RKC Level Gauge – Four mounting methods for buoy level gauges

Create Date: 2024-8-30 12:03:23|Source: RKC

1. The buoy level gauge is welded and installed under the guide wire

At the bottom of the container, determine the position according to the requirements of the movement direction of the level gauge buoy, and weld or rivet the support under the fixed guide wire.

2. Buoy level gauge ruler installation

1. The connecting part of the ruler should be straight, smooth, and should not have concave and convex phenomena, so as not to affect the normal operation of the hammer pointer or cause measurement errors.

2. The ruler should be perpendicular to the liquid level in the storage tank, and there should be no inclination, and the verticality of the ruler installation should not be greater than 5°, so as not to cause the hammer pointer to be stuck and the measurement to fail.

3. When welding the ruler tripod, the installation surface should be on the same plane as far as possible, and the installation hole should be on the same straight line, that is, to ensure that the scale surface of the ruler and the guide on both sides of the hammer pointer should be straight and called a straight line, so that the hammer pointer can be flexibly lifted on the ruler.

3. Buoy level gauge guide wire installation

1. Straighten the steel wire with force and fix it on the lower support, pay attention not to bend or knot the steel wire, so as not to affect the buoy to move up and down.

2. The two guide wires should be perpendicular to the ground and parallel to each other, so as to ensure that the distance between the two is 300mm

3. The guide wire passes through the guide lug hook of the buoy, and then penetrates the hook screw, fixes the end of the wire and clamps it with a wire chuck, and tightens the hook nut to make it in a tense state, and then tightens the upper nut to prevent loosening, and then covers the cover.

Fourth, the buoy connection wire and hammer pointer installation

One end of the buoy and the connecting steel wire is clamped and fixed with a wire chuck, and then the other end of the connecting steel wire is loaded into two guide pulley boxes that are installed in advance, and is connected with the hammer pointer, clamped and fixed with a wire chuck, and finally adjusts each guide pulley bracket to make the connecting steel wire and the horizontal vertical, so that the buoy moves flexibly on the guide wire, and there is a light slippery feeling, no stuck, twisted, knotted, rolled or damaged and other phenomena.
RKC Level Gauge – Four mounting methods for buoy level gauges

More on that
Specifications and models of RKC thermostats Specifications and models of RKC thermostats

CH102 (48×48×100mm) CH402 (48×96×100mm) CH902 (96×96×100mm) 1. RH400 size: 48*96, depth 60, about 250g 1. Thermocouples: K, J, R, S, B, E, N, T, W5RE/W6RE, PL‖, U, L ...

What should I pay attention to when wiring the RKG thermostat? What should I pay attention to when wiring the RKG thermostat?

1. For thermocouple input, the corresponding compensation wire should be used. 2. For RTD input, 3 wires with low resistance and no difference should be used 3. The input signal line should be far away from the power line of the instrument. Power supply and load lines to avoid noise interference 4. The instrument power cord is usually ...

Initialization parameter setting of the rkc thermostat Initialization parameter setting of the rkc thermostat

1. Press the ISET) button for 2 seconds to enter the parameter setting mode, press ISET until "LCK" is displayed, press the [] key to move the cursor to the thousands, and press the [] button to change the number of thousands from "0" to "1" to display "1000" to unlock. 2. Press the ISET button for 3 seconds to return to SV/PV display mode 3. Press [SET]+ ...

A few things to note about the installation of the RKC thermostat A few things to note about the installation of the RKC thermostat

1) For RTD input, 3 wires with low resistance and no difference should be used. 2) The input signal line should be far away from the power line of the instrument, the power supply line and the load line to avoid noise and annoyance. 3) The power cord of the instrument is generally annoyed by the power supply. 4) Instrument complement ...

RKG thermostat - an introduction to the characteristics of digital displays RKG thermostat - an introduction to the characteristics of digital displays

1) It is a display of the common cathode. It uses the principle of the positive electrode as the segmented input, with the ground wire as the common output, and the segmented input is valid as a high-level input. 2) It is a display with a common anode. It uses an anode as an aggregate input, and in contrast to the common cathode, the segment is effective at a low level output ...

How to set the parameters of the RKG thermostat - intelligent digital display controller? How to set the parameters of the RKG thermostat - intelligent digital display controller?

1. First of all, the digital display should be installed on the cabinet, so the overall coordination should be considered, too large may not fit, too small to see the display numbers. 2. In addition, the large size of the instrument is generally more expandable, the same function price may be expensive, the small size of the instrument may be ...

RLC thermostat - a classification introduction of floor heating thermostats RLC thermostat - a classification introduction of floor heating thermostats

Floor heating thermostats can be divided into digital thermostats and analog thermostats according to different input and output forms. Digital thermostats generally have liquid crystal display or digital tube display panels, and set and control the temperature through buttons, while analog thermostats generally use knobs or slider band wave wheels to set ...

Common faults and solutions of RKC temperature controllers Common faults and solutions of RKC temperature controllers

1. The power indication is normal, but the temperature controller has no screen display. Most of this fault is caused by the heating of the voltage regulator element (7805 or 7812) on the thermostat during long-term use, which leads to the breakpoint of the solder joint, and sometimes it is caused by the phenomenon of virtual soldering at the factory, and the main re-soldering can be done. 2. Temperature controller ...

RKC converters – what are the functions of converters? RKC converters – what are the functions of converters?

1. Power conversion: convert the voltage (rated 100V) and current (rated 5A or 1A) of the transformer into voltage (several volts) to meet the requirements of weak current components. 2. Isolation: current, secondary side security, and work grounding are used to ensure the safety of people and equipment, while weak current ...

RLC thermostat – the wiring method of the thermostat RLC thermostat – the wiring method of the thermostat

Many household appliances and large-scale equipment products will be installed in the use of thermostats, thermostats will be combined with the change of ambient temperature in the switch when working physical deformation, which will produce some special effects, resulting in conduction or disconnection action, in order to achieve automatic ...

Wiring method of the RKG thermostat Wiring method of the RKG thermostat

Take CD901 as an example, L(1) pin to 220 volt live wire, N(2) pin 220 volt neutral wire, 3,4 pins for the first output, 5,6 pins for the second output, 7, 8, 9 pins are alarm output, Finally, the three pins are connected to thermocouples or PT100 ...

RLC Thermostat - Fault and Troubleshooting of Vapor Pressure Temperature Controller RLC Thermostat - Fault and Troubleshooting of Vapor Pressure Temperature Controller

Faulting and troubleshooting of vapor pressure temperature controllers (1) Common faults and common faults of the vapor pressure type temperature controller include contact burning or adhesion, failure of the mechanical transmission mechanism and leakage of temperature sensor in the temperature sensing tube. Its detection method is: put the thermostat knob in a parking position, and use ...

How to set the parameters of RKC thermostat RH900 How to set the parameters of RKC thermostat RH900

1. Lower limit deviation alarm setting: press the SET key to select and display "SLP", the green display screen displays the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. This parameter indicates the difference between the alarm point and the master setpoint. 2. The upper limit deviation alarm is set ...

For some considerations in the RKG thermostat setup For some considerations in the RKG thermostat setup

RKC Thermostat Operation Note: 1. Clean the instrument only after the power is off; 2. To remove the stains on the monitor, please use a soft cloth or cotton paper; 3. The display is easy to be scratched, and it is forbidden to use hard objects to operate the panel buttons, otherwise the buttons will be damaged or scratched. RLC thermostat ...

RKC thermostat - what are the anti-interference measures of the instrument? RKC thermostat - what are the anti-interference measures of the instrument?

1. Electromagnetic induction (refers to the coupling of magnetism). There is a strong alternating magnetic field in the surrounding space of high-power transformers, AC motors, high-current power grids, etc., and the closed loop formed by the lines of the control system (detection, transmission, conversion, regulation, calculation, execution, auxiliary, display, etc.) is located in the ...

Introduction and wiring method of Japan physical and chemical RKC thermostat Introduction and wiring method of Japan physical and chemical RKC thermostat

  The core control algorithm of the temperature regulator is PID control, P (Proportional) ratio + I (Integral) point + D (Differential) differential control. In addition to the traditional PID control algorithm, RKC also has ON-OFF control, custom parameter control, adaptive parameter control and other algorithms, ...

Key features of the RLC thermostat: Key features of the RLC thermostat:

Thermocouples, RTDs, analog and other signals are freely inputted, and the range can be set freely; The software zeros the full degree, the cold end measures the temperature separately, the amplifier is self-stabilizing, and the display accuracy is better than 0.5%FS; Fuzzy theory combined with traditional PD method, fast and stable control, advanced tuning ...

RRKC Thermostat – The working principle and main features of the pop-up thermostat RRKC Thermostat – The working principle and main features of the pop-up thermostat

How it works The sudden jump thermostat is a kind of bimetal disc after constant temperature as a heat-sensitive reaction component, when the temperature of the main part of the product increases or decreases, the heat generated is transferred to the bimetal disc, and when the operating temperature is set, it acts quickly, and the contact is broken through the action of the mechanism.

Analysis of common fault causes of RKC temperature controller Analysis of common fault causes of RKC temperature controller

1. The power indication is normal, but the temperature controller has no screen display. Most of this fault is caused by the heating of the voltage regulator element (7805 or 7812) on the thermostat during long-term use, which causes the solder joint to show a breakpoint, and sometimes it is caused by the phenomenon of virtual soldering at the factory. 2. Temperature controller ...

RKC thermostat - how to set the PID of the thermostat? RKC thermostat - how to set the PID of the thermostat?

1. Setup (XMT201-D): Press the SET button for 3 seconds to enter the inner parameter setting state. E: This parameter is the advance of heating stop when P = 0, when P is not equal to 0, the instrument is the intelligent PID working mode, and when P is not equal to 0, the E parameter is meaningless. 2.P: is the proportional band, that is, the proportional ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top