Working environment
In the actual application of inverters, most people install inverters directly in industrial sites in order to reduce costs. The job site generally has the problems of large dust, high temperature and high humidity, and in some occupations, there are also metal dust, corrosive gases and so on. It is necessary to take appropriate measures according to the situation on the spot.
1) The inverter should be installed inside the control cabinet.
2) The inverter is installed in the middle of the control cabinet; The inverter should be installed vertically, and the large components that may obstruct the exhaust and air intake should be avoided directly above and below.
3) The upper and lower edges of the inverter should be separated from the top and bottom of the control cabinet, and the small spacing of the partition and the large components of the necessary device should be greater than 300mm.
4) If special users need to remove the keyboard in use, the keyboard hole of the inverter panel must be tightly sealed with tape or replaced with a fake panel to avoid a lot of dust from entering the inverter.
5) Most of the internal printed boards and metal structural parts of the inverter have not been specially treated with moisture and mildew, and the metal structural parts are prone to rust if they are in a harsh working environment for a long time. Under the condition of high temperature operation, the conductive copper bar will be more corroded, and the corrosion will cause damage to the fine copper wires on the microcomputer control board and the drive power board. Therefore, for applications with humidity and corrosive gases, it is necessary to have basic requirements for the internal planning of the frequency converter used.
6) When the inverter is used in dusty places, especially in places with multi-metal dust and flocculents, the overall control cabinet is required to be sealed as a whole, and the air inlet and outlet are specially planned for ventilation; There should be a protective net and a protective top cover air outlet on the top of the control cabinet; The bottom of the control cabinet should have a base plate, air inlet, wire inlet holes, and a dust filter.
Electromagnetic interference
In the modern industrial control system, the microcomputer or PLC control skills are mostly selected, and in the process of system planning or transformation, we must pay attention to the disturbance of the inverter to the microcomputer control panel. Due to the fact that the microcomputer control board planned by some inverters does not meet EMC international standards, conduction and radiation disturbance will occur after the use of inverters, which often leads to abnormal operation of the control system, and the following methods are available for your reference.
1) Install an EMI filter at the input end of the inverter, which can effectively press the conduction disturbance of the inverter to the power grid, and install input communication and DC reactor, which can improve the power factor, reduce harmonic pollution, and have a good comprehensive effect. In some cases where the distance between the motor and the inverter is more than 100m, it is necessary to add a communication output reactor on the inverter side to deal with the leakage current protection caused by the distribution parameters of the output wire to the ground and reduce the external radiation disturbance.
One way is to thread the steel pipe or shield the cable, and connect the steel pipe shell or cable shield with the earth. In the case of not increasing the communication output reactor, the selection of steel pipe threading or shielded cable will increase the distributed capacitance of the output to the ground, and it is easy to overcurrent.
2) Electrically shielding and blocking the analog sensor detection input and imitation control signal. In the planning process of the control system composed of frequency converters, it is advocated that imitation control should not be used as much as possible, especially when the control interval is greater than 1m and the device is across the control cabinet. Because the inverter generally has multi-stage speed setting, switching frequency input and output, it can meet the requirements. If you have to use analog control, it is recommended that you must use a shielded cable and complete a remote grounding on the sensor side or the inverter side. If the disturbance is still severe, the DC/DC barrier method needs to be completed. It is possible to choose a standard DC/DC module, or choose a v/f conversion optical block, and then choose the frequency setting input.
3) Install EMI filters, common-mode inductors, high-frequency magnetic rings, etc. to the input power supply of the microcomputer control board, which can effectively conduct and disturb the microcomputer control board. In addition, in the case of serious radiation disturbance, such as GSM and PHS base stations around, a metal mesh shield can be added to the microcomputer control board for shielding.
4) Good grounding. It is necessary for the grounding wire of the strong current control system such as the motor to be firmly grounded through the grounding busbar, and the shielding ground of the microcomputer control board should be grounded separately. For some occasions where the disturbance is severe, it is advisable to connect the sensor, I/0 interface shield and the control ground of the control board.
|
More on that
|
Inverter composition and various functions - Reynolds
Rectifier circuit: rectify 50HZ communication power into direct current.
Frequency conversion circuit: The rectified direct current is inverted into a variable frequency communication current.
Control part: control the frequency of communication electricity output by the inverter circuit.
Maintenance circuit: maintenance and blockage of overcurrent and phase loss ...
|
|
Characteristics of isolation transformer at the input end of AC power supply - Reynolds
a。 When the third harmonic and disturbance signals are severe, a barrier transformer can be used to eliminate the third harmonic and disturbance signals.
b。 The use of barrier transformers can generate new neutrals and avoid the abnormal operation of equipment due to defective neutrals in the grid.
...
|
|
Reynolds inverter FAQ - parameter class
1. What are the factory parameters of inverter rehabilitation?
N600 = 100 (often press the WR button for 3-5 seconds), it is necessary to be in the shutdown state to be effective.
2. In the parameters of the N308 motor of the inverter, [motor leakage inductance reactance] is the specified sub...
|
|
Introducing the Reynolds JJR5000 series of soft starters
Reynolds JJR5000 series all-digital intelligent AC motor soft starter adopts power electronics technology, microprocessor technology and modern control theory technology, which is a new type of starting equipment at the current level. This product can limit the starting current of the asynchronous motor when it starts, and is widely used in fans, ...
|
|
Reynolds permanent magnet synchronous motor solutions
The permanent magnet synchronous motor has high-efficiency motor drive performance, which can complete high-speed, high-precision, high-stability, fast-responding, high-efficiency and energy-saving motion control. Reynolds drives provide a vector control technology solution for permanent magnet synchronous motors.
...
|
|
Key points for the selection of AC contactors - Reynolds
1. Select varieties according to the above series according to the purpose and requirements of use
Note that the main circuit load type is strictly differentiated, whether it is DC or communication.
The communication contactor is different from the DC contactor, and is only suitable for DC-1 to DC-5 loads when used for DC loads.
|
|
Reynolds soft starter problem solving
1. The soft starter does not start and the fault-free code appears, perhaps because the control power supply is not connected, the solution is to check the power supply of the control power supply to see if the circuit connection is correct.
2. The motor starts when the motor announces a hum/no start signal, perhaps because of the thyristor/module ...
|
|
Introduction to the appearance of Reynolds inverter
Bypass cabinet: The cabinet is equipped with high-voltage inlet and outlet isolation switches QS1 and QS2, as shown in Figure 2. Among them, QS1 is a single-pole single-throw variable frequency incoming knife switch, and QS2 is a single-pole double-throw power frequency and variable frequency outgoing knife switch. The bypass cabinet is a high-voltage environment, please observe the live display and electromagnetic lock status to ensure that the ...
|
|
The distance between the Reynolds frequency converter and the motor determines the cable and wiring method
1. The interval between the inverter and the motor should be as short as possible. This reduces the cable's capacitance to ground and reduces the source of disturbance.
2. The control cable is shielded cable, the power cable is shielded cable or from the inverter to the motor.
|
|
Frequency converter overcurrent problem treatment - Reynolds
General treatment methods for inverter overcurrent problems:
The output side of the inverter is a PWM voltage waveform, and after passing through the motor winding, the output current is approximately a sine wave, and lags behind the voltage by a phase viewpoint, which is determined by the power factor of the motor. The output current of the inverter passes through ...
|
|
Inverter frequency regulation fault solution - Reynolds
Most of the applications of frequency converters (hereinafter referred to as -VFDs) are primarily due to the fact that VFDs can change the output frequency and thus change the speed of the motor. If the frequency of the VFD cannot be adjusted and no damage is found on the hardware, it can be considered that the maximum output torque of the VFD is less than the load progress torque ...
|
|
Precautions for low-temperature operation of VFD
1. VFD should be operated in an environment above minus 10°C as much as possible, and it is best to operate indoors.
2. When the VFD is started and stopped, try to start and stop with the VFD itself, do not close the power supply, and keep your VFD in a power-on state.
3. Give VFD l ...
|
|
How to determine the frequency of start-up – Reynolds
Generally, most motors start to speed up from 0Hz, but in some special cases, it is necessary to start directly from a certain frequency. At this time, the frequency output of the VFD at the moment of activation is the activation frequency. In general, you need to set the activation frequency in the following situations.
...
|
|
Protection feature of overcurrent trip - Renol
1. Maintenance objectives of overcurrent
In the frequency conversion speed regulation system, there are two devices: the frequency converter and the motor. The degree of tolerance to overcurrent is not the same. The planners of the production machinery decide on the capacity of the motor based on the principle of heat. That is, as long as the electricity ...
|
|
Precautions for Wiring Reynolds Inverters
1. The inverter itself has a strong electromagnetic disturbance, which will disturb the work of some equipment, so we can add a cable sleeve to the output cable of the inverter.
2. The control line in the inverter or control cabinet is at least 100mm away from the power cable, etc.
...
|
|
Problems between the inverter and the motor – Reynolds
1. The power and temperature rise of the motor
Regardless of the method of the inverter, different degrees of harmonic voltage and current occur during operation, so that the motor runs under non-sinusoidal voltage and current. Rejection of material introduction, taking the sine wave PWM type inverter that is now widely used as an example, ...
|
|
Reynolds assisted Sinopec Weirong shale gas project
With the rapid development of China's national economy, the supply and demand situation of oil and gas resources is becoming increasingly severe, and the import of oil and gas is increasing year by year, so it is urgent to expand the field of domestic oil and gas exploration and development. Strengthening the exploration and development of shale gas resources can make up for the lack of conventional oil and gas resources and promote the sustainability of the oil and gas industry.
|
|
The structure of the low-voltage circuit breaker - Reynolds
Low-voltage air circuit breaker, also known as active air switch or air switch, belongs to the switch electrical appliance, is used when the circuit is overloaded, short circuit and undervoltage can actively break the circuit of the electrical appliances, can also be used as infrequent start of the motor or opening and closing circuit, low-voltage air circuit breaker has an all-round circuit breaker ...
|
|
The role of frequency conversion technology in work equipment - Reynolds
Because inverters are widely used, there are many differences in the corresponding types and specifications. We are broadly divided into two categories: voltage and current. The current type of inverter products is characterized by the use of a large inductor as the energy storage link in the middle DC link, and the reactive power will be buffered by this inductor. ...
|
|
The working principle of the motor soft starter – Reynolds
Motor soft starter is the primary selection of power electronics skills and microprocessing skills and modern control theory and design and production of advanced level of new engine equipment, motor soft starter mainly has anti-interference function, high reliability, multiple protection functions and other characteristics, according to these characteristics of electric ...
|
|