pins for the second output, 7, 8, 9 pins are alarm output, The rear three pins are connected to thermocouples or PT100 and so on.

What are the technical parameters of the rkc thermostat - the jump thermostat? What are the technical parameters of the rkc thermostat - the jump thermostat?

1. Electrical parameters: (1) VDE, CQC, UL, TüVAC250V 50-60Hz 10A (resistive load) (2) ULAC125V 50Hz 15A (resistive load) 2. Operating temperature range: -50-270°C (optional), temperature accuracy: ≥ ±2°C 3. Reset and action ...

RLC thermostats – a common failure of mechanical thermostats RLC thermostats – a common failure of mechanical thermostats

1. The terminal post of the thermostat is stuck and falls off Cause the compressor not to start, the thermostat dynamic and static contacts can not be disconnected, so that the compressor does not run, the thermostat contacts can not be disconnected, so that the motor of the refrigerator compressor does not stop, in addition to the balance elastic force is too weak, it can also be ...

RKC converters – what are the functions of converters? RKC converters – what are the functions of converters?

1. Power conversion: convert the voltage (rated 100V) and current (rated 5A or 1A) of the transformer into voltage (several volts) to meet the requirements of weak current components. 2. Isolation: current, secondary side security, and work grounding are used to ensure the safety of people and equipment, while weak current ...

Introduction to the functions of the RKC temperature control meter Introduction to the functions of the RKC temperature control meter

(1) RH400 size: 48*96, depth 60, about 250g Details: ●A variety of input types are available: 1) Thermocouples: K, J, R, S, B, E, N, T, W5RE/W6RE, PL‖, U, L 2) Temperature measurement RTD input: PT100, JPT100...

RKC Level Gauge – The structure of a float level gauge RKC Level Gauge – The structure of a float level gauge

(1) For the indicator, also known as the display panel, the indicator plays the role of local display, convenient for long-distance observation of the actual situation of the liquid level, the indicator is generally bundled with the pontoon, easy to install. (2) It is a magnetic float, which is located in the pontoon and is in direct contact with the liquid to be measured, ...

Initialization parameter setting of the rkc thermostat Initialization parameter setting of the rkc thermostat

1. Press the ISET) button for 2 seconds to enter the parameter setting mode, press ISET until "LCK" is displayed, press the [] key to move the cursor to the thousands, and press the [] button to change the number of thousands from "0" to "1" to display "1000" to unlock. 2. Press the ISET button for 3 seconds to return to SV/PV display mode 3. Press [SET]+ ...

Causes and treatment methods of inverter overvoltage Causes and treatment methods of inverter overvoltage

 1. According to the theory of cutting off the overvoltage, when the transformer is cut off, the current in the transformer inductance cannot be abruptly changed, and the stored magnetic field energy forms a vibration between the excitation inductance of the transformer and the ground capacitor, and the overvoltage occurs. 2. Transformer ...

What are the common devices for RKC thermostats – digital displays? What are the common devices for RKC thermostats – digital displays?

In a variety of electronic control equipment, digital display has become an indispensable and important link. The electronic devices and corresponding driving circuits used for digital display are called digital displays. Commonly used digital displays include glow digital tube displays, fluorescent digital tube displays, projection ...

RKC Level Gauges – How to Install Float Level Gauges Correctly RKC Level Gauges – How to Install Float Level Gauges Correctly

In general, the following points should be followed when installing a float level timer: 1. In order to prevent the float from sliding or hitting the sealed tube at high speed during transportation, causing the measuring belt to fall out, the instrument is fixed at the bottom of the sealed tube with a clamp before leaving the factory, and the magnet is on the top of the sealed tube.

RTC thermostat - how to set the parameters of the thermostat RTC thermostat - how to set the parameters of the thermostat

1. Lower limit deviation alarm setting: Press the SET key to select and display "SLP", the green display screen displays the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. This parameter indicates the difference between the alarm point and the master setpoint. 2. The upper limit deviation alarm is set ...

What should I pay attention to when operating the RKC thermostat? What should I pay attention to when operating the RKC thermostat?

The instrument can be cleaned only after the power is off; To remove stains from the monitor, use a soft cloth or cotton paper; The display is easy to be scratched, and it is forbidden to use hard objects to operate the panel buttons, otherwise the keys will be damaged or scratched. ...

RHK thermostat – a rapid detection method for common air conditioner thermostats RHK thermostat – a rapid detection method for common air conditioner thermostats

1 Bellows or diaphragm air conditioner thermostat Fault Symptom: Poor contact or burning, resulting in the circuit cannot be connected; The frequent action of the contact arc and sticking causes the circuit to be unbreakable; Leakage of thermostat in the temperature sensing chamber, causing the contacts to fail to operate and lose control ...

A few things to note about the installation of the RKC thermostat A few things to note about the installation of the RKC thermostat

1) For RTD input, 3 wires with low resistance and no difference should be used. 2) The input signal line should be far away from the power line of the instrument, the power supply line and the load line to avoid noise and annoyance. 3) The power cord of the instrument is generally annoyed by the power supply. 4) Instrument complement ...

The main technical specifications of the RKG thermostat The main technical specifications of the RKG thermostat

Input: all kinds of thermocouple (TC), RTD standard current and voltage signals (see input type table); Basic error: 0.5% of the input full-scale ±±1 word; Resolution: 1°C, 0.1°C; Sampling period: 3 times/sec Alarm function: ...

RLC thermostat - common faults and solutions of intelligent temperature controllers RLC thermostat - common faults and solutions of intelligent temperature controllers

1. Heating for a period of time, the temperature does not change. Displays the ambient temperature of the site at all times (e.g. room temperature 25°C) In case of such failures, first check whether the SV value setting value is set, whether the instrument OUT indicator is lit, and whether the No. 3 and 4 terminals of the "multimeter" measuring instrument have 12VDC output.

RRKC thermostats – the commissioning steps of mechanical thermostats RRKC thermostats – the commissioning steps of mechanical thermostats

1. Confirm the angle sample first. See where the angle of the sample is today. 2. Pick up the thermostat, first confirm whether the switch of the thermostat is tight, stuck, whether the white dot falls off, whether there is sound when the thermostat contacts are in contact, and if there is no sound, there should be two possibilities! ...

RLC Level Gauge - Classification and construction of pontoon level gauges RLC Level Gauge - Classification and construction of pontoon level gauges

1. Classification of pontoon level gauges The pontoon level gauge is also divided into two types: inner pontoon and outer pontoon, the so-called internal and external division refers to the place where the pontoon is installed, in the container of the liquid to be measured is the inner pontoon, and the outer pontoon is called the outer pontoon outside the liquid container to be measured.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top