Voltage regulator failure and solution - Delixi

Create Date: 2024-8-30 12:03:23|Source: Delixi

1. There is no output, no voltage indication or no start when the machine is turned on. Overvoltage or undervoltage maintenance

1. Adjust the internal output voltage adjustable potentiometer

2. The wrong phase and the lack of phase are maintained, and the two phases are arbitrarily replaced by three phases

3. The main control circuit board is broken 3. Replace

4. The output AC is broken 4. Replaced

                                 Voltage regulator failure and solution - Delixi

Second, the output voltage is abnormal

1. It is the same modulation regulator 1, and the sub-modulation regulator is replaced

2. Exceed the voltage stabilization scale of the regulator itself 2. Replace the wide-scale regulator

3. The travel limit switch is broken 3. Replace

4. The phase circuit board is broken 4. Replace

5. Servo motor incineration 5. Replacement

3. Unstable voltage

1. Exceed the voltage stabilization scale of the regulator itself 1. Replace the wide-scale voltage regulator

2. The travel limit switch is broken 2. Replace

3. The circuit board is broken 3. Replaced

4. Servo motor incineration 4. Replacement

Fourth, tripping without reason at work

1. The main gate capacity is selected to be smaller, and the appropriate capacity air switch is replaced

2. The air switch is broken 2. Replaced

3. The surge voltage is too high instantaneously 3. Replace the contactless high-precision voltage regulator

Fifth, the buzzing sound inside the voltage regulator is very loud

1. Overload with load 1. Reduce the equipment after it

2. There is debris inside 2. Remove the debris

6. The squeak inside the regulator is loud

1. The voltage is unstable 1. Normal

2. There is ash and dirt on the surface of the carbon brush 2, and the dust and dirt are removed

7. The electric regulator cannot actively operate after a power failure

1. The full active toggle switch is not open 1

2. Circuit board failure 2. Replacement

8. There is no boost or step-down according to the panel (non-power regulators have no such function)

1. Servo motor incineration 1. Replacement

2. The travel limit switch is broken 2. Replace

3. Circuit board incineration 3. Replacement

4. Manual, active knob is not open to manual 4, open to manual

More on that
Thermal calculation of Delixi linear regulator Thermal calculation of Delixi linear regulator

Thermal accounting requires information such as power loss, thermal resistance of the package, and ambient temperature. The power loss is calculated in the same way as the efficiency accounting, which is simply the value of the difference between the output input voltage and the input current. Thermal resistance should have a technical standard documented, and if it is not available, it is necessary to consult the manufacturer. Basically...

The reason why the switch socket is hot - Delixi The reason why the switch socket is hot - Delixi

1. The socket quality is low quality First of all, we should check whether the socket is a miscellaneous and inferior product, the copper clamping force in the defective socket is not good, resulting in poor contact between the socket and the plug, and the socket and plug will heat up after a long time of electrical use. So be sure not to buy cheap miscellaneous ...

Delixi inverter in the die-casting machine frequency conversion energy-saving transformation Delixi inverter in the die-casting machine frequency conversion energy-saving transformation

First, the principle of energy saving The die-casting machine is a typical periodic variable load equipment, and a complete production cycle includes the stages of mold clamping, injection, cooling, and mold opening and ejection. Usually the power of hydraulic equipment is supplied by a quantitative oil pump, and the motor that drives the oil pump to work has always been rated for its ...

Delixi inverter E180 series technical features Delixi inverter E180 series technical features

1. Superior performance The new vector control algorithm is adopted, and the starting cabinet is large, the torque response is fast, and the control accuracy is high, which further improves the operation efficiency of the motor. 2. Powerful function and low cost of use Built-in large number of ...

Delixi molded case circuit breaker Icu=ICS understands Delixi molded case circuit breaker Icu=ICS understands

Delixi 3P air switch, rated current 630A, rated voltage 380V. The Icu=Ics=70kA of this circuit breaker. When the short-circuit current reaches 70kA, can the circuit breaker still be used? If it works, the ICU is already at its limit, which is a contradiction. If it can't be used, ICS is 70KA, which means ...

The 2016 Delixi Electric Construction Industry Summit was successfully held The 2016 Delixi Electric Construction Industry Summit was successfully held

2016 is the first year of the "13th Five-Year Plan", with the adjustment of China's economic structure, the construction profession is also changing. On September 8th, with the theme of "riding the wind and waves, building the future together", the Delixi Electric Construction Career Summit opened in Qingdao, the "International Sailing Capital". The summit ...

Delixi inverter load type Delixi inverter load type

The correct choice of Delixi inverter is very critical to the normal operation of the control system. When selecting a frequency converter, it is necessary to fully understand the load characteristics driven by the frequency converter. In practice, people often divide production machinery into three types: constant torque load, constant power load and fan, water pump ...

Precautions for leakage vacuum circuit breaker circuit - Delixi Precautions for leakage vacuum circuit breaker circuit - Delixi

Leakage vacuum circuit breaker connection: When normal operation, regardless of whether the three-phase load is balanced or not, the sum of the three-phase current phasor through the main circuit of the zero-sequence current transformer is equal to zero, so there is no induced electromotive force in the secondary winding, and the leakage maintainer operates in a closed state. In the event of leakage or ...

Delixi circuit breaker insulation accident Delixi circuit breaker insulation accident

The circuit breaker insulation incident can be divided into the internal insulation terminal and the external insulation incident. The hazards caused by internal insulation incidents are generally greater than those of external insulation. (1) Internal insulation incidents The internal insulation end is mainly a bushing and a current transformer ...

The material of the transformer - Delixi The material of the transformer - Delixi

In view of the regulation and control effect of the transformer in the power system, technicians need to choose the appropriate transformer finishing device operation, so as to play a normal effect. Winding data is the primary problem that transformer devices need to pay attention to, and the effects of devices of different materials are different. Concerning...

The circuit breaker is set in accordance with the principle - Delixi circuit breaker The circuit breaker is set in accordance with the principle - Delixi circuit breaker

1. When the main circuit is equipped with a total leakage maintainer, the main barrier switch, the branch barrier switch, the main circuit breaker, the branch circuit breaker or the main fuse, and the shunt fuse should also be installed. When the total leakage maintainer is a leakage circuit breaker with short-circuit, overload, and leakage maintenance functions, it can not be ...

A brief introduction to the characteristics of Delixi A brief introduction to the characteristics of Delixi

1. Nominal value A suitable approximation of a switchgear or component and equipment to mark or identify it. 2. Limiting value The maximum or minimum promise of a quantity in the specification and specification. 3、 ...

The main factor affecting the poor heat of the instrument - Delixi The main factor affecting the poor heat of the instrument - Delixi

The operation of differential thermal analysis is simple, but in practical work, it is often found that the same sample is measured on different instruments, or different samples are measured on the same instrument, and the results of the differential thermal curve of industrial electrical appliances are different. The high temperature, shape, area, and size of the peaks will all change. ...

Causes and solutions for circuit breaker closing failure - Delixi circuit breaker Causes and solutions for circuit breaker closing failure - Delixi circuit breaker

1. Failure analysis. 1) Closing fuse, control fuse blowing or poor contact. 2) Poor contact of DC contactor or poor contact of control switch contact and auxiliary contact of circuit breaker. 3) The DC voltage is too low. 4) Closing and locking action. ...

Delixi universal circuit breaker CDW9 series maintenance operation Delixi universal circuit breaker CDW9 series maintenance operation

Delixi intelligent all-round circuit breaker CDW9 series, should be checked regularly every year, first open and close and long-distance equipment, successively use a variety of additives, test operation program column, control unit test using a small test suite; Every two years or when the control unit repair target reaches 100, it should be ...

Analysis of the quality of Delixi surge protector Analysis of the quality of Delixi surge protector

Look at the quality of the surge protector, to see whether it can complete his basic specification, relative to the surge protector of the primary specification is whether the surge operating voltage can be constrained below the required value, the surge protector must discharge the lightning current when the mission is completed, this specification must be completely completed.

Delixi inverter built-in bypass soft starter CDRA-K3 Delixi inverter built-in bypass soft starter CDRA-K3

Delixi built-in bypass soft starter CDRA-K3 series is a set of soft start, soft parking and multi-functional protection in one of the motor control equipment. Realize a smooth starter motor without impact during the entire starting process. CDRA-K3 series has built-in bypass contactor and control power supply.

Delixi surge protector SPD technology is used Delixi surge protector SPD technology is used

Since its creation in the 1970s, which began as a patent for Zap Trap under the pleasant name, surge maintenance equipment (SPD) has become essential in many lightning protection systems (LPS). Surge maintainers are now used in electrical installations to avoid transient overpower ...

Drawing precautions for wiring diagram of electrical components - Delixi Drawing precautions for wiring diagram of electrical components - Delixi

(1) The drawing of the wiring diagram and the wiring table shall be subject to the request of GB6988.6-1993 in the "Production of Control System Function Table Diagram". (2) All electrical components and wires should be marked with letter symbols and wiring numbers that differ from those in the schematic diagram of the electrical circuit. Schematic diagram catalog number, final ...

Delixi inverter analog output fault analysis Delixi inverter analog output fault analysis

The analog output of Delixi inverter is abnormal, and the operating frequency of the inverter does not match the output of the controller? Solution(s): First, you should determine what hardware is going wrong. Make the controller enter the manual debugging situation, respectively...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top