Before the closed busway device, it should be ensured that the electrical shaft, the transformer and distribution room, the decoration project of the place through which the busway passes, and the heating and ventilation project are all completed to ensure that the closed busway is not polluted. The reserved holes and embedded parts of the floor and wall should be embedded and reserved according to the position required by the design.
It is necessary to clean the surface of the copper bar on the connecting parts and movable joints of the functional units of the closed busway, and the shell and before the insulator device should also be wiped clean and there should be no residue.
The interphase short-circuit plate of the shell should be correctly connected outstanding, the interphase support plate should be strong, the shell of segmented insulation should be insulated, the torsion bolts of each joint part of the shell should be fastened with force distance wrench, the contact surface should be closed, and the fasteners of the bus duct must be hot-dip galvanized.
The bus duct and the shell should be concentric, and the error shall not exceed 5mm, and the bus duct section and the bus duct section should be aligned with the bus duct shell when the two adjacent sections of the bus duct section are connected, and the bus duct and the bus duct shell shall not be subjected to mechanical stress after the connection.
It is necessary to do an insulation test before the whole device of the closed bus duct, and use a 1000V megohmmeter to measure the insulation resistance between phases, between phase shells, and each functional unit, and its insulation resistance shall not be less than 20MΩ. The installation personnel should carefully check the specifications and models of all bus ducts against the closed bus duct system diagram to prevent blind installation, resulting in rework and affecting the quality of the construction device.
|
More on that
|
Busway installation method - Wiener
1. Busway horizontal device, the interval between the two brackets is ≯2500mm, and the interval between straight devices is ≯3600mm;
2. When the device bracket is straight, it should be drilled with the channel side plate and fastened with M6-M8 bolts.
3. In the process of installation construction, priority should be given to the power supply system, ...
|
|
Analysis of the conditions for the use of sealed busbars - Wienal
Ambient air temperature: turn off the busbar system to benchmark the ambient air temperature; Unless otherwise ruled, the manufacturer should give an additional current to shut down the busbar system at a base ambient air temperature of 35°C; If applicable, the manufacturer should give an additional coefficient k: (K1=1 at 35°C) in order to determine the size of the package.
|
|
Conductor and bus welding requirements - Wiener
1. Before welding, it is necessary to check whether the welding equipment is defective, whether the grounding of the electrical equipment is reliable, and strictly abide by the "welder safety operation procedures" when welding.
2. Correct wires and busbars, and prohibit the use of handleless files.
...
|
|
What is the Wiener bus system
The Wiener bus system is a standardized system for bus spacing, which is used in low-voltage power supply and distribution switchgear, so that the bus can both conduct electricity and support electrical components. The system is divided into 40, 60, 100 and 185mm systems.
...
|
|
Wiener bus differential protection switching operation
1. Whether the scale of bus differential maintenance is determined, and whether the maintenance goal is unchanged
Generally, differential maintenance includes bus differential maintenance, transformer differential maintenance, generator differential maintenance and line differential maintenance. The basic principle of achieving differential maintenance is common, i.e. on all sides or on each side...
|
|
Introduction to busbars in Wiener's electrical system
The bus bar is an intermediate link in the voltage distribution device at all levels, and its role is to gather, distribute and transmit electric energy. It is mainly used for the connection of the electrical main circuit between the power plant generator outlet line and the main transformer, the plant transformer and the distribution box, also known as the busbar.
...
|
|
The advantages of low-voltage closed busbar system without punching connections
1. Save space. The components are attached to the busbar, which can save 1/3 of the size of the box transformer.
2. Operation**. The busbars are placed behind the components, and the upper and lower plates can be sealed to prevent touch protection.
3. Improve the stability and reliability of operation, improve the dynamic and thermal stability, and the bus bar is not perforated.
|
|
Busbar system in detail – Vernal
1. In the 60mm bus system, the square fuse type blocking switch can be directly hooked.
2. The 60mm bus system refers to the three-wire or four-wire bus spacing of 60mm.
3. Strip NH-fuse type load barrier switch with scale 00 ...
|
|
Wiener bearing repair technology
1. Comprehensive correction of bearings
The comprehensive correction of the bearing includes the comprehensive and strict correction process of the damaged bearing after cleaning, dismantling, inspection, roller table grinding or replacement of inner and outer rings, new rolling element manufacturing/original rolling element grinding, rolling element replacement, assembly, clearance adjustment and inspection and packaging.
|
|
Wiener Data Center Bus System
Although the service life cost of the busbar system is usually lower than that of the traditional wiring method, the busbar system still bears a considerable cost compared to other structural elements of the water supply and drainage or HVAC system.
In addition, customized busbars ...
|
|
220V DC Hazard of Bus System – Wiener
The grounding of the DC system should include two situations: the one-point grounding of the DC system and the two-point grounding of the DC system.
In the DC system, the positive and negative poles of the DC are insulated from the ground, and when the ground of one pole is generated, there is no grounding current due to the fact that there is no grounding current.
|
|
How to choose the right fuse - Wiener
1. Select the type of fuse according to the line requirements and installation conditions. Circuits with small capacity are semi-enclosed or enclosed without fillers; The selection of large short-circuit current has a packing closed type; Semiconductor component maintenance selection of quick fuses.
...
|
|
Wiener looks at the busway drawing method
First, in the CAD system drawing, it is a plan of the bus duct, and two parallel polylines can indicate the bus duct.
2. The busway includes the following parts:
1. Feeder busbar, which is used to transmit electricity
2. Plug-in busbar with plug-in interface above, ...
|
|
Power system bus wiring features - Wiener
1) Single bus wiring. Single bus wiring has the advantages of simple and clear, less equipment, small investment, convenient operation and conducive to expansion, but the reliability and flexibility are poor. When there is a fault or maintenance of the bus bar or bus barrier switch, the full power supply of the bus must be disconnected.
...
|
|
Characteristics of power system bus wiring mode
(1) Single bus wiring. Single bus wiring has the advantages of simple and clear, less equipment, less investment, convenient operation and expansion, but its reliability and activity are poor. When the bus or bus divider is faulty or overhauled, it is necessary to disconnect all power to the bus.
...
|
|
NH-Fuse Type Disconnector Instructions for Use
When switching on and off components, you should pay attention to the following:
–In accordance with VDE-0105-100, only operation by electrical professionals or persons with electrical knowledge is allowed (operation without electricity, closing, disconnecting, and replacing fuses ...).
|
|
Busway installation method - Wiener
1. Busway horizontal device, the interval between the two brackets is ≯2500mm, and the interval between straight devices is ≯3600mm;
2. When the device bracket is straight, it should be drilled with the channel side plate and fastened with M6-M8 bolts.
3. In the process of installation construction, priority should be given to the power supply system, ...
|
|
Precautions for installation of Wiener busway
1. Before the bus duct installation, it should be ensured that the electrical shaft, substation and distribution room, the decoration project of the place through which the bus duct passes, and the heating and ventilation project are all completed to ensure that the bus duct is not polluted. The reserved holes and embedded parts of the floor and wall should be embedded and reserved according to the position required by the design. The functions of the busway are single ...
|
|
Laminated busbar system – Wiener
In the power system, the bus connects the various current-carrying branch circuits in the power distribution device together, and plays the role of collecting, distributing and transmitting electric energy; According to the appearance and structure, the bus bar is roughly divided into three categories: hard busbar, soft busbar and closed busbar.
...
|
|
Phase of the busway in the low-voltage incoming line – Wiener
According to the requirements of the relevant specifications, the placement of the three-phase busbar can be roughly divided into two kinds according to the model of the low-voltage distribution cabinet and the different manufacturers: horizontal placement and placement of the down wire, according to the order of placement.
|
|