Debugging of basic parameters of inverter - LS power generation

Create Date: 2024-8-30 12:03:23|Source: LS/Power Generation

There are many functional parameters of the inverter, and there are generally dozens or even hundreds of parameters for users to choose. In practice, it is not necessary to set and debug every parameter, and most of them only need to use the factory setting value. However, some parameters are closely related to the application of practice, and some are related to each other, so they should be set and debugged according to practice. The functions of various types of inverters are different, and the names of the same functional parameters are also inconsistent, so this paper takes the basic parameters of Fujifilm inverters as an example. Since the basic parameters are simply available for all types of inverters, it is completely possible to draw inferences from one another.

                               Debugging of basic parameters of inverter - LS power generation

1. Acceleration and deceleration time

The acceleration time is the time it takes for the output frequency to rise from 0 to the highest frequency, and the deceleration time is the time it takes to go down from the highest frequency to 0. Generally, the acceleration and deceleration time is confirmed by the rise and fall of the frequency setting signal. When the motor accelerates, the rise rate set by the frequency must be bound to prevent overcurrent, and when the motor is decelerating, the falling rate must be bound to prevent overvoltage.

Acceleration time setting requirements: the acceleration current is bound below the overcurrent capacity of the inverter, so as not to cause the inverter to trip due to the overrun; The key to setting the deceleration time is to prevent the voltage of the lubricating circuit from being too large, and not to cause the regenerative overvoltage to stall and trip the inverter. The acceleration and deceleration time can be calculated according to the load, but in the debugging, it is often used to set a longer acceleration and deceleration time according to the load and experience, and check whether there is an overcurrent and overvoltage alarm after starting and stopping the motor; Then the acceleration and deceleration time is gradually shortened, and the best acceleration and deceleration time can be confirmed by repeating the operation several times according to the criterion that no alarm is generated during the operation.

Second, the torque is increased

Also known as torque compensation, it is a method to increase the low-frequency scale f/V in order to compensate for the decrease in torque at low speed caused by the resistance of the stator winding of the motor. When set to automatic, the voltage during acceleration can be automatically increased to compensate for the starting torque, so that the motor can accelerate smoothly. If manual compensation is selected, the best curve can be selected according to the load characteristics, especially the starting characteristics of the load. Regarding variable torque loads, if the selection is not done properly, the output voltage at low speed will be too high, and the phenomenon of wasting electric energy will even occur, and even the phenomenon that the motor will have a large current when starting with a load, and the speed will not go up.

3. Electronic thermal overload protection

This function is set to protect the motor from overheating, which is to calculate the temperature rise of the motor according to the operating current value and frequency of the CPU in the inverter, and then carry out overheating protection. This function is only applicable to the occasion of "one to one", and in the case of "one to many", thermal relays should be installed on each motor.

Electronic thermal protection setpoint (%) = [rated current of motor (A) / rated output current of inverter (A)] × 100%.

4. Frequency Bondage

That is, the upper and lower amplitudes of the output frequency of the inverter. Frequency restraint is a protective function to prevent misoperation or external frequency setting signal source from malfunctioning, which causes the output frequency to be too high or too low, so as to prevent damage to the equipment. It can be set according to the practice situation in use. This function can also be used as a speed limit, such as a belt conveyor, because the material is not too much, in order to reduce the wear and tear of machinery and belt, you can choose to use the inverter drive, and the upper limit frequency of the inverter is set to a certain frequency value, so that the belt conveyor can run on a fixed, lower operating speed.

5. Bias frequency

Some are also called error frequency or frequency error setting. Its purpose is that when the frequency is set by an external imitation signal (voltage or current), this function can be used to adjust the frequency to set the output frequency when the signal is low, as shown in Figure 1. When the frequency setting signal of some inverters is 0%, the error value can be effective in the scale of 0-fmax, and some inverters (such as Mingdianshe and Sanken) can also set the bias polarity. If the output frequency of the inverter is not 0Hz but xHz when the frequency setting signal is 0% in debugging, then the bias frequency is set to negative xHz at this moment to make the output frequency of the inverter 0Hz.

6. Frequency setting signal gain

This function is only useful when setting the frequency with an external imitation signal. It is used to compensate for the inconsistency between the externally set signal voltage and the internal voltage (+10V) of the inverter; When the input signal is the largest (such as 10v, 5v or 20mA), the frequency percentage that can output the f/V graph can be calculated and set as a parameter. If the external setting signal is 0-5V, if the output frequency of the inverter is 0-50Hz, the gain signal can be set to 200%.

7. Torque restraint

It can be divided into two types: driving torque restraint and brake torque restraint. It is based on the output voltage and current value of the inverter, and the torque is calculated by the CPU, which can significantly improve the shock load recovery characteristics during acceleration, deceleration and constant speed operation. The torque restraint function enables automatic acceleration and deceleration control. Assuming that the acceleration and deceleration time is less than the load inertia time, the motor can be automatically accelerated and decelerated according to the torque setting value.

The drive torque function provides a robust starting torque, and in steady-state operation, the torque function will control the motor deterioration, and the motor torque will be bound within the maximum set value, when the load torque suddenly increases, even when the acceleration time is set too short, it will not cause the inverter to trip. When the acceleration time is set too short, the motor torque will not exceed the Z-maximum set value. A large drive torque is beneficial to the start, so it is more appropriate to set it to 80-100%.

The smaller the braking torque setting value, the greater the braking force, which is suitable for the occasion of rapid acceleration and deceleration, if the braking torque setting value is set too large, there will be an overvoltage alarm phenomenon. If the braking torque is set to 0%, the total amount of regeneration added to the main capacitor can be close to 0, and then the motor can be decelerated to a stop without using a braking resistor when decelerating. However, in some loads, such as when the braking torque is set to 0%, there will be a short time idle phenomenon when decelerating, which constitutes the repeated start of the inverter, and the current is not firm in a large way, and the inverter will trip in serious cases, which should cause attention.

8. Selection of acceleration and deceleration methods

It is also called acceleration and deceleration curve selection. Generally, there are three kinds of curves: linear, nonlinear and S, and most of them choose linear curves; The nonlinear curve is suitable for variable torque loads, such as fans, etc.; The S-curve is suitable for constant torque loads, and its acceleration and deceleration changes more slowly. Punctuality can be based on the load torque characteristics, the corresponding curve can be selected, but there are exceptions, the author in the debugging of a boiler inverter, the acceleration and deceleration curve is selected as a nonlinear curve, and the inverter trips when the operation is started, and the adjustment and change of many parameters has no effect, and then it is normal after changing to the S curve. The reason is: the induced draft fan rolls by itself due to the flue gas activity before starting, and becomes a negative load when it rotates, so that the S curve is selected, so that the frequency rise speed at the beginning of the start is slower, and then the inverter tripping is prevented, of course, this is the method selected for the inverter without starting DC braking function.

9. Torque vector control

Vector control is based on the theoretical belief that asynchronous motors have the same torque generation mechanism as DC motors. The vector control method is to decompose the stator current into regular magnetic field current and torque current, control them separately, and output the stator current composed of the two to the motor together. Therefore, in principle, the same control function can be obtained as that of DC motors. Using the torque vector control function, the motor can output the highest torque under various operating conditions, especially in the low-speed operation area.

Now the inverter is simply selected non-reverberation vector control, because the inverter can be compensated for the slip according to the load current and phase, so that the motor has very hard mechanical characteristics, and the requirements can be met in most occasions, and there is no need to set up the speed repercussion circuit outside the inverter. This function can be set by selecting one of useful and ineffective according to the practical situation.

A related function is slip compensation control, the effect of which is to compensate for speed errors caused by unfirm loads, and a slip frequency corresponding to the load current can be added. This function is primarily used for positioning control.

10. Energy-saving control

Fans and pumps are attributed to the reduced torque load, that is, with the decrease of speed, the square share of load torque and speed decreases, and the inverter with energy-saving control function is planned to have a special V/f mode, which can improve the efficiency of the motor and inverter, which can automatically reduce the output voltage of the inverter according to the load current, and then achieve the energy-saving intention, which can be set to useful or invalid according to the specific situation.

It should be clarified that the two parameters of nine and ten are very advanced, but there are some users who cannot enable these two parameters in the equipment transformation, that is, the inverter trips frequently after it is enabled, and everything is normal after it is deactivated. The reasons are: (1) The parameters of the original motor are too different from the motor parameters required by the inverter. (2) Insufficient understanding of the function of setting parameters, such as the energy-saving control function can only be used in the V/f control method, and cannot be used in the vector control method. (3) The vector control method is enabled, but the manual setting and automatic reading of the motor parameters are not carried out, or the reading method is improper.

More on that
Servo drives and servo motors – LS produces electricity Servo drives and servo motors – LS produces electricity

Driver: Under the premise of carrying out frequency conversion skills, the servo drive has carried out more advanced control skills and algorithm operations than general frequency conversion in the current ring, speed ring and azimuth ring inside the drive (the frequency converter does not have this ring), and it is much stronger than the traditional servo in terms of function.

The five stages of mastery of PLC technology The five stages of mastery of PLC technology

One. Logical stage   The so-called logical stage is to be able to complete the general logical planning in the relay system, since it is a relay system, so the knowledge of power drag is the foundation of this stage. I personally summarize that the root of learning the relay system lies in the word "grab", the relay system ...

How to troubleshoot the fault of the inverter - the power inverter How to troubleshoot the fault of the inverter - the power inverter

Because the application method is incorrect or the setting environment is unreasonable, the inverter will simply malfunction and cause problems, or the expected operation effect will not be satisfied. In order to prevent problems before they occur, it is important to carefully analyze the cause of the problem in advance. ...

Introduction to LS Master-K series PLC programming Introduction to LS Master-K series PLC programming

LS is an electrical equipment company affiliated to LG, kglwin3.62 programming software Chinese version is a professional plc programming software designed to help daily more efficient planning and development software, the software supports the programming and debugging of LG Master-K series and LG MASTER-K series, and provides ...

An internal component of LS's power circuit breaker An internal component of LS's power circuit breaker

1. Auxiliary contact: the contact mechanically linked with the main circuit of the circuit breaker and the closing mechanism is mainly used for the display of the circuit breaker and the closing status, and is connected to the control circuit of the circuit breaker through the opening and closing of the circuit breaker to control or interlock its related electrical appliances. For example, output to signal lights, relays, etc.

Inverter harmonic calculation method - LS power generation Inverter harmonic calculation method - LS power generation

1. Method 1 Method 1: Fourier transform to obtain the amplitude and phase of each harmonic of voltage and current, calculate the active power of each harmonic according to P=√3UIcosφ, and add the active power of all harmonics to obtain the harmonic power. Method 2: Measure the total active work ...

The difference between inverter and power saver - LS produces electricity The difference between inverter and power saver - LS produces electricity

First, the frequency conversion skill is only one of the many power-saving skills, including voltage regulation and current limiting, power factor compensation, phased power regulation, frequency conversion, chopping, filtering, energy feedback and other skills, even if the power saver using the principle of frequency conversion is concerned, the frequency converter is only power-saving.

Inverter maintenance principle analysis and inspection method Inverter maintenance principle analysis and inspection method

Principle analysis is the most fundamental way to eliminate the problem, when other methods are difficult to see the effect, you can start from the basic principle of the circuit, step by step to view, and finally find out the cause of the problem. To use this method, it is necessary to have a clear understanding of the principle of the circuit, and to grasp the various ...

The difference between low-speed and high-speed centrifuges – LS generates electricity The difference between low-speed and high-speed centrifuges – LS generates electricity

Through the rational planning of the structure of the low-speed centrifuge, the hygienic dead angle can be effectively eliminated. The transition of the structural parts is smooth, and the surface is polished. External structural components, fasteners, and rollers are made of stainless steel. The housing is a clamshell type, which allows for thorough cleaning of the interlayer space of the centrifuge housing without the need for a bowl ...

Grounding of the secondary side of the voltage transformer and the current transformer - power generation Grounding of the secondary side of the voltage transformer and the current transformer - power generation

1. The transformer is grounded twice It refers to the grounding of the S2 terminal of the current transformer or the ground of the n terminal of the voltage transformer. As long as the single point is grounded, because the transformer is blocked between the second and the first, before grounding, the secondary winding has no potential connection with the ground, after grounding, the transformer ...

The inverter selects the appropriate peripheral equipment - LS power generation The inverter selects the appropriate peripheral equipment - LS power generation

After we have selected a suitable Variable-frequency Drive (VFD), we also need to consider whether we need to equip other peripheral equipment according to the actual situation of the site. The peripheral equipment selected by VFD mainly includes circuit breakers, reactors, contactors, braking resistors, etc. ...

LS power generation installs the switching power supply step LS power generation installs the switching power supply step

The basic method of switching the power supply of the device requires us to carry out the corresponding installation and debugging according to the specific model and the device environment. And in the process of installation, we need to pay more attention to safety and stability to ensure the normal operation of the switching power supply. ...

Inverter control motor operation method - LS power generation Inverter control motor operation method - LS power generation

When the main circuit of the inverter is connected to the power line, in order to control the operation of the motor, it is also necessary to connect the relevant terminals to the peripheral control circuit, and set the parameters of the inverter's starting method to the external operation form. The inverter controls the motor to run, and there are two common methods, which are to turn on the ...

LS MASTER-K120S series PLC features and advantages LS MASTER-K120S series PLC features and advantages

(1) This series is divided into two types: economic type and standard type, which can meet the requirements of different customers: Economical: 10/14/20/30 points (10/14 points with 2 built-in analog potentiometers), up to 70 points. Standard type: 20/30/40/60 point DR/DRT (2-axis position ...

The cause of the failure of low-voltage electrical appliances - LS power generation The cause of the failure of low-voltage electrical appliances - LS power generation

In the control circuit of low-voltage electrical appliances, there are simple low-voltage components such as: buttons, safe, etc.; There are also slightly messy low-voltage electrical control components, such as circuit breakers, touch devices, time relays, thermal relays and other simple components, which makes it necessary to diagnose and analyze the cause of the problem. ...

Common practical knowledge in the inverter industry - power inverter Common practical knowledge in the inverter industry - power inverter

The inverter is the power frequency power supply (50Hz or 60Hz) converted into various frequencies of AC power supply to achieve the variable speed operation of the motor equipment, by changing the motor power frequency to achieve speed adjustment, is an ideal high-efficiency, high-speed regulation means. Frequency converters are used in industrial production and residential ...

The size of the contactor is selected by the type of contactor - LS produces electricity The size of the contactor is selected by the type of contactor - LS produces electricity

1. Select the corresponding category of contactor according to the control object, operation times and application category of the contactor. 2. Select according to the rated voltage of the line at the application location. 3. Select the rated current of the main contact of the contactor according to the load capacity. 4. About the voltage level of the lead coil ...

Meaning and classification of LS Electronic Motor Relay (EMPR). Meaning and classification of LS Electronic Motor Relay (EMPR).

The Electronic Motor Relay (EMPR) is a digital motor maintenance relay with an MCU that has a compact and compact form factor that can be combined directly with a contactor. Through the implementation of real-time data processing, high reliability and high precision can be completed, and it can pass through phase loss, reverse, unbalance, stalled rotor, connection...

The power of LS power inverter is selected The power of LS power inverter is selected

The relationship curve between the load rate β and the power η of the inverter can be seen: when β = 50%, η = 94%; When β = 100%, η = 96%. Although the β has doubled, the η change is only 2%, but it is also considerable for medium to high power (a few hundred kilowatts to several thousand kilowatts) electric motors. The system power is equal to the inverter power ...

Inverter failure and solution - power generation Inverter failure and solution - power generation

1. HW problem This problem may be a fault unique to LG-IG5 series inverters, and the main causes are as follows: (1) Damage to the cooling fan. Due to the use of environmental and other factors, the friction of the fan bearing is too large, causing the fan load to be too large and showing H ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top