The treatment method of leakage protector often tripping - Delixi

Create Date: 2024-8-30 12:03:23|Source: Delixi

1. Trial delivery and commissioning method

The first thing to find is the fault of the remaining current action maintainer itself. The detailed operation method is: first block the power supply, and then remove all the zero sequence transformer load side leads of the remaining current action maintainer (the remaining current action maintainer of the second and third levels will directly remove the outgoing line) and then close the maintainer. If the maintainer is still not operational, it is clear that the maintainer itself is faulty and should be repaired or replaced. If it can operate normally, then there is nothing wrong with the maintainer itself, and then look for the switchboard or line. The operation method is: first block the load of each outgoing line or AC contactor, if it cannot be operated, it is clear that there is something wrong with the distribution board, and the electrical, appearance and other equipment should be checked whether the insulation is outstanding and whether the wiring is correct; If it can operate normally, it means that there is no fault on the switchboard. When it is confirmed that the fault occurs on the outer line, the branch line search method can be used to find the fault point.

                            The treatment method of leakage protector often tripping - Delixi

2 Visual inspection method

The intuitive inspection method is that the inspectors analyze and judge the fault phenomenon, and conduct an intuitive inspection of the maintenance area, including the remaining current action maintainer and the line equipment to be maintained, and then find out the fault points. During the inspection, the inspection should focus on the corners, branches, crossings and other messy sections and fault-prone points of the line. This method is simple and easy to implement and is suitable for finding obvious faults. For example, the wire is broken and the wire is on the ground, the wire is in contact with the wire and the wire is incorrectly wiring, etc.

3 Numerical comparison method

The numerical comparison method is to measure the line or equipment with the help of the surface of the instrument, and compare the measured value with the original value, and then find out the fault. In particular, when the insulation of the neutral wire of the line is reduced or the neutral wire of the equipment is repeatedly grounded, it simply causes the total maintenance to trip frequently, while the secondary maintainer does not trip. When dealing with the tripping of the secondary maintainer, the method of switching the phase wire and the neutral wire should not be adopted to put into operation the secondary maintenance, and the repeated grounding wire of the equipment can be removed.

4-point exclusion method

When checking the fault points of the line, you can disconnect the branches of the low-voltage power grid in accordance with the order of "first backbone, then branch, and then end", and only test the power transmission of the backbone line, if the backbone line is fine, then the backbone line can operate normally. Then, put the branches and then the end into operation. When the maintainer trips when the line is put into operation, the fault point is on the line, and the fault point can be found on this line in a centralized manner

More on that
Introduction to the closed-loop control system of stepper motor Introduction to the closed-loop control system of stepper motor

1. The closed-loop control of the stepper motor was first in the form of encoder For stepper motors with low split ratio, a slotted disc and photoelectric sensor are usually used as a reaction encoder assembly, and the number of notches is equal to the number of steps taken by the motor per revolution, · About high resolution ...

CDQ1F series PC-level excitation automatic transfer switch - Delixi CDQ1F series PC-level excitation automatic transfer switch - Delixi

Delixi Electric's newly launched CDQ1F series PC-level excitation active transfer switch, with more complete specifications and stronger functions, the power-off time can be shortened to less than 0.1s, escorting the continuous use of electricity in important places! CDQ1F Active ...

Delixi voltage regulator working principle Delixi voltage regulator working principle

In Delixi voltage regulator, the voltage correction from and under voltage conditions is performed through two basic operations, namely Oersted and step-down operation. These operations can be switched on and off manually or automatically by electronic circuits. Under voltage conditions, the voltage of the boost operation is increased to the rated voltage.

Delixi general inverter E100 series products introduction Delixi general inverter E100 series products introduction

E100 series products are a standard inverter with optimized open-loop vector control, V/F control, stable performance, rich functions, optimized structural design, exquisite appearance, and high cost performance. Technical features: ...

Why is the operation of the inverter energy-efficient? - Delixi Why is the operation of the inverter energy-efficient? - Delixi

The inverter lowers the output frequency to reduce the speed of the motor, taking the conditioning air volume as an example. By reducing the air volume, power consumption can be significantly reduced. Why is the operation of the inverter energy-efficient? According to fluid mechanics, power = pressure× flow, flow ...

Delixi integrated voltage regulator knowledge Delixi integrated voltage regulator knowledge

The role of a voltage regulator is to convert an unstable DC voltage into a stable DC voltage. The integrated voltage regulator has a wider and wider range of applications due to its advantages such as small size, good voltage regulation performance and perfect maintenance function. There are two types of integrated voltage regulators: linear power supply regulators and switching power supply regulators.

Delixi inverter installation and wiring Delixi inverter installation and wiring

1. The device of the inverter 1.1 The device environment requirements of the inverter Ambient temperature - 10 °C - 40 °C; Ambient humidity: The relative humidity does not exceed 90% (no condensation); Other occasions requiring no direct sunlight, no corrosive gas and flammable gas, less dust, ...

Delixi selects the rated parameters of the contactor Delixi selects the rated parameters of the contactor

According to the controlled target and operating parameters such as voltage, current, power, frequency and operating system, the additional parameters of the contactor are determined. 1) The coil voltage of the contactor should generally be lower, so that the insulation requirements of the contactor can be reduced, and it is safer to use. But for the sake of the party ...

Working principle and function of thermal relay Working principle and function of thermal relay

Thermal relay is a maintenance appliance used for overload maintenance of electric motors or other electrical equipment and electrical lines. In the actual operation of the motor, if the machine is in abnormal condition or the circuit is abnormal, the motor will be overloaded, the motor ...

Precautions for the use of Delixi leakage protector Precautions for the use of Delixi leakage protector

1. If the two branch lines are connected, the current in the zero line flows to each other, which destroys the operating current balance in the zero sequence current transformer and causes the leakage maintainer to malfunction. If you want to use the neutral line of the power branch line as the neutral line of the lighting branch line nearby, it will cause the leakage of the power branch line.

Delixi anti-leakage is different from ordinary circuit breakers Delixi anti-leakage is different from ordinary circuit breakers

Circuit breaker refers to a switchgear that can close, carry and break the current under normal circuit conditions, and can close, carry and break the current under abnormal circuit conditions within a specified time. Circuit breakers can be used to distribute electrical energy, infrequently start asynchronous motors, and ...

The difference between inverter reactor and filter - Delixi The difference between inverter reactor and filter - Delixi

The following options are available on the output side of the drive: 1) Output reactor, when the length of the cable output from the inverter to the motor is greater than the specified value of the product, the output reactor should be added to compensate for the charging and discharging influence of the coupling capacitor when the long cable of the motor is running, so as to prevent the inverter from overcurrent. Output ...

Delixi fan and pump load frequency conversion selection Delixi fan and pump load frequency conversion selection

Delixi general fan, pump, the requirements for the inverter are simple, only the inverter capacity is equal to the motor capacity. Roots blowers, deep-water pumps, sediment pumps, and fast-changing musical fountains are available in a larger capacity. Lifting...

Delixi molded case circuit breaker Icu=ICS understands Delixi molded case circuit breaker Icu=ICS understands

Delixi 3P air switch, additional current 630A, additional voltage 380V. The Icu=Ics=70kA of this circuit breaker. When the short-circuit current reaches 70kA, can the circuit breaker still be used? Assuming it works, the ICU is now at its limit, which is paradoxical. Assuming it can't be used, Ics is 70KA, clarifying ...

Delixi voltage regulator boot voltmeter does not indicate fault analysis and solutions Delixi voltage regulator boot voltmeter does not indicate fault analysis and solutions

When the Delixi voltage regulator is turned on, the voltmeter does not indicate the problem phenomenon and cause analysis 1. The plug is not plugged in firmly, and there is no output voltage 2. The fuse is broken When the Delixi voltage regulator is turned on, the voltmeter does not indicate the problem is solved ...

What are the advantages and disadvantages of dry and oil regulators? - Delixi What are the advantages and disadvantages of dry and oil regulators? - Delixi

Oil Regulator: Also known as non-contact inductive regulator or intelligent non-contact regulator (only the name of the company's own selling point). Forte: 1. No contact, no protection, impact resistance (especially instantaneous impact, 2 times of normal.) The reason for this is the slow response, which ...

General parameter setting skills of inverter - Delixi inverter General parameter setting skills of inverter - Delixi inverter

1. Upper frequency (high speed) SEt - HSP and lower limit frequency (low speed) SEt - LSP The upper frequency is the frequency corresponding to the *** large given, and the lower frequency is the frequency corresponding to the *** small given. The upper and lower limit frequencies are set to limit the speed of the motor, so as to satisfy the design.

Delixi voltage regulator in the case of no load stable work? Delixi voltage regulator in the case of no load stable work?

Most modern LDOs and switching regulators operate reliably under no-load conditions, and some older power devices require a minimum load to ensure stability, because one of the electrodes that needs to be compensated is affected by the payload resistance. For example, the LM1117 requires a load current of at least 1.7 mA (most ...

The scope of use of Delixi universal inverter The scope of use of Delixi universal inverter

A universal inverter is an electronic device used to control the speed of an electric motor, which can change the speed of the motor according to the needs and achieve higher production efficiency and energy savings. The general-purpose inverter has a wide range of application scales and can be used for various types of motors, including communication motors, direct motors, ...

The core difference between air disconnector and circuit breaker - Delixi The core difference between air disconnector and circuit breaker - Delixi

1. Although the air switch is a type of circuit breaker, it is a switch that will automatically disconnect as long as the current in the circuit exceeds the rated current. However, air switches are used in low-voltage distribution networks and electric traction systems, mostly on the low-voltage side. Widely used in the home, such as general household switches ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top