In power distribution equipment such as voltage distribution cabinets and switchgear at all levels of power plants and substations, the conductors connected between large electrical equipment such as generators and transformers and various electrical equipment are called busbars. Busbars, also known as busbars, are used to gather, distribute, and transmit electrical energy. There are two kinds of bus connection mode of bus connection and double bus connection, and today Shanxi power distribution cabinet manufacturer Jin Taiheng will tell you about the advantages and disadvantages of single bus connection.
Single bus wiring can be divided into two types: single bus unsegmented and single bus segmentation.
1. The single bus is not segmented wiring.
When there is only one power incoming line, this kind of wiring is commonly used, as shown in Figure 1 (a) each incoming and outgoing line is equipped with a blocking switch and circuit breaker. The barrier switch close to the line is called the line barrier switch, and the barrier switch close to the bus is called the bus barrier switch.
Advantages: simple and clear wiring, less equipment, good economy. Due to the simple wiring, the possibility of misoperation by the control cabinet operator is reduced.
Defects: Poor reliability and flexibility. When the power line, bus or bus barrier switch has a problem or is repaired, the power supply of all users is suspended.
Scope of application: It can be used for tertiary load users with small capacity and low power supply liaison requirements, or secondary load users with backup power supply.
Single bus wiring
2. Single-bus segmented wiring.
When there is a dual power supply, a single bus segment wiring is often selected, as shown in Figure 1(b), a barrier switch or circuit breaker segment can be selected. The single-bus segmented wiring can be operated separately or side by side.
When the segmented operation is selected, each section is equivalent to the operation of the single bus without segmented wiring, and the electrical system of each section of the bus does not affect each other. When any section of the bus has a problem or maintenance, only the power supply of the load on the section of the bus will be stopped. When any power supply line is faulty or overhauled, if the other power supply can bear the load of all the lead wires, the power supply of the load carried by the bus can be restored through the "reverse operation", otherwise the load carried by the power supply should still stop running or partially stop running.
If the power supply is overhauled when running side-by-side, there is no need for the bus to cut off, just disconnect the circuit breaker and blocking switch of the power supply and adjust the load of the other power supply. However, when the bus is faulty or overhauled, it will cause a short-term power outage of the normal bus.
Due to the inconvenience of the reverse operation, the barrier switch section is no longer selected, and the single bus wiring of the circuit breaker section is generally selected. When there is a problem with a section of the bus in the switch cabinet, the segmented circuit breaker and the power supply do not affect the normal operation of the other section of the bus.
Advantages: high reliability of power supply, flexible operation (only refers to the single bus wiring with circuit breaker segments), except for bus faults or maintenance, continuous power supply to users.
Defects: When the bus is faulty or overhauled, about 50% of users will have a power outage.
Scope of application: When there are two power supply lines, the single bus segmented wiring is selected, which can supply power to the primary and secondary loads, especially after the standby power supply is installed and actively put into the equipment, the power supply reliability of the single bus wiring with circuit breaker segmentation is further improved. Load symmetry and overall balance (this is used in most coal mine switchgears and distribution cabinets).
When choosing the connection mode of the switch cabinet bus, it is necessary to fully consider its advantages and disadvantages, and use different bus wiring methods under the condition that it is sufficient to meet the application.
|
More on that
|
The advantage of busway over cable in construction - Wienal
Modern power supply lines play a very important role like the aorta of the human body, and if something goes wrong, it can have serious consequences. Before the 80s of the 20th century, many stable cables were used in modern construction. With the rapid development of the city, the power load of the building ...
|
|
Advantages and disadvantages of bus full differential protection
Thorough differential maintenance of the bus is to connect the current transformer of all the connecting elements on the bus to the differential circuit according to the same name phase and polarity, the characteristics and transformation ratio of the current transformer should be the same, if the transformation ratio can not be together, the compensation converter can be used to compensate, satisfactory ΣI=0.
...
|
|
Knowledge points of Wiener busway
Busway was born in the United States, first put into practical use in Japan, and then spread all over the mountains and regions in prosperous countries and regions. So what is a busway? Busway is a high-current trunk tappable power supply system, usually made of a metal housing (iron or aluminum).
|
|
Busbar system reverse operation – Wiener
(1) For the charging of the spare bus, when there is a bus tie circuit breaker, the bus tie circuit breaker should be used to charge the spare bus. At this moment, the maintenance device of the bus tie circuit breaker should be fully invested, and the relevant maintenance value and time limit should be changed to a smaller one, so as to facilitate the bus tie circuit breaker when there is a problem, the bus tie circuit breaker can quickly trip, cut ...
|
|
Closed busway essentials – Wiener
Before the closed busway device, it should be ensured that the electrical shaft, the transformer and distribution room, the decoration project of the place through which the busway passes, and the heating and ventilation project are all completed to ensure that the closed busway is not polluted. The reserved holes and embedded parts of the floor and wall should be embedded and reserved according to the position required by the design.
...
|
|
Precautions for the installation of explosion-proof distribution boxes - Vernal
The protection level mark of explosion-proof distribution box is the protection level of IP products that we often mention, which has two parameters, one represents the level of avoiding foreign objects from entering the shell, and the second represents the level of waterproof entering the shell.
Installation of explosion-proof ...
|
|
A detailed description of the Wiener comb busbar and connection terminals
The Wiener comb busbars and connection terminals are available with QUADRON®CrossLinkBreaker in size 000/00
Recommended installation: Wire entry at the lower end of the NH-fuse disconnector through the comb busbar.
In the installation position and ...
|
|
The technology of the main bus bar in the low-voltage open light cabinet - Winer
One of the characteristics of the Wiener low-voltage switchgear is the multi-functional busbar system. The bus bar is a conductor that connects large electrical equipment such as generators and transformers with various electrical devices. The role of the bus bar is to transmit electric energy with the, and the bus bar is the main equipment constituting the electrical wiring. ...
|
|
185Power - The solution for the 185mm busbar system
Since the launch of the 185Power system in 2014, Wiener has continued to develop new connection technologies and fuse-type disconnector technologies for the 185Power system on the basis of the 185mm bus technology.
In addition to the application of 1600A below ...
|
|
The difference between air-type busway and dense busway - Vernal
1. The insulating medium is different: there is a certain open space between the copper bars of the air bus duct, that is to say, the insulation between the copper bars mainly depends on air, and the insulation medium between the copper bars of the dense bus duct (many people call it a closed bus duct) is an organic insulating material.
2. Copper bar placement ...
|
|
Difference Between Busbar and Busway – Vernal
The connection of voltage distribution devices at all levels in the substation, as well as the connection of electrical equipment such as transformers and corresponding distribution devices, mostly use bare wires or stranded wires of rectangular or circular cross-section, which are collectively referred to as busbars.
The role of the bus bar is to collect, distribute and transmit electrical energy. Because the busbar ...
|
|
Fuse selection method - Wiener busbar
1. Select the model of the fuse according to the circuit requirements and device conditions. Circuits with small capacity are semi-enclosed or enclosed without fillers; The selection of large short-circuit current has a packing closed type; Semiconductor component maintenance selection of quick fuses.
...
|
|
Busbar system reverse operation – Wiener
(1) For the charging of the spare bus, when there is a bus tie circuit breaker, the bus tie circuit breaker should be used to charge the spare bus. At this time, the maintenance device of the bus tie circuit breaker should be fully invested, and the relevant maintenance value and time limit should be changed to a small size, so that when there is a problem with the bus, the bus tie circuit breaker can be quickly tripped, cut off...
|
|
220V DC Hazard in Busbar System – Wiener
The grounding of the DC system should include two conditions: the one-point grounding of the DC system and the two-point grounding of the DC system.
In the DC system, the positive and negative poles of DC are insulated from the ground, and they do not cause any harm when generating a ground current because there is no path to constitute a grounding current, but the ground of one pole is long.
|
|
Strip Switch vs. Disconnector Circuit Breaker Comparison – Wiener
Bar switches are different from regular switches. They are critical to ensuring effectiveness. For example, when the current exceeds a certain amount of time, they cause heat to be generated, allowing the fuse to switch the fuse to further assist in breaking the circuit. Therefore, as a kind of current protection device, they can achieve ...
|
|
A brief introduction to the classification of busway - Wiener
Busway (referred to as busway) is a busbar system composed of metal plates (steel plates or aluminum plates) to protect the shell, conductive bars, insulating materials and related accessories. It can be made into a plug-in closed bus with plug-in junction boxes at intervals, or as a feed-in type without a junction box in the center ...
|
|
Wiener bearing repair technology
1. Comprehensive correction of bearings
The comprehensive correction of the bearing includes the comprehensive and strict correction process of the damaged bearing after cleaning, dismantling, inspection, roller table grinding or replacement of inner and outer rings, new rolling element manufacturing/original rolling element grinding, rolling element replacement, assembly, clearance adjustment and inspection and packaging.
|
|
The main components of the Wiener bus system in the distribution cabinet are composed
(1) Busbar
It is the basic element of the bus system, and there are a variety of standards, which can be installed with 5mm or 10mm thick rectangular busbar, double T type and triple T type busbar. The busbar is divided into 1-4 wires, 1 wire can be used with N or PE, 2 wires can be used together with N and PE, 3 wires are two-phase, and 4 wires can be used for three-phase ...
|
|
Analysis of the conditions for the use of sealed busbars - Wienal
Ambient air temperature: turn off the busbar system to benchmark the ambient air temperature; Unless otherwise ruled, the manufacturer should give an additional current to shut down the busbar system at a base ambient air temperature of 35°C; If applicable, the manufacturer should give an additional coefficient k: (K1=1 at 35°C) in order to determine the size of the package.
|
|
Wiener busbar system PT disconnection treatment
The judgment of PT three-phase voltage loss (symmetrical disconnection) is fundamentally the same for each manufacturer, and it is judged according to the three-phase no voltage and the current of the line. The same is true for PT asymmetrical wire breakage. After analyzing the characteristics of PT wire breaking, the specific judgment of PT asymmetric wire breaking of different manufacturers ...
|
|