Operation failure is manifested by the dragging or misoperation of the circuit breaker. Because the most basic and important function of the high-voltage circuit breaker is to operate correctly and remove the fault of the power grid quickly. If the circuit breaker drags or malfunctions, it will pose a serious threat to the power grid, first of all: (1)) expand the scale of the impact of the incident, which may expand the original only circuit fault to the entire busbar, or even the whole plant and the whole plant power outage; (2) If the time of fault removal is prolonged, it will affect the operation and stability of the system and aggravate the damage of the controlled equipment; (3) The formation of non-full phase operation. As a result, it often leads to abnormal operation and vibration of power grid maintenance, which simply expands into a system incident or a large-scale power outage. For example. In a power plant, the sleeve SW2-220 type oil-less circuit breaker tie rod was broken due to the lack of strength, and the B phase was not disconnected, forming a non-full-phase operation, so that the neutral point gap of the No. 4 main transformer produced spark discharge, and the arc involved the 220kV eastward bus, which made the bus differential maintenance action, and the No. 2 generator and two lines tripped, and because of the influence of negative sequence current, the main insulation of the generator rotor pole was almost all damaged.
The top causes of operation failure are:
(1) Deficiencies in operating organization;
(2) Mechanical defects of the circuit breaker body;
(3) Defects of operation (control) power supply.
The specific analysis is as follows.
1. Operational organizational shortcomings.
The operating structure includes electromagnetic structure, spring structure and hydraulic structure
The field calculations show that the defects of the operating organization are the primary cause of the operation failure, accounting for about 70%. For electromagnetic and spring tissues, the primary cause of mechanical problems in its tissues is that they are not sensitive. The jamming here may not only be due to the insensitive adjustment of the original assembly, but also due to poor maintenance, and another reason for the formation of tissue mechanical problems is improper lock adjustment, and the self-tripping (tripping) of the operation circuit interrupter is most likely due to such reasons. The loosening and displacement of each joint part is mostly due to the fact that the screws are not tightened, the pins are not well attached or the original anti-loosening structure has shortcomings. It is worth noting that loosening and displacement are far more common than damage to parts, so it can be seen that the meaning of preventing loosening is no less than preventing damage to parts.
For the hydraulic structure, its mechanical defects are mainly formed by poor sealing, so it is particularly important to ensure the reliable sealing of high oil pressure parts.
The electrical shortcomings of the organization are mainly caused by the shortcomings of auxiliary switches and micro switches. Most of the problems of auxiliary switches are not switched, which often causes the operating coil to burn out. In addition, there is also a problem because of the poor contact after switching. Micro switches mainly refer to the interlocking and maintenance switches on hydraulic organizations. The incident calculation data of SW6 breaker show that the micro switch defects account for about 50% of the electrical defects of its tissue. In addition to the shortcomings of auxiliary switches and micro switches, the largest share of the electrical shortcomings of the organization is the secondary circuit fault. Attention should also be paid to these "secondary angles of secondary angles". For example.
(1) In the 220kV substation of a certain power bureau, the SW6-220 circuit breaker C phase of the main transformer secretly jumped during operation, forming non-full-phase operation, resulting in severe consequences. The reason is that the outer sheath of the lead wire of the C-phase organization opening coil is worn, and the iron yoke window is discharged, forming the negative electrode grounding of the DC system. Because the insulation monitoring equipment of the substation failed, it could not be found in time, and the appearance team accidentally touched the positive pole during the operation, forming a DC two-point grounding, so that the circuit breaker C phase jumped secretly.
(2) The SW6-220 type oil-less circuit breaker of a substation is connected to the wrong secondary line during maintenance, so that the circuit breaker refuses to divide when there is a fault, and it expands into a power outage for the whole institute.
(3) The SW6-220I. type oil-less circuit breaker of a power plant, the F4 auxiliary switch of the CY3 organization, due to poor manufacturing quality and lack of contact elasticity, seems to be connected but not connected. When the line fails, the circuit breaker can not be opened correctly, so that the circuit breaker fails maintenance action, 220kV bus power failure, less power transmission 155,000 kW · h, 75,000 kW less power generation, · h。
2. The mechanical shortcomings of the circuit breaker body
The shortcomings of the mechanical failure of the circuit breaker body are all mechanical shortcomings. These include damage to the porcelain bottle, loose joints, damaged parts and jamming of foreign objects. For example; The SW7-220 type oil-less circuit breaker of the No. 3 generator and transformer of a power plant rejects C during grid-connected operation, forming non-full-phase operation, causing the 220kV bus connection and line circuit breaker to trip, and reducing power generation by 400,000 kW ··h. The reason for the incident is that the circuit breaker has been operated 3,600 times, the parts are severely worn, the straightening structure is deformed, and it is not overhauled and replaced in time, which finally caused the incident.
The SW7-220 type oil-less circuit breaker has a special "late action" problem, and the reason is: the oil in the arc extinguishing chamber and the triangle box of the circuit breaker is isolated. In order to prevent the oil leakage of the arc extinguishing chamber into the triangle box during operation, the dynamic seal of the conductive rod is generally adjusted very tightly, when the temperature rises in summer, the dynamic seal often holds the conductive rod, when the circuit breaker receives the opening order, the conductive rod movement to overcome the holding force, often dozens to hundreds of millimeters late to complete the opening action. For this "late moving" phenomenon, it is not easy to find out only by checking the circuit breaker after the incident, and can only be found by looking at the oscilloscope of the faulty recorder. In order to prevent such incidents, in the SW7-220 type less oil circuit breaker maintenance process has been the allowable scale of the conductive rod dialing force has been ruled, as long as the maintenance process is carefully implemented, there will be no "late action" incident in operation.
3. Disadvantages of operation (control) power supply
The shortcomings of the operating power supply of the circuit breaker are also one of the three major root causes of operation failure. Among the disadvantages of operating power supplies, the lack of operating voltage is the most common disadvantage. The reason is mostly because the power station chooses the AC power supply after silicon rectification as the operating power supply, and when the system fails, the power supply voltage drops significantly, or although there is a battery pack, the voltage drop between the operating power supply and the circuit breaker is too large, so that the actual operating voltage is lower than the lower limit of the rule. For example, a substation has a problem due to a distribution line, and the circuit breaker bursts when it coincides; The phase of the 44kV line of the other substation is wrong, and the circuit breaker bursts when the switch is closed and connected to the grid. These are all caused by the power supply of the silicon rectifier supplied by the substation, and when the line is faulty, the bus voltage drops. Therefore, in 1982, the former Ministry of Water Resources and Electric Power formulated the "Interim Rules on the Operation Energy of Substations", requiring that new substations should no longer use silicon rectifier as the operating power supply, and it is recommended to promote the use of batteries and energy storage operating organizations, and to transform and improve the operating power supply of existing substations, and strengthen management.
|
More on that
|
Delixi CDM molded case circuit breaker upgrade
The 6 series electronic molded case circuit breaker CDM6Ei was launched in 2017 with the addition of a 1600A shell frame; High through-off capacity, *** high Ics=65kA, to meet specific application occasions; Long-distance four-remote communication to complete intelligent connectivity; Support mobile APP communication and alarm non-tripping function; The maximum operating temperature of the product can be ...
|
|
Characteristics and parameters of industrial molded case circuit breaker - Delixi
1. Extra limit short-circuit breaking can be used for Icu
There are two types of breaking capacity targets for circuit breakers: additional limit short-circuit breaking capacity of 4U and additional operating short-circuit breaking capacity Ics. As a characteristic parameter, ICS is not only a brief consideration of the breaking ability of the circuit breaker, but also a breaking purpose.
|
|
Frequently asked questions about Delixi voltage regulators
Delixi voltage regulator will have a stable preset amplitude of a fixed output voltage, regardless of its input voltage or load conditions change.
There are two types of voltage regulators: linear and switched
The linear regulator is an active (BJT or MOSFET) operated by a high-gain differential amplifier ...
|
|
Introduction of four-quadrant regulator - Delixi
A four-quadrant power supply is a power supply capable of absorbing and supplying positive and negative currents and voltages. While a simple voltage converter is capable of generating a fixed output voltage from the input voltage, this feature is not sufficient in some applications. An example is the control of voltage nodes connected to capacitors that ...
|
|
Voltage regulator failure and solution - Delixi
1. There is no output, no voltage indication or no start when the machine is turned on. Overvoltage or undervoltage maintenance
1. Adjust the internal output voltage adjustable potentiometer
2. The wrong phase and the lack of phase are maintained, and the two phases are arbitrarily replaced by three phases
3. The main control circuit board is broken 3. Replace
4. The output AC has been ...
|
|
Delixi reduces the number of inverter maintenance times
Inverter is a very widely used equipment in the modern factory, this is a new type of equipment, the price is very noble, and the price of inverter repair is also very expensive, so in the process of using inverter, pay attention to the use of inverter, on the one hand, inverter, delay inverter ...
|
|
Inverter maintenance technology - Delixi inverter
(1) Fault characteristics
a) *** tripping may occur during operation, but if it is restarted after resetting, it often trips as soon as the speed rises.
b) has a large inrush current, but most drives can already be tripped, maintenance without damage. Due to the ...
|
|
Delixi three-phase motor electrical control circuit principle
What is the principle of the electrical control circuit of the three-phase motor? First of all, let's take a look at what is the principle of electrical control of work machinery. The schematic diagram of the electrical control circuit of the working machinery is actually connected with graphic symbols, text symbols and lines to show the connection relationship and circuit of each electrical component.
|
|
Reduce the maintenance cost of the inverter - Delixi
Frequency converter is a widely used equipment in modern factories. This is a very expensive new type of equipment, and the maintenance price of the inverter is also very expensive, so in the process of using the inverter, we should pay attention to the use of the inverter.
Thing...
|
|
Delixi circuit breaker common model features
CDB1 miniature circuit breaker is a current-limiting high-breaking miniature circuit breaker with overload and short-circuit maintenance, which is suitable for communication 50Hz, additional voltage 400V and below, additional current 63A and below circuits, as line overload and short circuit maintenance, can also be used under normal circumstances.
|
|
Delixi EM60 series inverter to factory settings
First, the process of inverter rehabilitation factory value
1. Study the manual and find the corresponding function number, or key combination.
2. Confirm that the parameters can be corrected (sometimes the inverter will set the parameter to write the protection function in order to prevent the parameters from being changed randomly, and the password must be guaranteed to enter the correction) ...
|
|
Delixi integrated voltage regulator knowledge
The role of a voltage regulator is to convert an unstable DC voltage into a stable DC voltage. However, the integrated voltage regulator has a wider and wider range of applications due to its advantages such as small size, good voltage regulation performance and perfect maintenance function. There are two types of integrated voltage regulators: linear power supply regulators and switching power supply regulators.
|
|
Delixi bearing rust causes
1. The instantaneous high temperature in the grinding process will make the surface of the workpiece reach a molten state, and the steel surface will react with the oxygen in the air chemically, which will form a very thin (20-30nm) iron oxide film.
|
|
Thermal calculation of linear regulator - Delixi
Thermal accounting requires information such as power loss, thermal resistance of the package, and ambient temperature. The power loss is the same as the power accounting, which is purely the value of the output input voltage difference multiplied by the input current. The thermal resistance should have a technical standard documented, and if it is not, it is necessary to ask the manufacturer. Basically...
|
|
Delixi CDHR16 series strip fuse disconnector
CDHR16 series strip fuse disconnector with an additional frequency of 50Hz, an additional operating voltage of 500/690V, and an additional operating current of 630A, which is mainly suitable for power distribution circuits and motor circuits with high short-circuit current, is used as a power switch, isolation switch, and as AC circuit short-circuit protection.
|
|
The advantages of the practical application of the inverter - Delixi
With the continuous progress of industrial automation, inverters have also been widely used, energy conservation and environmental protection as the center of China's industrial economic development, in the direction of the sustainable development of China's industry, but also in the effective promotion of the sustainable development of China's inverter profession, so that I ...
|
|
The reason why the Delixi switch socket is hot and hot
1. The quality of the socket is low
First of all, we should check whether the socket is a miscellaneous defective product, the copper clamping force in the defective socket is not enough, resulting in a poor connection between the socket and the plug, and the socket and plug will heat up after a long time of electrical use. Therefore, you must not buy cheap miscellaneous electric ...
|
|
Delixi inverter speed parameters
There are two speeds of Delixi inverter, one is the target speed, and the other is the speed of practice.
The target speed requires the value of the detailed parameters to be adjusted, such as the *** high frequency/*** high frequency in the inverter parameters; Regarding the practical output speed, the frequency needs to be checked in the inverter parameters ...
|
|
Delixi air switch is connected to the reverse hazard
If the zero line of Delixi's air switch is reversed to the front, there is not much obstacle to the 2P circuit breaker and 2P leakage circuit breaker. The only effect is that it looks irregular, and you need to find the zero line from scratch when repairing, which brings a little inconvenience.
...
|
|
Precautions for the use of Delixi leakage protector
1. If the two branch lines are connected, the current in the zero line flows to each other, which destroys the working current balance in the zero sequence current transformer and causes the leakage protector to malfunction. If you want to use the neutral line of the power branch line as the neutral line of the lighting branch line nearby, it will cause the leakage of the power branch line.
|
|