1. The power-on trip or the main power terminal part of the inverter shows sparks.

Disconnect the power cord, check whether the input terminal of the inverter is short-circuited, and check whether the DC side terminals P and N of the central circuit of the inverter are short-circuited. Perhaps the cause is a damaged rectifier or a short circuit in the central circuit.

2. There is no manifestation when the power is on

Disconnect the power cord, check whether the power supply has a phase loss or open circuit condition, if the power supply is normal, then check whether there is a voltage in the DC side terminals P and N of the central circuit of the inverter, and if the above check is normal, the internal switching power supply of the inverter is damaged.

                            Inverter phenomenon detection method and judgment - Senlan

3. No output when the machine is turned on (the motor does not start)

Disconnect the output motor line, turn on the inverter again, investigate the input frequency displayed on the inverter panel, and measure the AC output terminal together. Perhaps the reason is that the inverter is set in the operating parameters or the terminal wiring is incorrect, or the inverter is partially damaged or the motor is not properly connected to the inverter.

4. "Overvoltage" maintenance during operation, the inverter stops output

Check to see if the grid voltage is too high, or if the motor load inertia is too high and the acceleration and deceleration time is too short for braking problems

More on that
Common brand inverter modification power method - Senlan inverter Common brand inverter modification power method - Senlan inverter

What are the advantages of inverter power correction? Many brands of inverter power boards, driver boards, and motherboards can be universal, as long as the type, volume, and hardware are the same, and the desired power and voltage value can be obtained by correcting the manufacturer's parameters. ...

Senlan inverter selection points Senlan inverter selection points

1. Select the inverter according to the load characteristics, such as the load is constant torque load, you can choose Siemens MM440 inverter, ABB ACS800 series inverter, etc.; If the load is a fan or pump load, you can choose Siemens MM430 inverter, ABB ACS510 series inverter, etc. 2、 ...

Common maintenance methods of inverter - Senlan inverter Common maintenance methods of inverter - Senlan inverter

1. Step-by-step decreasing method The so-called gradual reduction method is to gradually reduce the scale of the problem through the analysis of the problem phenomenon and the identification of measurement parameters, and finally implement it to the specific circuit or component that causes the problem. In essence, it is a certainty, a negation, a negation, a negation, a final ...

PLC control belt conveyor soft start method PLC control belt conveyor soft start method

Belt conveyor is a kind of continuous conveyor, which is one of the main types of fixed or escorted cranes. Belt conveyor is the use of friction to convey the dynamic, with belts, steel belts, steel fiber belts and chemical fiber belts as a kind of compliance with the transmission of materials and traction operations.

The output side of the inverter is equipped with a contactor - Sunland inverter The output side of the inverter is equipped with a contactor - Sunland inverter

When the power supply and the inverter are replaced, for example, if the inverter has a problem, in order to make an emergency, let the motor be directly changed to be driven by the power frequency power supply; Perhaps the inverter is used for soft starting, and after the motor is accelerated to the power frequency speed, it is changed to be driven by the power frequency power supply. ...

Sunland inverter helps the green development of non-ferrous metal mining Sunland inverter helps the green development of non-ferrous metal mining

From October 28th to 29th, the "First National Tailings Engineering and Comprehensive Utilization Skills Seminar" sponsored by the China Nonferrous Metals Society was successfully held in Dexing City, Jiangxi Province. From China Nonferrous Metals Society, China ENFI, Jiangxi Copper, Beijing Institute of Mining and Metallurgy, University of Science and Technology Beijing and other countries...

The reason for VFD trip protection - Senlan The reason for VFD trip protection - Senlan

In general, there is a problem with the maintenance trip of the VFD. If you look at the faulty code, you can see what kind of fault is causing it. 1. The selection talent of VFD may be too small; Generally, when selecting VFD, it should be about 20% larger than the rated power of the motor, so that when the motor reaches full load...

Sunland inverter does not show fault repair Sunland inverter does not show fault repair

After inspection, the circuit board of the machine is composed of a fan switching power supply board, a control board with a switching power supply and a driving board, etc., the fan power supply and the control board operation power supply are independent of each other, the fan power supply output is normal, and the control board operation power supply is not output due to the problem. ...

Inverter overcurrent treatment method - Senlan inverter Inverter overcurrent treatment method - Senlan inverter

Overcurrent or overload of the inverter is a common problem of the inverter, and overcurrent refers to the value of the current flowing through the inverter beyond its additional range. 1. If the power supply of the inverter is out of phase, the circuit at the output end is disconnected or the motor winding ...

Precautions for starting electrical equipment after a long holiday - Senlan Precautions for starting electrical equipment after a long holiday - Senlan

1. Do a good job of moisture-proof operations, clean up water and oil stains on site, insist on the boring environment of electrical equipment, and pay attention to preventing the inverter from being exposed. 2. Do a good job of maintenance and maintenance, take advantage of the shutdown for maintenance, clean the frequency conversion dust, and clean the frequency conversion air duct; Tighten the frequency conversion cable joint to prevent loosening, ...

Precautions for the selection of exhaust fan inverter - Senlan Precautions for the selection of exhaust fan inverter - Senlan

1. Whether it has perfect maintenance function There will be many problems in the production process of the equipment, and if you want to prevent accidents, the equipment must have a perfect maintenance function, so as to prevent the loss of the enterprise. Therefore, when buying an exhaust fan inverter, you need to understand the safety function of the equipment first.

Causes and solutions of inverter skipping current faults - Senlan Causes and solutions of inverter skipping current faults - Senlan

1. There is a short circuit to the ground in the output circuit of the inverter, you can check whether the wiring is correct and troubleshoot 2. If the motor parameters are incorrect, you can check the parameter settings and identify the parameters 3. The acceleration time is too short, and the acceleration time can be increased.

Hope Sunland inverter introduction and common models Hope Sunland inverter introduction and common models

It is hoped that Sunland inverter is mainly used in three-phase asynchronous AC motor to control and adjust the motor speed. Sunland inverter is mainly composed of microprocessor, including rectification, filtering, inverter, brake, drive, detection, etc. In order to achieve the purpose of changing the power supply voltage, according to the actual needs of the motor...

Hope Sunland inverter fault code Hope Sunland inverter fault code

Hope Sunland inverter part of the fault code Er.ocb (1) Overcurrent at the moment of starting: There is a short circuit inside the motor There is a short circuit in the motor wiring The starting voltage is too high Check the motor and wiring Check the motor wiring Seek service Check the torque ...

The inverter is regularly replaced with the device - Sunland inverter The inverter is regularly replaced with the device - Sunland inverter

1. Cooling fan As a prerequisite for ensuring the normal operation of the inverter, efficient and fast in-line cooling fans have become an indispensable conversion configuration of the inverter. Because of the wear of the internal bearings of the cooling fan and the reduction of the grease function in the process of application, the cooling of the fan.

Effect of inrush current on inverter - Senlan Effect of inrush current on inverter - Senlan

In the process of repairing the inverter, we can find that because of the back electromotive force in the stator winding, the electromotive force in the synchronous generator state and the self-induced electromotive force in the self-loop rotor, the current impact will inevitably have a negative impact on the motor, the inverter (Variable-frequency ...

Introduction to the inverter maintenance and energizing test - Senlan Introduction to the inverter maintenance and energizing test - Senlan

First, the inverter is not repaired and the power test is tested (1) Inverter repair test rectifier circuit At the two ends of the inverter to detect the internal DC power supply, P and N ends, adjust the multimeter to the resistance RX10 gear, the red watch pen is connected to the P end, and the black watch pen is connected to R, S, T in turn.

Solve the inverter fault method - Sunland inverter Solve the inverter fault method - Sunland inverter

Motherboard faults are often manifested as faults that are difficult to visually identify, such as system startup failure and screen invisibility. You can use a brush to gently brush off the dust on the motherboard, in addition, some plug-in cards and chips on the motherboard are in the form of plugs.

The difference between soft starter and inverter - Sunland inverter The difference between soft starter and inverter - Sunland inverter

Soft starter is actually a motor control device with motor soft start, soft stop, light load energy saving and a variety of maintenance functions. First of all, it is a three-opposite parallel thyristor and its electronic control circuit connected in series between the power supply and the controlled motor. By manipulating the conduction of three opposite parallel thyristors ...

The method of selecting the appropriate peripheral equipment for the inverter - Senland The method of selecting the appropriate peripheral equipment for the inverter - Senland

When we have selected a suitable Variable-frequency Drive (VFD), we also need to consider whether we need to equip other peripheral equipment according to the actual situation of the site. The peripheral equipment selected by VFD mainly includes circuit breakers, reactors, contactors, braking resistors, etc. ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top