The difference between inverter reactor and filter - Delixi

Create Date: 2024-8-30 12:03:23|Source: Delixi

The following options are available on the output side of the drive:

1) Output reactor, when the length of the cable output from the inverter to the motor is greater than the specified value of the product, the output reactor should be added to compensate for the charging and discharging influence of the coupling capacitor when the long cable of the motor is running, so as to prevent the inverter from overcurrent. There are two types of output reactors, one output reactor is an iron-core reactor, which is used when the carrier frequency of the inverter is less than 3KHZ. ANOTHER OUTPUT REACTOR IS THE FERRITE TYPE, WHICH IS USED WHEN THE CARRIER FREQUENCY OF THE INVERTER IS LESS THAN 6KHZ. The function of adding an output reactor at the output end of the inverter is to increase the wire spacing between the inverter and the motor, and the output reactor can effectively press the instantaneous high voltage that occurs when the IGBT switch of the inverter is pressed, and reduce the adverse effects of this voltage on cable insulation and motor. In order to increase the interval between the inverter and the motor, the cable can be appropriately thickened, the insulation strength of the cable can be increased, and the unshielded cable can be selected as much as possible.

2) Output DV/DT reactor, the output DV/DT reactor is to constrain the rise rate of the output voltage of the inverter to ensure the normal insulation of the motor.

3) Sine wave filter, which makes the output voltage and current of the inverter approximate to the sine wave, and reduces the harmonic domain change coefficient of the motor and the insulation pressure of the motor.

                                    The difference between inverter reactor and filter - Delixi

The following options can be added to the input side of the drive:

1) Incoming line reactor, the input reactor can press the harmonic current, improve the power factor and weaken the impact of the surge voltage and current on the inverter in the input circuit, and weaken the impact of the power supply voltage imbalance.

2) Input EMC radio disturbance filter, the function of EMC filter is to reduce and press the electromagnetic disturbance caused by the inverter. There are two types of EMC filters, Class A and Class B filters. EMC Class A filters are used in the second category, i.e., industrial applications, and meet the EN50011A standards. EMC Class B filters are mostly used in the first type of applications, i.e., civil and light industrial applications, and meet the EN50011 Class B standard.
More on that
Delixi voltage regulator fault phenomenon and analysis Delixi voltage regulator fault phenomenon and analysis

Delixi regulator output voltmeter keeps swinging back and forth, and sparks occur at the carbon brush, and the problem phenomenon and cause analysis 1. The contact pressure between the carbon brush and the coil plane is too small 2. The carbon brush is severely worn Delixi voltage regulator has ...

The cause of the failure of Delixi inverter The cause of the failure of Delixi inverter

1. Overcurrent (short circuit) Overcurrent problems are the most common in the side of various faults in the inverter. The problem is mostly due to the following problems: first, as long as the speed converter is reported when starting, it is clear that the overcurrent is very serious, and most of them are load short circuits, mechanical parts stuck, inverters...

The reason for the whitening of the copper bar installed on the Delixi plastic case circuit breaker The reason for the whitening of the copper bar installed on the Delixi plastic case circuit breaker

In the project, because of the 630 A circuit breaker wiring bar in the 500 kVA box-type transformer, see the second circuit breaker and circuit breaker on the left in the figure. The temperature of this corresponding region is significantly higher than that of the other two corresponding regions, and the other two phases are also hot, and the copper bars of this phase have turned white. There is no induction Deli ...

Choose the right inverter method - Delixi Choose the right inverter method - Delixi

The type of inverter is selected according to the type of production machinery, speed regulation range, static speed accuracy, and starting torque requirements, and it is most appropriate to decide which inverter is the most suitable to use. The so-called suitability is not only easy to use, but also economical, to meet the basic conditions and requirements of technology and production. ...

The role of Delixi inverter on the motor The role of Delixi inverter on the motor

1. Frequency conversion speed regulation and energy saving. The inverter frequency conversion speed regulation and energy saving are mainly manifested in the application of fans and pumps. In order to ensure reliability in actual production, all kinds of production machinery are designed with power drives, and there is a certain margin. After turning down the motor rotation when there is no need to run at full speed in production, ...

Noise characteristics of different switching regulator topologies - Delixi Noise characteristics of different switching regulator topologies - Delixi

Currently, there are many different switching regulator topologies. Some topologies are widely used, such as the classic buck converter, also known as the buck converter. However, there are also some lesser-known switch-mode DC-DC converters that include Zeta topologies. These topologies are divided into fundamental topologies ...

Delixi three-phase transformer introduction Delixi three-phase transformer introduction

All large AC power blocks are transmitted and distributed at high voltage levels via a three-phase transformer. Single-phase transformers can be electrically connected to form a three-phase transformer bank in a distribution system. But the standard is to combine a single phase coil into a three-phase transformer unit on a common core ...

The operating structure of the high-voltage circuit breaker - Delixi The operating structure of the high-voltage circuit breaker - Delixi

1. Classification of switch operation organization At present, the switches we encounter are generally divided into many types, such as oil-rich type (old model, now you can't see it at all), oil-poor type (some user stations also have it), SF6, vacuum, GIS (combined electrical appliances) and so on. These are all about the arc extinguishing medium of the switch. ...

Delixi frequency converter E series precautions Delixi frequency converter E series precautions

1. Before the inverter device is in place and debugged, please tighten the components, especially the connecting bolts of the wire part, if not tightened, the connection will be heated and cause fire. 2. The on-site planning of the installation should be reasonable, and the excellent ventilation environment should be maintained. 3. The incoming and outgoing power lines of the inverter are not ...

Low dropout linear regulator application type - Delixi Low dropout linear regulator application type - Delixi

1.AC/DC the use of power supply Schematic diagram of the use of low-dropout linear regulators in AC/DC power supplies. In this circuit, the AC voltage is stepped down by the power transformer to obtain the low voltage of communication, and then the unstable DC voltage is obtained through the rectifier filter circuit, and then the voltage is regulated linearly by the low dropout ...

The difference between Delixi LDO and DC-DC The difference between Delixi LDO and DC-DC

The so-called DC-DC is actually DC to DC voltage, of course, LDO is also a kind of DC-DC, and only LDO can only achieve step-down. The general DC-DC is mainly converted from DC to AC communication through the self-excited vibration circuit inside, so the external inductance and capacitor are required to achieve LC vibration (and LDO is only ...

Fault analysis of commonly used voltage electrical appliances - Delixi Fault analysis of commonly used voltage electrical appliances - Delixi

1. Voltage circuit breaker problem The contact is overheated, you can smell the power distribution control cabinet, by checking that the moving contact is not completely inserted into the static contact, and the contact pressure is not enough, resulting in a decrease in the switching capacity, causing the contact to overheat. At this moment, it is necessary to adjust the operating organization so that the moving contact is completely inserted into the static contact ...

Delixi time control switch how to adjust the control time Delixi time control switch how to adjust the control time

1. Check the time first, if the time of the week, hour and minute is correct, don't care. If it's not correct, you need to take care of it yourself. Conditioning is very simple, you just need to press the clock, and then adjust the week by week, the hour of conditioning, and the minutes of conditioning. ...

Delixi low dropout linear regulator type Delixi low dropout linear regulator type

1.AC/DC the use of power supply Schematic diagram of the use of low-dropout linear regulators in AC/DC power supplies. In this circuit, the alternating current is stepped-down by the power transformer to obtain the AC low voltage, and then through the rectifier filter circuit to obtain the unstable DC voltage, and then through the low dropout linear voltage regulation.

How to wire and use the number of switches when the inverter starts and stops - Delixi How to wire and use the number of switches when the inverter starts and stops - Delixi

The control of the inverter is nothing more than the fundamental logic of starting, aborting, forward rotation, rotation, and speed regulation, which fundamentally requires that the level condition is effective, rather than the rising edge is effective, so the use of button switches to control the inverter is generally required to use the self-protection of the button...

The change of frequency conversion control mode - Delixi inverter The change of frequency conversion control mode - Delixi inverter

In the process of practical speed regulation, an ordinary frequency-adjustable communication power supply can not meet the requirements of speed regulation and control of asynchronous motors, and must also take into account the effective use of the motor magnetic field, the suppression of the starting current and the acquisition of the desired torque characteristics, such as low-frequency torque characteristics.

The basic knowledge of Delixi switching regulators The basic knowledge of Delixi switching regulators

1. What is a switching regulator? Switching regulator, English (regulatior), some people call it a regulator, a voltage regulator source. To achieve voltage regulation, it is the demand control system (negative feedback), from the automatic control theory, we know that when the voltage rises through negative feedback to reduce it, ...

Delixi CDI-EM60 series inverter Delixi CDI-EM60 series inverter

Delixi CDI-EM60 series inverter is a high-performance inverter, with the following characteristics and use: Characteristic: 1. It has good stability and reliability to ensure the stability and safety of the system operation. 2. High degree, wide range of speed control, ...

Analysis of common problems of inverter - Delixi Analysis of common problems of inverter - Delixi

1. Why does the maintenance function of the inverter operate when the clutch is connected to the load? When the load is connected with a clutch, at the moment of connection, the motor changes sharply from the no-load condition to the area with a large slip rate, and the large current flowing through causes the inverter to trip over the current and cannot work. ...

The treatment method of leakage protector often tripping - Delixi The treatment method of leakage protector often tripping - Delixi

1. Trial delivery and commissioning method The first thing to find is the fault of the remaining current action maintainer itself. The detailed operation method is: first block the power supply, and then remove all the zero-sequence transformer load side leads of the remaining current action maintainer (the second and third level remaining current action maintainers will directly remove the outgoing ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top