1. The circuit breaker cannot be closed
Causes:
1. The undervoltage coil does not work (the voltage is normal). Solution: Replace the undervoltage coil.
2. Press the closing button, and the closing coil will not work when it is powered up. Solution: Replace the undervoltage coil.
3. Poor contact of the closing button. Workaround: Replace the closing button.
4. The melt core of the control loop is burned out. Solution: Replace the fuse core after confirming that the control loop is normal and there is no short circuit.
5. The circuit breaker is not stored for energy. Solution: Check that the motor control supply voltage must be ≥ 85%.
6. The closing solenoid controls the power supply voltage less than 85%. Solution: The power supply voltage of the closing solenoid must be ≥ 85%.
7. The closing solenoid has been damaged. Solution: Replace the closing solenoid.
8. Poor contact of the secondary circuit of the drawer circuit breaker. Solution: Shake out the drawer circuit breaker and shake it back to the "on" position. Check whether the secondary circuit is connected reliably.
9. The universal transfer switch is in the stop position. Solution: Turn the switch to the left or right power supply.
2. The main switch of the incoming cabinet cannot be opened
Causes:
1. The opening button is not in good contact. Workaround: Replace the opening button.
2. The opening coil burns out. Solution: Replace the opening coil
3. The main metering reactive power meter is reversed or not rotated
Causes:
1. The power factor of capacitance compensation is high or advanced. Solution: Adjust the capacitance compensation to 0.92-0.97.
2. The phase sequence of the transformer incoming line is wrong. Workaround: Readjust the phase sequence.
3. The voltage and current circuit is normal. Solution: Replace the reactive power meter.
Fourth, the capacitor cabinet can not be automatically switched
Causes:
1. The current sampling signal line is not connected. Solution: Connect the current sampling signal line.
2. Check whether the fused core of the controller is burned out. Solution: Replace the melt core.
3. The voltage is too high, and the controller shows overvoltage. Solution: Adjust the overvoltage protection point.
4. The current is small, and the controller display is ahead. Solution: It can work normally automatically when the current is increased.
5. The compensator of the capacitor cabinet (distribution cabinet related category: box-type substation and distribution box) shows overvoltage. Solution: Adjust the set voltage value higher than the actual voltage.
6. The current sampling signal line is not connected. Solution: Connect the current sampling signal line.
7. The fuse core of the compensation controller is burned out. Solution: Replace the melt core.
8. The current is small. Solution: Further debugging and processing after the electric current increases.
Fifth, the drawer outlet line energy meter does not turn
Causes:
1. Check whether the secondary plug-in is in poor contact. Solution: Adjust the secondary plug-in contact piece.
2. The current and voltage are normal. Solution: Replace the watt-hour meter.
6. Dual-power switching cannot be switched automatically
Causes:
1. The universal transfer switch does not go to the automatic position. Workaround: Turn the switch to the automatic position.
2. The manual transfer switch is not converted to the automatic position. Solution: Turn the handle automatic transfer switch to the automatic position.
3. The under-voltage tripper is not closed. Solution: Check whether the voltage is consistent with the tripper voltage level V ≥ 85%.
4. The time relay is not closed. Solution: Check whether the contact voltage of the time relay 2#7# is normal.
5. The circuit breaker excitation mechanism is not reset. Solution: Check whether the mechanical interlock is loose and whether there is any stuckness.
7. The power factor of the capacitor cabinet cannot reach more than 0.9
Causes:
1. The capacitance of the capacitor is reduced. Solution: Replace the capacitor.
2. Some circuits are not energized. Solution: Replace after inspection.
3. The original design load increases. Solution: Increase the compensation capacity of the capacitor bank.
|
More on that
|
Cable management components for Rittal's IT cabinets
An IT cabinet generally needs to arrange a lot of cables, including strong current cables for power supply equipment, optical fibers used for communication, and weak current cables for signal transmission. So many cables in a cabinet if not well packed up form a clutter of cables in the cabinet, and then ...
|
|
Rittal X Kongsberg | Smart ship "Wei" can be expected
Smart ships are a key area clearly supported by national policies. Driven by policy guidance and innovation, China has achieved phased results in the research and construction of smart ships. As the world's leading provider of enclosure systems, Rittal has a wide range of applications in the marine and port sectors.
|
|
A basic introduction to a very popular explosion-proof box in Rittal
As a commonly used box in Rittal, many users do not understand the material and structure of this series of boxes.
Now I would like to introduce the Rittal explosion-proof enclosure
Apply:
– Zones 1 and 2 or Zones 21 and 22 according to 94/9/EG
– Ambient temperature range: -30°C.
|
|
Five hidden details you didn't know about Rittal cabinets and common Q&A
Five details that are easy to overlook:
One of the hidden details: steel
The most basic thing of a cabinet is to look at the steel, the Rittal standard cabinet is made of section steel, there are many masters who understand the cabinet to understand, the steel plate must be thick, just knock it with your fingers. General ...
|
|
Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets
What is a busbar?
Answer: In the voltage distribution devices at all levels of power plants and substations, the wires connecting engines, transformers and various electrical appliances are called busbars.
What is the classification of busbars?
Answer: soft bus (mostly used in outdoor power distribution room with high voltage) and hard bus (low ...
|
|
What are the main classifications of Rittal cables – power cables?
Classified by voltage level
According to the voltage level, it can be divided into medium and low voltage power cables (35 thousand volts and below), high-voltage cables (above 110 thousand volts), ultra-high voltage cables (275-800 thousand volts) and ultra-high voltage cables (1000 thousand volts and above). In addition, it can also be divided into AC ...
|
|
Rittal Rittal economy air conditioning, RBT cooling unit
Rittal has an economical air conditioner on the market, and the Rittal RBT cooling unit – is your most economical choice! If a limited budget makes you more interested in the cost
Extremely sensitive, then RBT is the ideal choice for you
Choose. Produced through large-scale assembly lines, as well as cold
But the unit itself is excellent ...
|
|
Common faults and troubleshooting methods of oil coolers - Rittal cabinets
Fault symptom 1: insufficient cooling capacity
Cause analysis
(1) The room or box is not sealed or the thermal insulation performance is poor
(2) The evaporator frost is too thick
(3) The efficiency of the compressor deteriorates
(4) The expansion valve is too large or too small
(5) There are more ...
|
|
What are the classifications of Rittal cabinets? What is the difference with a general cabinet?
1. What are the classifications of Rittal cabinets?
1. According to the function, it can be divided into: fireproof and anti-magnetic cabinet, power cabinet, monitoring cabinet, shielding cabinet, safety cabinet, waterproof cabinet, safe, multimedia console, file cabinet, wall-mounted cabinet.
2. According to the scope of application, it can be divided into: outdoor cabinets, ...
|
|
Rittal cabinets – the cause of moisture in electrical cabinets
(1) The cause of moisture in the cabinet
1) Environment shutdown. The ring main unit or the opening and closing station itself is a closed environment, because of the poor ventilation conditions, it is easy to gather moisture and generate condensation, and there are many large buildings today in order to reduce the occupied area, the opening and closing station, the power distribution room is built in the basement. Cause...
|
|
Rittal cabinet - knowledge quiz of high and low voltage distribution cabinet (1-10)
1. What is TT, IN, IT system?
A: The TT method refers to a protection system that directly grounds the metal shell of electrical equipment, which is called a protective grounding system, also known as a TT system. The TN method is a protection system that connects the metal shell of the electrical equipment with the working neutral line, called ...
|
|
A detailed introduction to the classification and division of Rittal cabinet products
Rittal products are divided into:
Rittal control cabinets: small enclosures (polycarbonate enclosures PK, junction enclosures KL, compact control enclosures EB, bus enclosures BG), compact control enclosures, plastic control enclosures KS, enclosure systems (subdivided into TS 8/SE 8 family), and...
|
|
Rittal Blue e+ cooling unit in the cooling of the Airbus A320 test plant
A new A320 Airbus aircraft must pass rigorous testing before it can be put into service, so to ensure a smooth flight, not only the aircraft itself needs to be protected from overheating, but also the test hardware needs to be properly protected. Airbus uses Rittal Blue e+ cooling units to make it ...
|
|
Precautions for the use of Rittal electrical cabinets
1. When the electrical cabinet is used, the shell should be reliably grounded, and the electrical parts should be comprehensively inspected to eliminate the phenomenon of leakage and open circuit that may be caused by long-distance transportation, and check whether the voltage is consistent with the working voltage.
2. The electric cabinet is a non-explosion-proof oven, so it is flammable, explosive, volatile and corrosive.
|
|
The Rittal plastic handle replaces the standard lock with or without a secure semi-circular cylinder
Product Model 2485.100
Replace standard locks with or without a secure semicircular cylinder.
Type::C
Color: RAL 9011
A note on the order number: Not suitable for AE 1018.600
Lock: Cylinder: No safety cylindrical cylinder
...
|
|
An introduction to the features of Rittal cabinet fans
Wide air volume range: 20-900m3/h
Innovative diagonal flow fan and brushless DC EC motor technology for higher air flow and uniform distribution of cold air
Comes with an interface module for controlling and monitoring fans
The standard degree of protection is IP54, up to IP56 with a water spray cover
...
|
|
Rittal at the Hannover Messe 2022 in Germany
"In 2022, with all the challenges, especially for small and medium-sized manufacturing companies – we need to think differently: if we want to support our customers and add value in our digital transformation, it's not just a single product innovation that will change. It will combine automation, digital ...
|
|
Rittal toroidal transformers Primary connection 115 V/400 V
Rittal toroidal transformer primary connection 115 V/400 V
Product Model: 3201.970
Power supply for wall-mounted air/water heat exchangers in 230 V sizes. A 115 V or 400 V main connector is available.
Product Description: Wall for 230 V Specification
|
|
Rittal X SF | Helping smart logistics airports set sail safely
Hello, your courier has been sent out and will be delivered tomorrow morning.
Perfect logistics network, intelligent sorting, digital control ...... The development of modern logistics has made logistics services increasingly efficient and fast, and timely delivery and next-day delivery are no longer slogans.
|
|
Rittal enclosures – how to determine the quality of a sheet metal enclosure cabinet
1. Look at the material, you should choose a sheet metal chassis cabinet, and the steel plate must be thick, you can feel which ones are thick and which ones are thin when you knock them with your fingers. Its rugged enclosure protects the board, power supply and storage devices, and is resistant to voltage, shock, and dust.
|
|