Method for measuring the quality of frequency converter modules – Reynolds

Create Date: 2024-8-30 12:03:23|Source: RENLE/RENOLDS

1. Test rectifier circuit:

To the P end and N end of the DC power supply inside the inverter, adjust the multimeter to the resistance X10 gear, the red watch rod is connected to P, and the black watch rod is separated from R, S, T, and there are tens of ohms of resistance in normal times, and it is basically balanced. On the contrary, the black watch rod is connected to the P terminal, and the red watch rod is connected to R, S, and T in turn, and there is a resistance value close to infinity.

Connect the red watch stick to the N-end and repeat the above steps, and you should get the same result. If there is a three-phase imbalance with the resistance value, it is clear that there is a problem with the rectifier bridge. When the red watch rod is connected to the P terminal, the resistance is infinite, which can determine the problem of the rectifier bridge or the starting resistance.

                               Method for measuring the quality of frequency converter modules – Reynolds

2. Test the inverter circuit:

Connect the red watch rod to the P terminal, and the black watch rod should be connected to U, V, and W, and there should be tens of ohms of resistance, and the resistance value of each phase is basically the same. The N-end of the black watch rod, the inversion should be infinity, repeat the above steps should get the same result, otherwise it can be determined that there is a problem with the inverter module.

3. Dynamic test: After the static test results are normal, the dynamic test can be carried out, that is, the power-on test machine. The following points must be paid attention to before and after power-on:

(1) Before powering on, it is necessary to confirm whether the input voltage is incorrect, and the 380V power supply will be connected to the 220V inverter, and the explosion machine (fried capacitors, varistors, modules, etc.) will appear.

(2) Check whether the connectors of the inverter have been correctly connected, whether the connection is loose, abnormal connection may sometimes lead to problems with the inverter, and the explosion machine will be out when it is severe.

(3) After powering on, detect the content of the problem, and preliminarily determine the problem and its cause.

(4) If there is no problem, first check whether the parameters are abnormal, and after the parameters are restored, start the inverter under the condition of no load (not connected to the motor), and test the output voltage value of U, V and W. If there is a lack of phase, three-phase unbalance, etc., there is a problem with the module or driver board.

(5) Under the condition that the output voltage is normal (no phase loss, three-phase balance), the load test should be full load test as much as possible.

More on that
Inverter acceleration and deceleration mode selection Inverter acceleration and deceleration mode selection

The selection of the acceleration form and deceleration form of the inverter is also called the selection of acceleration and deceleration curves. Generally, there are several forms of inverter, such as linear, S-shaped, semi-S-shaped, etc., and the characteristics and uses of each form are as follows. 1. Linear form The form makes the inverter ...

The inverter uses a power-saving method – Reynolds The inverter uses a power-saving method – Reynolds

As an electronic electric, the inverter itself also consumes electricity (about 3-5% of the rated power). A 1.5 hp air conditioner consumes 20-30W of electricity, which is equivalent to the length of a lamp. The inverter works under the power frequency and has the function of saving electricity, which is practical. However, the conditions are: First, high power and ...

Misunderstanding of inverter control loop wiring - Reynolds Misunderstanding of inverter control loop wiring - Reynolds

1. The wires of the inverter control circuit should be strictly distinguished from the main circuit cable (power line) and placed separately. This effectively prevents the inverter's control circuit from being disturbed by harmonics in the inverter's main circuit. 2. To separate the connection of the inverter from the terminals or contacts of other control circuits, ...

Reynolds-5G empowers the paper industry to improve quality and efficiency of the industrial IoT control system Reynolds-5G empowers the paper industry to improve quality and efficiency of the industrial IoT control system

From September 23rd to September 25th, 2020, the 2020 China International Paper Technology Exhibition was held in Hall D1 of Suzhou International Expo Center.

There will be problems with the inverter left for a long time - Reynolds There will be problems with the inverter left for a long time - Reynolds

Most inverter brand products can rely on the heat generation of internal electrical components to remove moisture during normal use. If you don't have to do it for a long time, it's easy to get wet. The chip pins, penetrating resistors, capacitors, and inductor pins of the DIP package will be severely rusted or desoldered, resulting in on-resistance ...

Application misunderstandings and drawbacks of inverter and countermeasures - Reynolds Application misunderstandings and drawbacks of inverter and countermeasures - Reynolds

Misunderstanding: connect electromagnetic switches and electromagnetic contactors in the output circuit of the inverter In actual use, some occasions require the use of contactors for frequency converter switching: such as when the frequency conversion is faulty, switch to the power frequency operation, or when the one-to-two method is adopted, a motor is faulty, and the variable frequency is used.

Reynolds universal inverter start-up mode Reynolds universal inverter start-up mode

1. Direct launch The universal inverter insists on starting at the beginning of the time according to the set starting frequency and starting frequency, and then accelerates to a given frequency according to the selected acceleration time Second, the speed of the tracking start Universal inverter ...

Inverter selection conditions and precautions - Reynolds Inverter selection conditions and precautions - Reynolds

1. When selecting the inverter, select the inverter with the appropriate control method according to the load characteristics In addition to the inverter manufacturing process, it is also important to choose which control method of the inverter. The control method of the inverter is mainly divided into two types: open-loop control and closed-loop control. In the meantime, the open-loop control method ...

Soft start uses common faults and solutions - Reynolds Soft start uses common faults and solutions - Reynolds

In the process of daily use of soft starters, it is inevitable to encounter some improper use or failure of soft starters in the process of use 1. The user starts ...

Analysis and repair of inverter failure cases - Reynolds Analysis and repair of inverter failure cases - Reynolds

1. The inverter can not speed up the frequency increase when it starts with load The 1366S-BR 040 inverter carries a load of 37 kW fan motors. During the trial operation, it was found that the inverter could not speed up the frequency increase normally, and the HIM display was speeding up. The inverter only swings at 1-4 Hz, and the motor emits a buzzing ...

Inverter leakage solution - Reynolds Inverter leakage solution - Reynolds

1. The cause of the leakage problem Some sites use frequency converters to control the motor, which will present the problem of leakage, and the leakage voltage ranges from tens of volts to 200 volts. In view of this problem, the reasons for this shortcoming are theoretically expounded and stated as follows. Depend on...

Progressive method of robustness of automatic control cabinets – Reynolds Progressive method of robustness of automatic control cabinets – Reynolds

1. Appropriate working environment 1. The ambient temperature is suitable All manufacturers have certain rules for active temperature control cabinets. The PLC promises that the ambient temperature is usually about 0 to 55 ° C, so during the equipment process, this heating element is not placed in the PLC; The PLC should have adequate ventilation and ...

The difference between "braking" and "parking" of the inverter - Reynolds The difference between "braking" and "parking" of the inverter - Reynolds

There are two types of inverter parking. One form is called "free parking". As the name suggests, it is to quickly "power off" the motor, so that the motor can slide and park by its own inertial force (OFF2 parking); The other form is called "brake parking". So this "brake parking ...

PLC and inverter communication mode PLC and inverter communication mode

1. The switching signal of PLC controls the inverter The PLC can control the start, stop and reset of the inverter through the program; It can also control different combinations of high-speed, medium-speed and low-speed terminals of the inverter to achieve multi-stage speed operation. However, because it is controlled by switching ...

Introducing the Reynolds JJR5000 series of soft starters Introducing the Reynolds JJR5000 series of soft starters

Reynolds JJR5000 series all-digital intelligent AC motor soft starter adopts power electronics technology, microprocessor technology and modern control theory technology, which is a new type of starting equipment at the current level. This product can limit the starting current of the asynchronous motor when it starts, and is widely used in fans, ...

Motor soft start mode – Reynolds frequency inverter Motor soft start mode – Reynolds frequency inverter

Starting performance is a very important performance parameter of motor products. The large starting current of the motor is an unpreventable problem in the process of direct starting. The high current during the engine process has a great impact on both the power grid and the motor itself. Therefore, according to different working conditions and different series of motors, ...

Difference Between Soft Starter and Inverter – Reynolds Difference Between Soft Starter and Inverter – Reynolds

Soft starters and frequency converters are two completely different products. The inverter is used in the local area where speed regulation is required, and its output not only changes the voltage but also changes the frequency at the same time; A soft starter is actually a voltage regulator, which is used when starting a motor, and the output only changes the voltage and does not change the frequency. Change...

The reason for using frequency conversion speed regulation - Reynolds The reason for using frequency conversion speed regulation - Reynolds

Variable frequency speed regulation can be used in most motor drag occasions, because it can provide accurate speed control, so it can easily control the rise, descent and variable speed operation of mechanical transmission. The use of frequency conversion can greatly improve the efficiency of the process (the variable speed does not depend on the mechanical part) and at the same time ...

How to control the torque of the inverter vector according to the system - Reynolds How to control the torque of the inverter vector according to the system - Reynolds

A brief introduction to the progress of the inverter in terms of torque: This function adds the output voltage of the inverter so that the output torque of the motor is proportional to the square of the voltage, so as to improve the output torque of the motor. Improve the skill of insufficient torque at low speed output of the motor, and use the "vector manipulation" ...

Reynolds inverter parameter settings Reynolds inverter parameter settings

The use of Reynolds inverters in industrial production is very important, in addition to speed regulation, soft start effect, the important thing is to be able to save energy. There are many functional parameters of Reynolds inverter, and there are generally dozens or even hundreds of parameters for users to choose. In practice, it is not necessary to ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top