1. The inverter should not be installed on the equipment with vibration, because the main circuit connection screw in the inverter is simply loose, and many inverters are damaged due to this reason.
Second, the wiring problem: the input terminal of the inverter is connected to an air and the initial maintenance current should not be too large, so as to avoid the incineration of a short circuit will not be too severe. The "N" terminus must not be grounded. Try not to be too long with the control line. Because the control board is simply disturbed by electromagnetic waves and malfunctions, it will also cause damage to the control board, and it is best to use shielded wires beyond 2 meters long. Do not be equipped with a contactor with high current and often action next to the inverter, because it disturbs the inverter very much, and often makes the inverter malfunction (showing various faults).
3. The inverter that often needs to park in an emergency should not rely on the inverter to brake itself, but add a braking unit or use mechanical brakes, otherwise the inverter is often impacted by the motor back electromotive force, and the fault rate will be greatly improved.
Fourth, if the inverter often runs at a low speed of 15Hz; Below, the motor should be equipped with a cooling fan!
Fifth, dust and moisture are the deadly killers of inverters. It is best to install the inverter in an air-conditioned room, or in an electric cabinet with a dust net, and clean the dust on the circuit board and radiator on time; If the inverter has been shut down for a period of time, it is best to blow the circuit board with a hair dryer before powering on.
6. When the heat dissipation fan is broken, it will announce overheating maintenance, and it should be replaced when the fan has a sound.
7. Some factories are powered by generators, the voltage is unstable, the inverter is often damaged, and the generator is equipped with voltage stabilization or overvoltage maintenance devices, which plays a very good role.
8. Lightning protection is also very important. Although it is rarely generated, when the drive is struck by lightning, it will be very damaged. The inverter with constant pressure water supply is the easiest to be struck by lightning because it has a lightning pipe that extends into the sky.
9. In order to avoid electromagnetic wave disturbance, the input, output and control line of the inverter should be shielded wire, and the wiring method of the shield layer can not be wrong, otherwise the effect is opposite, and it is possible to cover it with an iron pipe, install a filter, and reduce the carrier frequency. We found that if the switch tube of the inverter switching power supply is a field effect transistor, its disturbance will be greater.
10. When the inverter is broken, don't hand it over to someone who has no maintenance experience to repair it! Otherwise, it may get worse and worse the more you repair! Sometimes it is about to fuse, you must check if there is a problem, some electricians have not experienced, immediately install a good fast melt (absolutely can not be replaced by copper wire), the result is that the inverter incineration is more ferocious. According to our experience, if the module is fast melting, most of the modules have problems, but the modules are bad and fast melting. Many inverter power modules and rectifier modules are interchangeable.
|
More on that
|
Fault analysis of servo motors – LS power generation
1. Problem phenomenon: servo error OL, servo motor can not start, and there is abnormal sound problem analysis and possible causes:
(1) Bearing damage, foreign objects falling and stuck, stator magnet bursting and falling or moving tissue jamming caused by the motor itself.
(2) ...
|
|
Variable frequency regenerative braking method - LS generates electricity
1. Energy consumption type
This method is to connect a braking resistor in parallel in the DC circuit of the inverter, and control the on/off of a power tube by detecting the DC bus voltage. When the DC bus voltage rises to about 700V, the power tube is turned on, and the regenerative energy is passed into the resistor.
|
|
LS power production contactors are used in this area
LS contactors are divided into AC contactors (voltage AC) and DC contactors (voltage DC), which are used in electricity, power distribution and consumption. Contactor in a broad sense refers to the electrical appliances that use the current flowing through the coil to generate a magnetic field and close the contact to control the load in industrial electricity.
...
|
|
The role of LS electric contactors
1. It is often used in electric motors as control targets.
2. It is used to control power loads such as factory equipment, electric heaters, working machines and various power units.
3. It has the effect of low voltage release protection.
4. It is suitable for frequent operation and long-distance control, and is an automatic operation.
|
|
Introduction to electrical equipment - LS Electricity
According to the requirements of safe, high-quality, reliable and economical operation of the production, transforming, transportation, distribution and use of electric energy in power plants and substations, the following electrical equipment is mainly included.
1. Primary equipment
Directly involved in production, ...
|
|
The difference between inverter overload and overcurrent - LS generates electricity
Inverter is an important drive material in modern industrial production, as a power equipment, it is working hard all the time, so its fault rate is very high, and the rapid processing of inverter faults, to ensure the continuity of industrial production, is every maintenance electrician and on-site debugging of electricians.
|
|
The principle and function of the power production contactor
The working principle of the power production contact is: when the contact coil is energized, the coil current generates a magnetic field, and the generated magnetic field leads the static iron core to produce electromagnetic attraction to the iron core, and drives the AC contact action, the normally closed contact is disconnected, the normally open contact is closed, and the two are connected to each other. When the coil is de-energized, the electric ...
|
|
The working principle of the LS power production module
When the LS power generation module is put into operation, its working process is generally divided into three stages: input sampling, user program fulfillment, and output rewriting. The completion of these three phases is called a scan cycle. During the entire operation, the PLC's CPU repeatedly performs the upper ...
|
|
LS power inverter function
1. Soft up
The direct launch of the inverter motor has a serious impact on the power grid, and it will also have too high requirements for the capacity of the power grid, which is extremely unfavorable to the service life of equipment and power grid circuits. After the use of inverter to save energy, the use of inverter's speed regulation (V/F) function will make the starting current from a small ...
|
|
Specifications for the use of power converters
Operating regulations for power inverters
Maintenance & Installation
Work according to the weight of the product.
The number of inverter boxes cannot be stacked in excess of the specified number.
Install according to the user manual.
Do not open the case during transport.
Do not place ...
|
|
Introduction to the use of PLC for power production
1. It is used for switching control
The ability of PLC to manipulate switching quantities is very strong. The number of points in and out of the control, less than a dozen points, dozens of points, more can be hundreds, thousands, or even tens of thousands of points, because it can be networked, the number of points is almost unlimited, no matter how many points can be controlled, the control ...
|
|
The role of the inverter's braking resistor - LS generates electricity
1. Maintain the inverter from the damage of regenerative electricity
In the process of rapid shutdown of the motor, because of the inertia, a lot of regenerative electric energy will be generated, if this part of the regenerative electric energy is not consumed in time, it will directly act on the DC circuit part of the inverter.
|
|
Basic introduction to transistors - LS produces electricity
A transistor is a solid-state semiconductor device with a variety of functions such as detection, rectification, amplification, switching, voltage regulation, and signal modulation. A transistor is a variable current switch that can manipulate the output current based on the input voltage. Unlike general mechanical switches (e.g. Relay, swit...)
|
|
LS has reached agreements with Doosan and Hanwha in Korea on a business model for vacuum power generation
LS Electric recently signed an MOU agreement with Doosan Fuel Cell, Hanwha Power Systems, and Hanwha Asset Management in Seoul, Korea, to establish a business partnership for city gas companies to develop a fuel cell-vacuum power generation business model. Through this agreement, the two sides will expand the scope of cooperation ...
|
|
The cause of the broken shaft of the motor - LS generates electricity
1. Improper device:
The motor is not concentrious with the equipment being dragged, resulting in excessive radial load on the motor, which eventually leads to metal exhaustion. When the radial load on the extension end of the motor shaft is too large, it will cause the motor shaft to have zigzag deformation in the radial direction. When the motor rotates, the shaft's ...
|
|
Classification of the nature of DC power supply of inverter - LS power generation
A frequency converter is actually an inverter. It starts by turning alternating current into direct current. Then the direct current is switched on and off with electronic components. Becomes alternating current. Thyristors for general inverters with larger power. And set up a device with adjustable frequency. Make the frequency adjustable within a certain range. Used to control ...
|
|
The working principle of LS PLC module
When LS PLC is put into operation, its operation process is generally divided into three stages, namely input sampling, user program fulfillment and output rewriting. The completion of these three phases is called a scan cycle. Throughout the operation, the PLC's CPU repeatedly performs the performance at a certain scanning speed on ...
|
|
Introduction of LS AC motors
1. AC synchronous motor: that is, the rotor is composed of permanent magnet data, so after rolling, with the change of the stator rotation magnetic field of the motor, the rotor also changes the speed of the response frequency, and the rotor speed = stator speed, so it is called "synchronization".
...
|
|
Automatic adjustment of motor parameters - LS power generation
Step 1: If the motor can be completely separated from the load, in the case of a power failure, the motor is mechanically separated from the load, and the motor is allowed to rotate freely without load.
Step 2: After powering on, select the VFD command source (F0-04) as the command channel of the operation panel.
...
|
|
Interference phenomenon of LS power inverter
1. As soon as the inverter of the heat exchange station is opened, the pressure transmitter jumps randomly;
2. In the water supply controlled by the inverter, the pressure transformer is used as a signal to collect the pressure, and the pressure transformer is disturbed by the inverter;
3. When the inverter starts the motor, the voltage converter signal is unstable and beats violently;
4. Pressure transformer (4-20 ...
|
|