1. The voltage level of the AC contactor should be the same as the load, and the type of contactor should be suitable for the load.
2. The accounting current of the load should be less than or equal to the additional working current of the contactor.
The turn-on current of the contactor is greater than the starting current of the load, the breaking current is greater than the breaking demand current when the load is running, and the accounting current of the load should consider the practical working environment and working conditions.
3. Check the dynamic and thermal stability for a short time.
The three-phase short-circuit current of the line should not exceed the dynamic and thermal stability current promised by the contactor, and the breaking ability of the contactor should also be verified when the contactor is used to disconnect the short-circuit current.
4. The additional voltage, current and the number and current capacity of the auxiliary contacts of the contactor suction coil should meet the wiring requirements of the control loop. It is necessary to consider the length of the line connected to the control loop of the contactor, the operating voltage value of the general introduction, and the contactor should be able to work at an additional voltage value of 85-110%. If the line is too long and the voltage drop is too large, the contactor coil may not reflect the closing instruction; Because the line capacitance is too large, it may not work for trip commands.
5. Check the operation frequency promised by the contactor according to the number of operations. If the operating frequency exceeds the specified value, the additional current should be doubled.
6. The parameters of short-circuit maintenance components should be selected in cooperation with the parameters of the contactor. When selecting, you can refer to the sample manual, which generally gives the cooperation table of contactor and fuse.
The cooperation between the contactor and the circuit breaker should be decided according to the overload coefficient of the circuit breaker and the current coefficient of short-circuit maintenance. The agreed heating current of the contactor should be less than the overload current of the circuit breaker, and the on-on and disconnection current of the contactor should be less than the short-circuit maintenance current of the circuit breaker, so that the circuit breaker can maintain the contactor.
In practice, the ratio of heating current and additional working current of the contactor is between 1 and 1.38 under a voltage level, and the overload coefficient parameters of the circuit breaker are more than 1, and different types of circuit breakers are different, so it is difficult to have a specification for the cooperation between the two, and the cooperation table cannot be formed, and the demand is calculated in practice
7. The installation interval of contactors and other components should comply with relevant national standards and specifications, and the repair and wiring spacing should be considered.
|
More on that
|
The basic component of the inverter is LS power generation
The inverter is usually divided into 4 parts: the rectifier unit, the high-capacity capacitor, the inverter and the controller.
Rectifier unit: converts alternating current with a fixed operating frequency into direct current.
High Capacitance: Stores converted electrical energy.
...
|
|
The function and function of the inverter VFD - LS produces electricity
1. Energy saving
The energy-saving effect of VFD is mainly manifested in the application of fans and water pumps. After the fan and pump load is selected for frequency conversion speed regulation, the power saving rate is 20% - 60%, because the actual power consumption of the fan and pump load is basically proportional to the cubic speed. When users ask for an average ...
|
|
What are the components of the PLC?
The basic components of PLC for power production:
1. Memory
The memory that registers the architecture software is called the architecture program memory.
The memory that registers the application software is called the user program memory.
2. Power supply
...
|
|
Key points of LS power BKN circuit breaker design
(1) The cooperation between the circuit breaker and the circuit breaker should consider the instantaneous trip device action value of the superior circuit breaker, which should be greater than the maximum expected short-circuit current at the outlet end of the lower circuit breaker.
|
|
Introduction to the design of inverter control cabinet - LS power production
The inverter should be installed inside the control cabinet, and the following problems should be paid attention to when planning the control cabinet:
1) Heat dissipation issues:
The heating of the inverter is caused by internal losses. In the inverter, the main circuit is the main circuit for the loss of each part, accounting for about 98%, and the control circuit accounts for 2%. ...
|
|
The cause of the failure of low-voltage electrical appliances - LS power generation
In the control circuit of low-voltage electrical appliances, there are simple low-voltage components such as: buttons, safe, etc.; There are also slightly messy low-voltage electrical control components, such as circuit breakers, touch devices, time relays, thermal relays and other simple components, which makes it necessary to diagnose and analyze the cause of the problem.
...
|
|
Why can't the inverter be equipped with a leakage protector - power generation
When using an inverter, a leakage maintainer must not be used. This is a major principle of the use of frequency converters.
Some users choose the corresponding leakage maintainer for the inverter when using the inverter. *The result is: the inverter moves together ...
|
|
Analysis of the problem of LS power inverter
1. What is the maintenance function of the inverter?
Maintenance functions can be divided into the following two categories:
(1) After detecting the abnormal situation, the correction action is automatically carried out, such as overcurrent loss speed avoidance, regeneration overvoltage stall avoidance.
(2) Block the PWM control signal of power semiconductor equipment after detecting the abnormality ...
|
|
LS power production automation subdivision industry service era
LS power automation drives are mainly for industrial enterprises and construction enterprises, including municipal, metallurgical, electric power, chemical and other power-oriented industrial enterprises, car, food and beverage, pharmaceutical and other professional enterprises, as well as OEM equipment manufacturing enterprises.
...
|
|
LS power generation low-voltage universal inverter vector control mode
The method of vector control frequency conversion speed regulation is to change the stator current Ia, Ib, Ic of the asynchronous motor in the three-phase coordinate system, after the three-phase - two-phase change, equivalent to the communication current Ia1Ib1 under the two-phase static coordinate system, and then after the directional rotation according to the rotor magnetic field, it is equivalent to synchronous rotation sitting.
|
|
Introduction to the output frequency of the inverter - LS power generation
1. Maximum frequency fmax, reference frequency fN and reference voltage UN
2. The upper frequency fH and the lower frequency fL
The output frequency of the inverter is limited to the upper and lower limit frequencies to prevent errors in the event of misoperation.
3. Frequency of activation
When the signal ON is activated, the ON ...
|
|
LS Electric reached a strategic cooperation with Nandu Power Supply and Changzhou Kunlan
Due to the "new infrastructure" policy, the Chinese government has vigorously promoted the new energy and ESS markets, and according to CNESA, the cumulative electrochemical energy storage scale in China will reach 19.3GW in 2023, which is expected to exceed 20% of the global market.
June 3 ...
|
|
Why can't the inverter be equipped with a leakage protector?
When using an inverter, a leakage maintainer must not be used. This is a major criterion for the use of frequency converters.
Some users choose the corresponding leakage maintainer for the inverter when using the inverter. *The result is: the inverter moves together ...
|
|
How to troubleshoot the fault of the inverter - the power inverter
Because the application method is incorrect or the setting environment is unreasonable, the inverter will simply malfunction and cause problems, or the expected operation effect will not be satisfied. In order to prevent problems before they occur, it is important to carefully analyze the cause of the problem in advance.
...
|
|
LS inverter series and its features
LS inverter, the full name of LS communication frequency conversion governor, after supplying a variety of equipment, converts direct current into communication electricity, and changes the voltage and frequency of ordinary power supply input to control the speed of the motor, to meet different industrial needs, and then complete the energy saving and environmental protection of the automation system. ...
|
|
Common faults and countermeasures of power inverters
1. OC failure
Like other inverters, overcurrent alarm is also a common fault of power inverter, in addition to the reasons for parameter settings such as acceleration and deceleration time, there are mainly the following possibilities in hardware: damage to high-power modules may cause OC alarm, low-power economical inverter ...
|
|
The method of judging the quality of components - LS power production
1. Detection of ordinary diodes
Use the MF47 multimeter to measure, connect the red and black watch pens to the two ends of the diode, read the reading, and then adjust the watch pen to measure. According to the results of two measurements, the forward resistance value of the general low-power germanium diode is 300-500Ω, and the silicon diode ...
|
|
Inverter carrier frequency adjustment method - LS power generation
A. The output voltage of the SPWM inverter is a series of pulses, and the pulse frequency is equal to the carrier frequency.
B. In the current of the motor, there is a harmonic component with a strong carrier frequency, which will cause the vibration of the motor core and announce the noise. If the frequency of the noise is the same as that of the motor core.
|
|
How to use the installation wiring of the LS inverter
1. Circuit wiring
(1) The input (R, S, T) and output (U, V, W) of the inverter cannot be connected incorrectly;
(2) Wire diameter selection
(1) The wiring of the power supply and the inverter and the wire diameter selection method of the motor of the same capacity are the same;
(2) The wiring between the inverter and the motor should consider the line electricity.
|
|
What are the determinants of the performance of LS inverters?
The quality of the control circuit determines the function of the LS inverter.
The function of the DC central circuit is to smooth the output of the rectifier circuit to ensure that the inverter circuit and the control power supply can obtain a high-quality DC power supply. When the whole ...
|
|