Mitsubishi servo system common alarms and solutions

Create Date: 2024-8-30 12:03:23|Source: Mitsubishi Electric/Mitsubishi Electric

The use of Mitsubishi AC servo system is mainly composed of three series: MR-ES, MR-J2S, MR-J3. In general, the cause of the fault can be preliminarily determined based on the code displayed on the servo drive, and then troubleshooting:

                                  Mitsubishi servo system common alarms and solutions

  1、AL. E6 - Indicates servo emergency stop. There are generally two reasons for this fault, one is that the 24V power supply of the control loop is not connected, and the other is that the EMG and SG of the CN1 port are not connected.

  2. AL.37 - parameter abnormality. The internal parameters are disordered, the operator sets the parameters incorrectly, or the drive is caused by external interference. The general parameters can be solved by restoring them to the factory value.

  3. AL.16-encoder failure. The internal parameters are out of order, or the encoder line is faulty, or the motor encoder is faulty. If the fault persists, the driver backplane is damaged.

  4. AL.20-encoder failure. Caused by motor encoder failure, cable breakage, loose connectors, etc. Replace the encoder line or servo motor encoder. When this fault occurs in the MR-J3 series, there is another possibility that the CPU ground wire of the driver is burned.

  5. AL.30 - abnormal regenerative braking. If an alarm occurs as soon as the power is applied, the internal brake circuit element of the drive is damaged. If it occurs during operation, the wiring of the braking circuit can be checked, and if necessary, the braking resistor can be externally equipped.

  6. AL.50, AL.51 - overload. Check whether the output U, V, W three-phase sequence wiring is correct, and the three-phase coil of the servo motor is burned out or the ground is faulty. Monitor whether the load rate of the servo motor exceeds 100% for a long time, the servo response parameters are set too high, and resonance is generated.

  7、AL. E9 - The main circuit is disconnected. Check whether the power supply of the main circuit is connected, if it is normal, the main module detects the circuit fault, and the driver or accessories must be replaced.

  8. AL.52 - The error is too large. The motor encoder is faulty or the circuit element of the drive output module is damaged, and there are usually many faults in the use of oil stains.

  In addition, a simple way to judge the fault of the servo motor: after removing all the wiring of the motor, rotate the motor bearing, if you can feel the obvious resistance, the rotation is not smooth, the fuselage coil is burned out, and the coupling is not properly assembled, it is easy to knock out the encoder, you can shake the motor encoder part, if you can hear the sound of the encoder fragments, the encoder is knocked out.
More on that
Mitsubishi Electric instruction format Mitsubishi Electric instruction format

(1) Arbitrary axis AC command (G140) G140 Instruction Address = Axis Address Instruction Address = Axis Address ... ; Command Address: Arbitrary Axis AC Command (G140) After that, specify the 1-character address set by the parameter (#12071-#12078) to be used for moving commands, etc.

Mitsubishi servo system common alarms and solutions Mitsubishi servo system common alarms and solutions

The use of Mitsubishi AC servo system is mainly composed of three series: MR-ES, MR-J2S, MR-J3. In general, the cause of the fault can be preliminarily determined based on the code displayed on the servo drive, and then troubleshooting: 1、AL. E6 - Indicates ...

Mitsubishi inverter overload fault judgment method Mitsubishi inverter overload fault judgment method

1. Check whether the three-phase electricity of the motor is balanced (1) If the three-phase voltage of the motor is unbalanced, then check whether the three-phase voltage at the output end of the Mitsubishi inverter is balanced. (2) If the three-phase voltage of the Mitsubishi inverter is also unbalanced, the problem is inside the Mitsubishi inverter, and it should be investigated.

The connection of the Mitsubishi inverter FR-A800 The connection of the Mitsubishi inverter FR-A800

The connection of the Mitsubishi inverter FR-A800

A brief description of Mitsubishi's PLC network structure A brief description of Mitsubishi's PLC network structure

1. The equipment layer/fieldbus CC-Link equipment layer is a field network that connects PLC and other control equipment, sensors and drive equipment, which is the lowest layer of the entire network system. CC-Link fieldbus connection is selected, the number of wiring is greatly reduced, and the maintainability of the system is improved. Whereas...

Mitsubishi PLC controls the servo motor through a touch screen Mitsubishi PLC controls the servo motor through a touch screen

The Mitsubishi PLCFX3U-48MT-ES-A is used as the control element, and the Mitsubishi touch screen GT1155-QFBD-C is used as the operating element to directly control the specific program design of the Mitsubishi servo motor. First, the selection of components in the control system 1. Selection of PLC In the application of Mitsubishi servo drive ...

Mitsubishi servo motor realizes positioning function Mitsubishi servo motor realizes positioning function

The motion control command of the PLC realizes the perfect positioning function. Briefly describe the Mitsubishi PLC positioning instructions, which can be divided into origin regression instructions DSZR, ZRN, positioning instructions PLSY, PLSR, DRVI, DRVA, variable speed operation PLSV.3 In the meantime, PLSY and PLSR are pulse output instructions, and their positioning functions are relatively ...

Mitsubishi PLC control inverter method Mitsubishi PLC control inverter method

1. Mitsubishi PLC's analog signal control inverter Hardware: FX1N, FX2N PLC hosts, equipped with 1 simple FX1N-1DA-BD extended analog output board; or analog input-output hybrid module FX0N-3A; or FX2N-2DA with two outputs; or four outputs ...

Mitsubishi PLC Explanation Notes on the Final Statement Mitsubishi PLC Explanation Notes on the Final Statement

If the language is a programming language without any explanation, it will be very difficult for the engineer to understand the program again, and some clarification can bring twice the result to the work. There are three types of explanations: notes, statements, and notes. Note: Explain a certain ...

Mitsubishi PLC communication detection steps Mitsubishi PLC communication detection steps

When you are ready to communicate through AJ71QE71, perform the ping procedure in MS-DOS mode to check if the connection is correct before the Mitsubishi PLC's GPPW starts to communicate. Support communication with Weilun touch screen through serial port. ...

Mitsubishi FX series PLC fault diagnosis method Mitsubishi FX series PLC fault diagnosis method

1. Power indication (LED indication) When power is supplied to the Mitsubishi PLC root unit, the [POWER] LED indicator light installed on the surface of the root unit turns on. If the power supply is closed but the [POWER] LED does not illuminate, please acknowledge the power wiring. In addition, if the same power supply has a drive sensor, etc. ...

Mitsubishi touch screen common faults and solutions Mitsubishi touch screen common faults and solutions

Fault 1: Mitsubishi touch screen contact deviation Phenomenon: The direction of finger contact does not match the mouse arrow. Analysis: When calibrating the orientation after installing the screwdriver, there is no vertical contact with the bull's-eye. Solution: Recalibrate the bearing. ...

Mitsubishi MELSEC iQ-F makes IoT a simple one Mitsubishi MELSEC iQ-F makes IoT a simple one

The MELSEC iQ-F series of small PLCs completes the high-speed system bus, supports a variety of networks, enriches the built-in functions, and makes it more convenient to use. From stand-alone use to network-based system proposals, we strongly support the needs of customers for "cutting-edge products in the manufacturing industry". Using the MELSEC iQ-F...

Mitsubishi PLC keeps the circuit written Mitsubishi PLC keeps the circuit written

There is a very common kind of circuit in Mitsubishi PLC - the persistence circuit. The holding circuit means that when the external input switch is a button, it can press the button through the holding circuit to insist on the output, similar to the self-locking in the electrical diagram. We use Mitsubishi PLC as an example to write a sticking circuit. ...

Confirmation and clearing of Mitsubishi inverter alarm history Confirmation and clearing of Mitsubishi inverter alarm history

When the FR-CS80 inverter detects an abnormality, it will display an error message or alarm in the operation panel according to the abnormal content, or maintain the function action and block the output of the inverter. When maintaining a function operation, please deal with the cause of its operation before resetting the inverter, and then start working. ...

Mitsubishi 5uplc monitors modbusTCP disconnect methods Mitsubishi 5uplc monitors modbusTCP disconnect methods

First, Mitsubishi uses FX5U series PLC with serial port and built-in modbus communication protocol, so that we can easily communicate with third-party equipment. If it is a communication between Mitsubishi PLC and the inverter, the focus is on designing the parameters. The inverter is heavy, set the address, baud rate, check, etc., ...

Mitsubishi inverter pre-use debugging steps Mitsubishi inverter pre-use debugging steps

1. No-load energizing test of Mitsubishi inverter. 1. Ground the ground terminal of the Mitsubishi inverter. 2 Connect the power input terminal of the Mitsubishi inverter to the power supply through the leakage maintenance switch. 3 Check whether the factory display window of Mitsubishi inverter is normal, if it is not correct.

Mitsubishi PLC commonly used model features Mitsubishi PLC commonly used model features

FX Series PLC: The FX3G PLC has a built-in large-capacity program memory, 32K steps, and the basic instruction processing speed can reach 0.21μs in standard mode. In the meantime, the FX series 5U is suitable for any industry, and is widely used by small and medium-sized enterprises. For example, this year's very popular mask machine is suitable for FX5U, and he can ...

Analysis of PLC and inverter connection problems - Mitsubishi Analysis of PLC and inverter connection problems - Mitsubishi

When the inverter is used to form an active control system for control, in many cases, the PLC and the inverter are used together, and how to correctly connect the PLC and the inverter together has become the key to the success of the system. 1. PLC switch command signal input Inverter input ...

Preparation steps for the installation of PLC - Mitsubishi Preparation steps for the installation of PLC - Mitsubishi

Installation and commissioning of the system Reasonable arrangement of system installation and commissioning procedures is the key to ensure that the installation and commissioning mission is completed efficiently and with high quality. 1. Preliminary skill preparation The more abundant the skills to prepare for the commissioning of the system device, the smoother the installation and commissioning will be. Former...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top