Static quizzes
1. Test the rectifier circuit
Find the P and N ends of the DC power supply inside the inverter, adjust the multimeter to the resistance X10 gear, connect the red watch rod to P, and separate the black watch rod to R, S, T. On the contrary, the black watch rod is connected to the P terminal, and the red watch rod is connected to R, S, and T in turn, and there is a resistance value close to infinity. Connect the red watch rod to the N-end and repeat the above process, and you should get the same result. If the following results are available, it can be determined that the circuit has been abnormal, A. The resistance value of the three-phase is unbalanced, and it is clear that there is a problem with the rectifier bridge. B. When the red watch rod is connected to the P terminal, the resistance is infinite, and the rectifier bridge problem or activation can be determined.
2. Test the inverter circuit
Connect the red watch rod to the P terminal, and the black watch rod separate from the U, V, and W, there should be a resistance value of tens of ohms, and the resistance value of each phase is fundamentally the same, and the reverse phase should be infinity. Repeat the above process to the N end of the black watch rod to get the same result, otherwise it can be confirmed that there is a problem with the inverter module.
Dynamic quizzes
After the test results are normal, the dynamic test can be carried out, that is, the power-on test machine. Before and after powering on, you must pay attention to the following points:
1. Before powering on, you must confirm whether the input voltage is wrong, and the 380V power supply will be fried (fried capacitors, varistors, modules, etc.) when connected to the 220V inverter.
2. Check whether the inverter's broadcast ports have been correctly connected, whether the connection is loose, abnormal connection may sometimes lead to problems with the inverter, and the explosion machine will be out when it is severe.
3. After powering on, detect the content of the problem, and preliminarily determine the problem and its cause.
4. If there is no problem, first check whether the parameters are abnormal, and after the parameters are restored, start the inverter under the condition of no load (not connected to the motor), and test the output voltage value of U, V and W. If there is a lack of phase, three-phase unbalance, etc., there is a problem with the module or driver board.
5. Under the condition that the output voltage is normal (no phase loss, three-phase balance), the load test should be a full load test as much as possible.
|
More on that
|
Precautions for long-term idle use of Delta inverter
If the inverter is to run the equipment again after being shelved for more than half a year, the probability of damage may be greatly increased due to many factors such as the placement environment, the service life of the inverter, and the load rate, and the failure usually presents the following problems:
1. After the equipment is powered on, it becomes ...
|
|
The principle, composition and function of Delta's inverter
1. What is a Delta inverter?
Delta inverter is a device that converts the power supply (50Hz or 60Hz) into a communication power supply of various frequencies to realize the variable speed operation of the motor.
|
|
Post-inverter shutdown maintenance project – Delta
1. Use a vacuum cleaner with a plastic nozzle to completely clean the inside and outside of the inverter cabinet to ensure that there is no excessive dust around the equipment.
2. Check the ventilation and lighting of the inverter room, and the ventilation equipment can work normally.
3. Check the inverter ...
|
|
Common problems with compact pressure transmitters – Delta
1. The transmitter does not return to zero under no pressure?
Answer: The cleaning method is to remove the transmitter from the device position, investigate whether the zero position is normal, and replace the pipeline sealing ring if it is normal. Check together whether the transmitter is perpendicular to the piping assembly, and if not, adjust the transmitter zero.
...
|
|
How to choose Delta's servo motor
When selecting a Delta servo motor, in principle, the selection should be based on the load conditions. There are two types of loads on the motor shaft, namely damping torque and inertial load. Both loads should be calculated correctly and their values should meet the following criteria:
1) When the machine is running with no load, in the whole speed range, Delta ...
|
|
Rated current design of inverter leakage circuit breaker - Delta
1. Install AC reactor and DC reactor. When the capacity of the inverter is greater than 500kva in the distribution transformer, and the transformer capacity is more than 10 times the capacity of the inverter, an AC reactor is installed on the input side of the inverter. And when the output voltage of the distribution transformer is unbalanced and uneven in three phases ...
|
|
How to choose Delta's power supply
1. First of all, calculate the maximum power consumption of the computer
The power consumption of the computer is different in different operating states, such as 95W on startup, 35W on standby, and up to 480W when the game is fully loaded.
The power consumption of the power supply is based on the computer ...
|
|
What are the series of Delta inverters?
1:VFD-EL,VFD-S,VFD-L,VFD-C200
Voltage 220V, 380V, power scale 100W-7.5kw
The above series are Delta's simple inverters, commonly known as economical inverters, which are used for small fans and pumps, conveyor belts on food and pharmaceutical machinery, etc., and are used for abbreviated ...
|
|
Wind turbine inverter speed regulation effect - Delta
What is the effect of speed regulation of fan inverter? According to the query materials, in industrial production, the throttling loss of the damper, baffle and other related equipment of the fan, as well as the protection and maintenance costs account for 7%-25% of the production cost.
|
|
Delta's high-performance servo ASDA-A3 series is a new product
With the rapid development of automation technology and shopping malls, customers have higher and higher requirements for the speed, accuracy and function diversification of servo products. In order to get used to the needs of shopping malls, recently, Delta launched the high-performance motion control high-end AC servo system ASDA-A3 series ...
|
|
Measures to avoid soft failure of inverters - Delta
The ways to reduce the soft fault of the inverter are: 1. Detect the overvoltage and undervoltage of the inverter; 2. Detecting overcurrent is the most frequent phenomenon of frequency conversion alarm.
Generally, the overvoltage alarm is generally presented at the time of shutdown, and the primary reason is that the deceleration time is too short or the braking resistance and braking unit have ...
|
|
Delta's soft starter component role
The soft starter is a device used to control the start and stop of the motor, which is composed of a number of components, including the soft starter controller, the soft starter conditioner, the soft starter power supply, the soft starter input and output module, the soft starter interface module, etc.
...
|
|
Inverter maintenance is easy to ignore the problem - Delta
1. After the inverter is repaired, the power number needs to be corrected, don't forget it
Generally, an inverter corresponds to a power number (also known as the number of horsepower), for example, a 75 kilowatt inverter is set under heavy load, and 100 kilowatts is set under light load. In this way, the customer will not use it to present ...
|
|
The role and application of Delta's thermostats
Delta's thermostat is a commonly used temperature control device, which can adjust the temperature according to the user's needs, and then achieve the intention of saving energy. The effect and use of Delta thermostats are also very widespread, so let's introduce the effects and uses of Delta thermostats.
...
|
|
Reduce the failure rate of Delta's inverters
Daily View Item 1:
Check whether the sound of the motor changes abnormally during operation, including whether there is vibration during the operation of the motor.
Project 2:
Check if the environment of the inverter unit has changed. For example, whether the ambient temperature is normal. Familiar with Delta's inverter ...
|
|
Delta's powerful NT series industrial-grade UPS
Delta's NT series industrial-grade UPS has always been an ideal choice for applications that require high power safety due to their high reliability and high-density planning. IGBT high-frequency switching sinusoidal pulse width modulation technology planning, which makes UPS have good power supply quality, high efficiency, low heat loss, noise ...
|
|
The power frequency motor is not normally installed with the inverter hazard
Installing a variable-frequency drive (VFD) on the power frequency motor can complete the accurate control and speed regulation of the motor, and improve the efficiency and accuracy of the motor. However, if not properly equipped and used, it may cause the following hazards:
...
|
|
Solution to Delta's overload trip fault
1. The main reason for VFD overload
(1) Mechanical overload. The main characteristic of overload is the heating of the motor, which can be detected by reading the operating current on the display.
(2) The three-phase voltage imbalance leads to excessive running current in a certain phase, resulting in overload tripping. It is characterized by uneven heating of the motor ...
|
|
Delta's active front-end and inverter's coordination
The popularity of frequency converters has brought significant energy savings to industrial applications. However, the high-frequency switching signal generated by the inverter is easy to cause electromagnetic interference and affect the power quality. Especially in industries with large loads such as lifting and elevators, it is becoming more and more obvious.
...
|
|
Delta's key steps in inverter maintenance
First, the maintenance of the inverter must first check whether the sound in the operation of the motor has changed abnormally, including, whether the motor is in operation to form a sensation.
2. Check whether the natural environment of the inverter installation has changed. For example, whether the operating temperature is normal. Learn more about Delta's inverter ...
|
|