Megmeet PLC – Analysis of common failures of PLC

Create Date: 2024-8-30 12:03:23|Source: MEGMEET

1. The CPU is abnormal

When the CPU is abnormally alarmed, check all the devices connected to the internal bus of the CPU unit. The specific method is to replace the potentially problematic units sequentially, find out the problematic units, and deal with them accordingly.

Second, the memory is abnormal

When the memory is abnormally alarmed, if it is a problem with the program memory, it still cannot be solved after ab initio programming, this situation may be caused by the disturbance of noise to change the program, otherwise the memory should be replaced.

3. The input/output unit is abnormal, and the expansion unit is abnormal

When this kind of alarm occurs, the connection status of the input/output unit and the extension unit adapter and the cable connection should be checked first, and the unit should be replaced after determining the unit where the problem occurred.

4. Non-implementation of procedures

In general, it can be viewed according to the process of input-program execution-output

(1) Input viewing is identified by the input LED indicator or by the input monitor composed of a writer. When the input LED is not lit, you can start to conclude that it is a problem with the external input system, and then check it with the multimeter. If the output voltage is abnormal, it can be concluded that the input unit is a problem. When the LED is on but the internal monitor is not visible, it can be considered a problem with the input unit, CPU unit, or expansion unit.

(2) The program is viewed through a monitor on the writer. When the contact status of the ladder diagram does not match the result, it is a program error (such as the use of two layers of internal relays, etc.), or a problem in the calculation part.

(3) Output view: Identification can be identified by output LED indicator. If the calculation result is correct but the output LED indication is incorrect, it can be considered to be a problem with the CPU unit or I/O interface unit. When the output LED is bright but there is no output, it can be determined that there is a problem with the output unit or an external load system.

Due to the different PLC models, the I/O and LED connection methods are different (some are connected to the I/O unit interface, and some are connected to the I/O unit). Therefore, the scale of the problem based on LED discrimination is also different.

5. Some procedures are not implemented

The inspection method is the same as the previous item, but if the input time of the counter, step controller, etc. is too short, there will be no echo problem, in this case, it is necessary to check whether the input time is large enough, and the check can be carried out according to the connection of the input time (the maximum response time of the input unit + the time of operation and scan multiplied by 2).

6. If the power supply is powered off for a short time, the program content will also disappear

(1) First check if there is a problem with the battery.

(2) After repeatedly turning on and off the power supply of the PLC itself. In order for the microprocessor to start up correctly, the PLC is equipped with a circuit for the initial reset point and a circuit for saving the program when the power supply is disconnected. When there is a problem with this circuit, the program cannot be saved. Therefore, you can check the power supply on and off.

(3) If the battery abnormal alarm still appears after replacing the battery, it can be determined that it is caused by the abnormal increase of the leakage current of the memory or external circuit.

(4) The on/off of the power supply is always synchronized with the machine system, and the noise impact of the machine system can be viewed. Since the disconnection of the power supply is often a problem that occurs at the same time as the operation of the machine system, most of it is caused by the strong noise generated by the motor or winding.

7. PROM does not work

Check to see if the PROM connection is good, and then decide if you need to replace the chip.

8. After the power is restarted or reset, the action stops

This problem can be attributed to noise disturbance or poor contact within the PLC. The cause of noise is generally caused by the reduction of small capacitor capacity or poor function of components on the circuit board, and the cause of poor contact can be viewed by gently knocking on the PLC body, and the connection status of the cable and the adapter can also be checked.
Megmeet PLC – Analysis of common failures of PLC

More on that
Megmeet PLC – System integration for PLC Megmeet PLC – System integration for PLC

In the manufacturing industry, there are a large number of open-loop sequential control based on switching quantities, which carries out sequential action numbers according to logical conditions and operates in chronological order; In addition, there is the control of chain protection actions according to the logical relationship that is not related to the sequence and timing; As well as a large number of switching quantities, pulse quantities, gauges...

Megmeet PLC - an introduction to the classification of PLC Megmeet PLC - an introduction to the classification of PLC

There are many types of PLC products, and their specifications and performance also vary. PLCs are usually classified according to their different structural forms, differences in functions, and the number of I/O points. 2.1 Classification by structural form According to the structural form of PLC, PLC can be divided into whole ...

Megmeet PLC - the hardware composition of PLC control Megmeet PLC - the hardware composition of PLC control

1. Power components The power supply assembly is used to provide the power required for the operation of the PLC, and the external power supply can be converted into a power supply for the PLC internal and applicable to the case. 2. Microprocessor CPU and memory components Microprocessor CPU is the core device of PLC, and CPU is different from each manufacturer.

Megmeet inverter - 5 precautions for the use of inverter Megmeet inverter - 5 precautions for the use of inverter

1. The circuit board inside the inverter belongs to precision electronic components, which needs to be moisture-proof and dust-proof, and the temperature and humidity are not too high, and cannot be installed on the bare wall, so the inverter should be installed in the middle of the control cabinet; The inverter should be installed vertically, and the installation should be avoided directly above and below ...

Megmeet PLC – 10 PLCs integrated failure analysis Megmeet PLC – 10 PLCs integrated failure analysis

1. Grounding problems The grounding requirements of the PLC system are relatively strict, and it is best to have an independent dedicated grounding system, and it should also be noted that other equipment related to PLC should also be reliably grounded. When multiple circuit grounding points are connected together, unexpected currents can be generated, resulting in logic errors or ...

Various welding methods for Megmeet welding machines Various welding methods for Megmeet welding machines

1) Hand arc welding (STICK) Shielded Arc Welding (abbreviated SMAW) in English, The principle is: the arc occurs between the coating electrode and the base metal, and the welding method of arc thermal ablation electrode and base metal is used. The outer layer of the electrode is covered with solder, which is dissipated in case of heat.

Megmeet inverter – three ways to connect the PLC to the inverter Megmeet inverter – three ways to connect the PLC to the inverter

(1) Use the analog output module of PLC to control the analog output module of the inverter The analog output module of the PLC outputs 0-5V voltage signal or 4-20mA current signal, which is used as the analog input signal of the inverter to control the output frequency of the inverter. This control method is simple to wiring, but it needs to be selected and changed.

Megmeet inverter - precautions for inverters at high temperatures Megmeet inverter - precautions for inverters at high temperatures

1. Carefully monitor and record the display parameters on the man-machine interface of the inverter, and reflect the abnormality immediately; 2. Carefully monitor and record the ambient temperature of the frequency conversion room, and the ambient temperature should be between -5 °C and 40 °C. The temperature rise of the phase-shifting transformer should not exceed 130°C; 3. Summer ...

Megmeet Inverter - Summary of Common Faults of High Voltage Inverter (11-20) Megmeet Inverter - Summary of Common Faults of High Voltage Inverter (11-20)

11。 If the interface board does not communicate with the monitor and does not establish communication with the interface board, the interface board will reset the monitor every 5 seconds, and if the communication is not established within 3 minutes and 30 seconds, it will be judged as a serious fault. Whether the communication line is normal, check whether the terminal is correct; Whether the I/O board is working properly. Especially the work ...

Analysis of the fault code of Megmeet welder Analysis of the fault code of Megmeet welder

1. E1: indicates sensor failure. In this case, it is necessary to check whether the sensors of Megmeet are damaged or whether the wiring is loose. 2. E2: Indicates overweight load. At this point, it is necessary to check whether the load of Megmeet exceeds the set maximum load. 3. E3: Indicates battery ...

Megmeet inverter - common faults and treatment methods of high-voltage inverters Megmeet inverter - common faults and treatment methods of high-voltage inverters

1. Control through this abnormal failure The abnormal fault of the control channel is usually caused by the optical fiber communication between the sub-PWM board and the power unit board, which is generally caused by the following situations: 1. Poor contact of the optical fiber connection part or falling off of the optical fiber head; 2. Optical fiber signal transmitter/receiver ...

Megmeet PLC - Introduction to the basic structure of PLC controller Megmeet PLC - Introduction to the basic structure of PLC controller

1. Power supply The power supply of the PLC plays a very important role in the whole system. It can't work properly without a good and reliable power supply system, so PLC manufacturers also attach great importance to the design and manufacture of power supplies. General AC voltage fluctuations are +10% (+15%) ...

Megmeet PLC – the three programming languages of PLC Megmeet PLC – the three programming languages of PLC

1. The ladder diagram language is the most commonly used programming language in PLC programming. The CPU reads physical input into a memory table, often referred to as an "input table". The form is evaluated for use in the procedure. Different platforms, using different types of registers; In each scan cycle, follow from left to right, ...

Megmeet inverter - common faults and treatment methods of high-voltage inverters Megmeet inverter - common faults and treatment methods of high-voltage inverters

The high-voltage inverter has a highly intelligent computing level and a perfect fault detection circuit, and can provide accurate positioning of all faults, and make clear instructions on the main control interface. In practical application, we find that common faults can be divided into abnormal control channels, IGBT overcurrent, overvoltage...

Megmeet welding machine - analysis of common problems of welding machine welding Megmeet welding machine - analysis of common problems of welding machine welding

One. It is difficult to start the arc and easy to break the arc 1. Confirm that the quality of the electrode you use is good, and the poor quality electrode may not meet the requirements of high-quality welding: 2. The welding rod that has not undergone drying treatment is also not easy to arc, and causes the arc to be unstable, so that the welding defects increase, and the welding ...

The cause and treatment method of the fault code Eroc1 of Megmeet inverter The cause and treatment method of the fault code Eroc1 of Megmeet inverter

1. Overcurrent fault of inverter Fault Code: OCF. (1) Fault name: inverter overcurrent fault (2) The cause of the failure: the motor nameplate data input is incorrect: the load dragged by the motor is too heavy: the machinery is stuck; Motor stalled. (3) ...

Megmeet inverter - over-temperature protection for common fault analysis and treatment of inverter Megmeet inverter - over-temperature protection for common fault analysis and treatment of inverter

1. Over-temperature protection of inverter and its necessity The temperature protection function of the inverter is an indispensable condition to ensure the stable operation of the inverter; In the main circuit power device of the inverter, the rectifier bridge and the inverter bridge are semiconductor power devices.

Megmeet welding machine - the application and protection of AC arc welding machine should pay attention to Megmeet welding machine - the application and protection of AC arc welding machine should pay attention to

What aspects should be paid attention to in the application and protection of AC arc welding machine: (1) It should be used according to the additional welding current and load continuation rate of the welding machine, and should not be overloaded. (2) The welding machine is not allowed to be short-circuited for a long time. (3) The regulating current should be operated at no load. (4) ...

Hollysys' nationally produced SCADA system was the first to be put into application in the refined oil pipeline network of National Petroleum Pipeline Network Group Co., Ltd Hollysys' nationally produced SCADA system was the first to be put into application in the refined oil pipeline network of National Petroleum Pipeline Network Group Co., Ltd

Preface: Energy security is an overall and strategic issue related to the country's economic and social development, and is crucial to the country's prosperity and development, the improvement of people's lives, and the long-term peace and stability of society. For the first time, the 14th Five-Year Plan and the Outline of the Long-Range Objectives Through 2035 include "comprehensive energy production capacity" in the ...

Megmeet PLC – How does PLC communicate with computers? Megmeet PLC – How does PLC communicate with computers?

1. In this computer, right-click, manage, check to find the device manager, plug in the USB-PPI cable (one end is connected to the computer, the other end is connected to the PLC), the computer device manager will pop up the port USB-SERLAL CH304 (com3), the number in parentheses may change, indicating that you have found the cable. This...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top