There are additional torque, maximum torque and servo motor inertia and other parameters in the standard items of each type of servo motor, and there must be relevant contact between each parameter and load torque and load inertia, and the output torque of the servo motor should meet the requirements of the motion conditions of the load organization, such as the speed of acceleration and the component of the organization; methods of movement of the organization (horizontal, vertical rotation), etc.; There is no direct relationship between the motion condition and the output power of the servo motor, but the higher the output power of the servo motor, the higher the relative output torque. Therefore, not only the tissue components will affect the selection of the servo motor, but the motion conditions will also change the selection of the servo motor. The larger the inertia, the greater the acceleration and deceleration torque, and the shorter the acceleration and deceleration time, the greater the output torque of the servo motor. When selecting the servo motor standard, follow the following steps.
(1) Clear requirements for the movement conditions of the load tissue, that is, the speed of acceleration/deceleration, the speed of movement, the component of the tissue, the movement method of the tissue, etc.
(2) According to the requirements of the operating conditions, the appropriate load inertia accounting formula is selected to calculate the load inertia of the organization.
(3) According to the load inertia and servo motor inertia, select the appropriate false servo motor standard.
(4) Combined with the inertia and load inertia of the servo motor in the primary selection, the acceleration torque and deceleration torque are calculated.
(5) Calculate the load torque according to the load component, configuration method, friction coefficient and operation effect.
(6) The maximum output torque of the primary servo motor must be greater than the acceleration torque + load torque; If the conditions are not met, it is necessary to use other types of accounting verification until the requirements are met.
(7) The continuous instantaneous torque is calculated according to the load torque, acceleration torque, deceleration torque and holding torque.
(8) The additional torque of the primary servo motor must be greater than the continuous instantaneous torque, for example, if it does not meet the conditions, it is necessary to choose other types of accounting verification until it meets the requirements.
|
More on that
|
Overheating failure light on start-up analysis - Reynolds
(1) Frequent starting, resulting in excessive temperature, causing overheating maintenance of soft starter. (The number of starts of the soft starter should be controlled to no more than 6 times per hour, especially for heavy loads)
(2) During starting, ...
|
|
Frequency converter maintenance and interference removal – Reynolds frequency converters
Working environment
In the actual application of inverters, most people install inverters directly in industrial sites in order to reduce costs. The job site generally has the problems of large dust, high temperature and high humidity, and in some occupations, there are also metal dust, corrosive gases and so on. There must be ...
|
|
Reynolds inverter control panel and code function description
1. Clarification of the function of the control panel
1. FUN button; Press the FUN button to enter the settings menu F00;
2. Press and hold the up or down button to scroll to the code you need to set;
3. At this moment, press the FUN button to confirm, and adjust the entry parameters to the required value;
4. After the adjustment is completed, ...
|
|
Frequency characteristics of Reynolds frequency converters
a. Output frequency scale. The output frequency scale that can be controlled by the general inverter, the lowest starting frequency is generally 0.1Hz, and the highest frequency is different according to the functional indicators of the inverter, generally 400Hz, and some models are 650Hz. No matter how high the output frequency is, it depends on the scale of the high-frequency inverter.
...
|
|
The abnormal installation of the inverter in the power frequency motor leads to hazards
Installing a variable-frequency drive (VFD) on the power frequency motor can complete the precise control and speed regulation of the motor, and improve the power and accuracy of the progressive motor. However, if it is not properly used and used, the following damages may occur:
...
|
|
Reynolds high-speed permanent magnet synchronous motor dedicated driver
The state proposes to "peak carbon emissions" by 2030 and complete "carbon neutrality" by 2060. Carbon neutrality is to try to reduce carbon dioxide emissions, and eventually achieve net zero emissions, that is, to make carbon dioxide emissions even offset.
However, due to economic development, CO2 emissions are stable ...
|
|
Precautions for low-temperature operation of VFD
1. VFD should be operated in an environment above minus 10°C as much as possible, and it is best to operate indoors.
2. When the VFD is started and stopped, try to start and stop with the VFD itself, do not close the power supply, and keep your VFD in a power-on state.
3. Give VFD l ...
|
|
Inverter: The right inverter to use - Reynolds
Low pressure issues
The VFD reports a low voltage issue when the drive's DC link voltage drops below 62% of the nominal level at the high setting (480 Vac) and 50% of the nominal value at the low setting (400 Vac).
The +10% and -15% voltage tolerances in most manuals are the ones that claim to be ...
|
|
Rated current analysis of inverter leakage circuit breaker
The output of the inverter is controlled by PWM (pulse width modulation, similar to high-speed switching), so a high frequency leakage current will occur, if you want to install a general leakage disconnect switch on the primary side of the inverter, it is recommended to select a sensitivity current of more than 200mA for each inverter and the action time is 0.1 seconds ...
|
|
How long is the cable between the inverter and the motor allowed - Reynolds
The voltage waveform output by the inverter is only similar to a sine wave, but not a real sine wave, and its waveform contains a large number of harmonic components.
As we all know, the higher harmonics will increase the output current of the inverter, causing the motor winding to heat up.
|
|
Reynolds inverter E.oC3 constant speed operation overcurrent fault solution
Reynolds inverter RNB1000 series E.oC3 constant speed operation overcurrent fault solution
Reynolds inverter fault codes:
E.oC3
Reynolds inverter fault phenomenon/type:
Constant speed operation overcurrent
Possible causes of Reynolds inverter failure:
...
|
|
Reynolds soft starter features:
The Reynolds soft engine is a new type of software launcher that can assist users in quickly launching and closing the computer system. It was developed by Reynolds and its main function is to provide a fast, safe and reliable software launcher that can assist users in quickly launching and closing ...
|
|
Frequency converters need to be replaced regularly – Reynolds
The inverter is composed of many electronic parts, such as semiconductor components, etc., in the application and protection involves the replacement of a related component, because of the composition or physical characteristics of the inverter, it will deteriorate in a certain period of time, which will reduce the characteristics of the inverter, and even ...
|
|
The heat dissipation method of Reynolds switching power supply
1. Transfer heat pipes for heat dissipation.
In many applications, the heat generated from the base steel plate of the power module is transferred through the heat transfer components to the distant heat pipe surface. In this way, the temperature of the base steel plate of the power module will be equal to the temperature of the heat pipe heat dissipation surface, the temperature of the heat transfer parts, and the temperature of the two contact ...
|
|
Precautions for the coordination of PLC and inverter - Reynolds
Under the current production conditions, when the inverter is used to form an automatic control system for control, in many cases, it is necessary to choose PLC and inverter to match the use, such as bearing cleaning, packaging paper printing, PCB board production, etc.
PLC ...
|
|
Precautions for the use of frequency converters - Reynolds
In order to ensure the safe, efficient and reliable operation of the inverter, the following keys should be grasped when using the inverter:
1) It is necessary for the grounding terminal of the inverter to be firmly grounded, so as to effectively press the radio frequency disturbance and enhance the reliability of the system: the frequency conversion speed regulation system is best to use independent grounding, grounding resistance...
|
|
Interpretation of Reynolds inverter models
Take the RNB2000 series inverter as an example.
The model number of the RNB2000 series 37kW inverter is: RNB2037-U
RN: on behalf of Reynolds;
B: low-voltage frequency conversion governor;
2: 2000 series;
...
|
|
Inverter control method - Reynolds
The output voltage of low-voltage general frequency conversion is 380-650V, the output power is 0.75-400kW, and the operating frequency is 0-400Hz. Its control methods have gone through the following four generations. 1U/f=C Sinusoidal Pulse Width Modulation (SPWM) Manipulation MethodIts Characteristics ...
|
|
Reynolds-5G empowers the paper industry to improve quality and efficiency of the industrial IoT control system
From September 23rd to September 25th, 2020, the 2020 China International Paper Technology Exhibition was held in Hall D1 of Suzhou International Expo Center.
|
|
Parameter setting of acceleration and deceleration time of Reynolds universal inverter
The acceleration time of the Reynolds inverter is the time required for the output frequency to rise from 0 to the high frequency, and the deceleration time is the time required to decrease from the high frequency to 0. Generally, the frequency converter uses the frequency setting signal to rise and fall to confirm the acceleration and deceleration time. The rise of the frequency setting must be limited when the motor accelerates.
|
|