Common faults in the instructions of Yaskawa G7 inverter
Overcurrent (OCOvercurrent)
Note: The output current of the inverter exceeds the overcurrent detection value.
Common Causes:
Short circuit or grounding occurs on the output side of the converter (motor burnout, poor insulation, contact due to cable damage, grounding, etc.).
The load is too large, and the acceleration time is too short; (Usually appears in the report during the debugging acceleration process, adjusting the acceleration time, and checking L2-03)
The solenoid switch on the output side of the converter has started working.
Short-term stall rotation of the motor, such as slow action of the brake when opening the brake (it may be that there is a problem with the brake, or there is a problem with the debugging program, or the brake pad is rubbed, or there is no zero-speed brake when the brake is opened, and the absence of zero-speed brake is usually a parameter, or there is a problem with the program)
GFGrounFavlt)
Note: The grounding current at the output end of the inverter exceeds 50% of the rated output current of the inverter.
Common Causes:
The output side of the converter is to the ground (contact and grounding caused by motor burnout, poor insulation, cable damage, etc.) with a shake meter to check whether the motor inlet wire is grounded and whether the motor wiring is wet in the converter box;
If the motor is not grounded, it may be caused by a faulty detection ring, please replace the drive plate.
The solenoid switch on the output side of the converter has started working.
The motor is stalled for a short time, such as slow braking action when opening the brake (it may be that there is a problem with the brake, or there is a problem with the debugging program, or there is a brake friction, or there is no zero-speed brake when the brake is opened, usually there is no zero-speed brake when the parameter or stroke is opened).
puf
Fuse (DCBusFuseOpen)
Note: The fuse installed in the main circuit is damaged due to a short circuit at the output end of the inverter. Common causes: Fuse burn, which may be due to the short circuit of the DC bus, resulting in fuse burn, and there are several reasons for the short circuit of IGBT:
quality problems, aging of components, etc.;
Due to the humid environment, the temperature is too high, the dust is more, the vibration, the external environment changes drastically, such as the air conditioner against the wind after the power failure, it is easy to report the loss of operation after power, and if the environment where the inverter is located vibrates greatly, it is easy to cause damage to the IGBT.
Whether there is a motor that stalls when starting and stopping, resulting in a large starting current.
Due to the failure of the drive, the IGBT trigger is poor.
The large amount of Yaskawa inverter G7, coupled with the aging of components in the long-term use process, the poor contact of the installation of peripheral equipment, and the influence of the external environment of the work will cause the inverter to report failure
|
More on that
|
Yaskawa servo motor MP2300/MP2310/MP2300S function introduction
It is an all-in-one controller with built-in power supply, CPU, communication and servo control.
From simple positioning and interpolation to advanced multi-axis control, we are looking for cost-effective devices.
Compatible with open networks
Just install the optional module in the slot, which not only corresponds to the open network, but also ...
|
|
How to deal with the fault Fn000 reported by Yaskawa servo drive
1. Check whether the encoder cable is good and carefully check the coding cord plug. Whether the soldering points and cable bow and foot row are normal;
2. If no wire and plug problems are found, rule out the interference of the encoder cable, please separate the encoder cable from other wires (power cables);
3. Line ...
|
|
Yaskawa Electric - Introduction to the starting method of three-phase asynchronous motor
There are three main starting methods of three-phase asynchronous: direct start, traditional decompression start and soft start.
Direct start, also called full pressure start. Decompression starting is to reduce the voltage on the stator winding during starting, and then restore the voltage to the rated after starting.
Include...
|
|
Yaskawa servo drive debugging method
Some methods when debugging Yaskawa servo drives
In the Yaskawa servo system under low rigidity (1-4) load, the inertia ratio is very important, from the perspective of the synchronous belt structure, the stiffness is about 1-2 (or even less than 1), at this time, the inertia ratio can not be automatically tuned, it must be ...
|
|
What industries can Yaskawa Robotics GP180 be used in?
1. Automobile manufacturing: In the automotive manufacturing industry, Yaskawa Robot GP180 can be used for welding, dispensing, cutting, and assembly, etc.
2. Electronics industry: In the electronics industry, Yaskawa Robot GP180 can be used for semiconductor chip production, mobile phone assembly, etc.
3. Food ...
|
|
Yaskawa inverter - what are the application fields of low-voltage inverter?
1. Fan
With the continuous development of industry, the application of fans is becoming more and more extensive, especially in the chemical, stone and textile industries. However, there is a general problem of over-air volume in the design of the fan, and throttling is generally used when the air volume needs to be adjusted, that is, the damper is adjusted.
|
|
What are the reasons for Yaskawa servo A71 alarm in addition to overload?
1. It occurs when the power is turned on
It's a servo unit fault
2. On servo on is happening
It is an abnormal wiring of the motor (there is a connection problem or there may be a wrong wire, I encountered a wrong phase)
3. The encoder wiring is abnormal
Servo unit failure
4. Re-enter the finger ...
|
|
What are the main models of Yaskawa robots?
Yaskawa robot models are mainly as follows:
Product 1, Yaskawa Robotics SEMISTAR-M, V series--MCL, MFL, MFS series MCL165
The MCL165 is suitable for handling large and heavy loads in clean rooms. The maximum load weight is 165KG, and the cleanliness reaches ISO6 level.
...
|
|
The application of Yaskawa inverter in the petroleum industry
1 Introduction
Over the years, Yaskawa has accumulated very rich experience in the petroleum industry, such as G7/P7/F7/G5/P5/G5HHP/VS and other different series of inverters have been widely used in OEMs, the main fields are centrifugal separators, pumps, fans, transportation equipment ...
|
|
Yaskawa inverter reports Uv1 fault code solution
Yaskawa inverter Uv1 fault name: main circuit undervoltage
If the operation command is not entered (the inverter is stopping), the following conditions occur.
1. The DC voltage of the main circuit is lower than the set value of L2-05 (the detection value of the undervoltage (UV) of the main circuit).
2. 200V class: about 190V ( ...
|
|
How to establish an external start signal for Yaskawa Robot DX100
1. Enter the editing mode of Yaskawa robot first
2. Select "Function Effective Setting" for setting
3. Select "Allow" to start the appointment
4. Click Settings to enter "Appointment Activation (Connection)"
5. Set the input signal and output signal you need.
|
|
The basic operation of Yaskawa robots
First, the correct boot steps: Yaskawa robot
1. Turn on the power switch of the transformer and press the power [start] button.
2. Turn on the [power switch] of the control box, and press the [servo button] according to the prompts on the screen of the instructor
2. Simple operation of the robot
...
|
|
Yaskawa Robotics - What is the processing structure of the robot controller?
1. Serial processing structure
The so-called serial processing structure means that the control algorithm of the robot is processed by the serial machine, for this type of controller, from the computer structure, control mode to divide, and can be divided into the following:
1. Single CPU structure, centralized control mode ...
|
|
Yaskawa servo drive failure causes and maintenance treatment
Yaskawa MOTOMAN servo drive fault repair:
1. The motor runs faster in one direction than in the other;
(1) Cause of failure: The phase of the brushless motor is wrong.
Solution: Detect or detect the correct phase.
(2) Cause of failure: In the absence of ...
|
|
What is the fault of Yaskawa servo drive alarm code 710 and how to solve it
Yaskawa servo drive alarm code 710 is overload (large load), the motor is overloaded for a few seconds to tens of seconds.
Solution(s):
1. Change the mechanism, or the acceleration and deceleration mechanism.
2. Change the motor.
3. Exclusion order:
1) The load is really too large
2) ...
|
|
Yaskawa robot spraying process application virtual simulation operation method
Spraying is another common process application of industrial robots, second only to welding process applications, and they all belong to high-intensity, high-precision, and high-sensitivity work tasks in harsh environments.
The spraying process has extremely high requirements for the performance of the robot, of course, for the formulation of the process, ...
|
|
Parameter setting steps of Yaskawa H1000 inverter
1. No-load power-on test of inverter
1. Ground the grounding terminal of the inverter.
2. Connect the power input terminal of the inverter to the power supply through the leakage protection switch.
3. Check whether the factory display of the inverter display window is normal, if it is incorrect, it should be reset, otherwise ...
|
|
The solution of Yaskawa servo drive alarm A.F10, A.F50, A.920
A.F10: Power line is out of phase (the low voltage state of one phase of R, S, and T phases lasts for more than 1 second in the state of the main circuit power supply ON)
Cause:
Poor wiring of three-phase wires
The three-phase power supply is unbalanced
Single-phase AC power input is not set (Pn00E ...
|
|
Yaskawa servo drive alarm 810 reset method
1. Check the reason for alarm 810: Alarm 810 is caused by the temperature inside the controller is too high, which may be caused by the heat inside the controller is too high or the power supply voltage is unstable.
2. Check the heat dissipation of the controller: check whether the radiator of the controller is blocked, ...
|
|
Yaskawa Servo Drive FAQ (1-9)
[1] Yaskawa 5 series 1KW drive on telegram 030 what is the reason?
When you power on, it will display 030, check the manual to explain: the main circuit is abnormal in various detection data, and there is no problem with the main circuit module after checking.
Is there a motherboard that can be swapped to try, if not...
|
|