1. Extra limit short-circuit breaking can be used for Icu

There are two types of breaking capacity targets for circuit breakers: additional limit short-circuit breaking capacity of 4U and additional operating short-circuit breaking capacity Ics. As a characteristic parameter, ICS does not only consider the breaking ability of the circuit breaker, but also serves as a breaking target, that is, after breaking several short circuit faults, it can also ensure its normal operation. For molded case circuit breakers, there should be a satisfactory ICU that can break the short-circuit current and trip the switch. According to the rules, the ICS of molded case circuit breakers only needs to be greater than 25% ICU to be qualified. At present, most of the ICS of circuit breakers on the market are between (50%-75%) ICUs, so the power distribution system with low power supply requirements only needs to consider the ICU.

                              Characteristics and parameters of industrial molded case circuit breaker - Delixi

2. Ability to limit current breaking

The ability to limit the current breaking refers to the ability to constrain the fault current when the circuit breaker is short-circuited and tripped. When the circuit breaker generates a short circuit, the contact is quickly opened to generate arc, which is equivalent to inserting an arc resistor in the line that is quickly added, and then restricting the addition of fault current. The fewer the circuit breaker disconnection moments, the closer the ICS is to the Icu, the better the current limiting effect, and the adverse effects of the electromagnetic effect, electric effect and thermal effect caused by the short-circuit current on the circuit breaker and electrical equipment can be greatly reduced, and the service life of the circuit breaker can be prolonged.

3. Short-circuit maintenance

Short-circuit maintenance is the instantaneous tripping of a short circuit. It is necessary to pay attention to adjusting the setting value of maintenance in time after the load change, so as to avoid the setting value being too small and frequent tripping affecting the power supply quality, or the setting value being too much will cause the line and equipment to not get useful maintenance.

4. Overload delayed maintenance

Overload delayed maintenance means that the load current exceeds the limit of the equipment and there is a risk of burning the equipment, and the maintenance device can block the power supply within a certain time. Overload has a process of heat accumulation, and maintenance actions do not need to be too agile. Regarding short-term overcurrent, maintenance should not be operated.

5. Barrier function

The blocking function is to require that the leakage current after the circuit breaker is disconnected will not cause damage to people and equipment. After repeated short-circuit trips, the switch function decreases, and the leakage current increases. For the human body, less than 30mA is a safe leakage current, but in a harsh environment, the leakage current exceeding 300mA lasts for more than 2 hours, which may cause insulation damage and cause a phase-to-ground short circuit and cause a fire.

6. Leakage maintenance

There are two types of leakage maintainers: thermomagnetic and electronic, and the electronic leakage has the advantages of small size, high precision and high sensitivity, but its anti-interference ability is poor. At present, the electronic leakage maintainer occupies the main current, and when the leakage current reaches the setting value, the execution circuit receives the induced voltage signal on the secondary side of the zero-sequence current transformer, and drives the conversion contact to output the leakage maintenance signal, so that the tripper acts to block the power supply.

Generally, the setting leakage trip current of the terminal switch is 30mA, and the setting value of the upper branch switch is 300mA. The arc short circuit with a high risk of fire is difficult to be effectively blocked by short-circuit maintenance, and the leakage current can be firmly disconnected from the grounding fault to avoid personal electric shock and phase-to-ground short circuit fault.

More on that
Delixi circuit breaker mechanism spring design Delixi circuit breaker mechanism spring design

The spring is a widely used component in the circuit breaker mechanism, and the critical spring has a great impact on the function of the circuit breaker. From the perspective of energy, combined with the installation space of the tension spring, the author uses the existing accounting formula of the tension spring to solve the unknown quantity from the known quantity to obtain the required tension spring parameters.

Delixi inverter built-in bypass soft starter CDRA-K3 Delixi inverter built-in bypass soft starter CDRA-K3

Delixi built-in bypass soft starter CDRA-K3 series is a set of soft start, soft parking and multi-functional protection in one of the motor control equipment. Realize a smooth starter motor without impact during the entire starting process. CDRA-K3 series has built-in bypass contactor and control power supply.

Delixi linear and switching regulators introduced Delixi linear and switching regulators introduced

01. What is a linear voltage regulator? A linear regulator uses a transistor or FET operating in its linear region to subtract the excess voltage from the input voltage of the application to produce a conditioned output voltage. The so-called voltage drop voltage means that the voltage regulator maintains its output voltage at its ...

General parameter setting skills of inverter - Delixi General parameter setting skills of inverter - Delixi

The setting menu of the inverter is divided into a first-level menu, a second-level menu, etc., and the menu is followed by parameters. If the inverter starts in standby (ready to run) condition, set the FUn-PSS-SP2 parameter to 15Hz, and then return to the standby state operation. In the practice setting ...

The reason for the instability of the voltage regulator output - Delixi The reason for the instability of the voltage regulator output - Delixi

It shows that the voltage regulator base is not voltage corrected, and the voltage regulator in this situation is like a transformer, the higher the input voltage, the higher the output voltage, the input decreases and the output voltage also decreases. This...

Parameters of Delixi inverter speed controller Parameters of Delixi inverter speed controller

(1) Gain Parameter: The share gain of the speed manipulator. If the gain is too large, it may cause speed fluctuations. (2) Integration time parameter: the integration time of the speed manipulator, that is, the change rate of the output signal of the manipulator under the deviation step signal. The shorter the integration moment ...

Delixi inverter EM60 series model introduction Delixi inverter EM60 series model introduction

S1 (Single-phase 110V, 50/60HZ) CDI-EM60G0R75S1 0.75KW CDI-EM60G1R5S1 1.5KW S2 (Single Phase 220V, 50/60HZ) CDI-EM60G0R4S2 (without built-in brake unit) 0.4KW CDI-EM60G0R4S2B (Built-in ...

The component of the main line of the inverter - Delixi The component of the main line of the inverter - Delixi

An inverter is usually a device that replaces a constant voltage and frequency with a constant voltage or frequency for a variable voltage. However, in the application, the inverter will inevitably present shortcomings, and when analyzing the shortcomings of the problem, in order to deal with the shortcomings well and quickly, ...

Delixi bearing rust causes Delixi bearing rust causes

1. The instantaneous high temperature in the grinding process will make the surface of the workpiece reach a molten state, and the steel surface will react with the oxygen in the air chemically, which will form a very thin (20-30nm) iron oxide film.

Delixi solid state relay relative to AC contactor characteristics Delixi solid state relay relative to AC contactor characteristics

Delixi solid state relay and Delixi communication contactor are more used products, so what are the advantages of solid state relay relative to communication contactor, how should we choose when we can choose? 1. First of all, the solid ...

The change of frequency conversion control mode - Delixi inverter The change of frequency conversion control mode - Delixi inverter

In the process of practical speed regulation, an ordinary frequency-adjustable communication power supply can not meet the requirements of speed regulation and control of asynchronous motors, and must also take into account the effective use of the motor magnetic field, the suppression of the starting current and the acquisition of the desired torque characteristics, such as low-frequency torque characteristics.

Delixi CDRA soft starter features Delixi CDRA soft starter features

Delixi CDRA soft engine is a set of soft start, soft stop, light load, energy saving and multi-functional protection in one of the motor control equipment. This is a shock-free and smooth motor during the entire start-up process. According to the type, it can be divided into equipment type and comprehensive. ...

Delixi inverter application case Delixi inverter application case

The traditional textile printing and dyeing industry is a labor-intensive industry, and the degree of automation is not high. Most of the transmissions used are not speed regulation, and most of the occasions that need speed regulation are DC motors, such as warping machines, sizing machines and many printing and dyeing equipment.

The difference between Delixi air switch and leakage protection switch The difference between Delixi air switch and leakage protection switch

1. The role is different The air switch is a kind of circuit breaker that protects the "object", which can protect the safety of the entire household wiring and electrical appliances and other items to prevent the wire from being burned due to overheating. The leakage protection switch is a kind of circuit breaker that protects "people", which can be cut in time when leakage.

The reason why the Delixi switch socket is hot and hot The reason why the Delixi switch socket is hot and hot

1. The quality of the socket is low First of all, we should check whether the socket is a miscellaneous defective product, the copper clamping force in the defective socket is not enough, resulting in a poor connection between the socket and the plug, and the socket and plug will heat up after a long time of electrical use. Therefore, you must not buy cheap miscellaneous electric ...

Product features of Delixi equalizer Product features of Delixi equalizer

1. The divider is the sixth generation of intelligent machine using microcomputer chips, and the intelligent program is very high. 2. Single-phase three-phase connection, the divider on the market is scored as A, B, and C three-phase wiring for three-phase electricity, which is not only inconvenient for installation, but also prone to phase sequence errors. 3. Can ...

Delixi control transformer use precautions Delixi control transformer use precautions

Delixi control transformer use of the most types is BK, JBK, BKC and other types, these transformers use some precautions as follows: 1. Before purchasing, please estimate the total capacity of the electrical appliances you use.

Delixi inverter common problems Delixi inverter common problems

1. The pressure of Delixi inverter system is unstable and simple vibration? Answer: The pressure of the system is unstable, which may be due to the following reasons: A. There is a problem with the orientation of the pressure of the pressure sensor collection system, the pressure collection point is too close to the water pump outlet, and the pipeline pressure is affected by the water outlet ...

How to wire and use the number of switches when the inverter starts and stops - Delixi How to wire and use the number of switches when the inverter starts and stops - Delixi

The control of the inverter is nothing more than the fundamental logic of starting, aborting, forward rotation, rotation, and speed regulation, which fundamentally requires that the level condition is effective, rather than the rising edge is effective, so the use of button switches to control the inverter is generally required to use the self-protection of the button...

Delixi participated in the 4th China Electrical Appliance Culture Festival Delixi participated in the 4th China Electrical Appliance Culture Festival

On January 27, the "4th China Electrical Appliance Culture Festival and World Electrical Products Expo" was grandly opened in Liushi, Wenzhou, the capital of China's electrical appliances. More than 500 companies from home and abroad showed their faces on more than 1,400 booths. The largest Delixi exhibition hall with a booth area of more than 1,800 square meters ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top