1. How to connect a PNP three-wire proximity switch to the input port of FX3U PLC.
Answer: The signal output termination of the PNP three-wire system near switch is connected to the input port of the PLC such as X0, the 0V end of the PNP type close switch to the 0V terminal on the PLC, and the S/S terminal is shorted with the 0V terminal, and the +24V end of the PNP type near switch is connected to the 24+ terminal on the PLC. If it is an external 24V power supply, then connect the signal output of the PNP three-wire system close switch to the input port of the PLC such as X0, the 0V end of the PNP type close switch to the negative of the external 24V power supply, and the S/S terminal and the negative short connection of the external 24V power supply, and the +24V end of the PNP type close switch to the positive of the external 24V power supply.
2. The scanning cycle of the PLC is fixed, so how do I know that the program I write exceeds the inherent scanning cycle, what is the way to know, and how to extend the scanning cycle?
A: If you want to know the current scan cycle, you can read it directly from the special register D8010 of the PLC; If there is a special memory in the PLC that can be used to set the stable scanning cycle, then it is necessary to set a specified value in this special memory to change the timing of the scanning cycle.
3. "MOV K0 K2Y0" means to reset Y0--Y7, so why does "MOV K1 K2Y0" not set Y0--Y7? And just a single Y0 set?
Answer: K2Y0 in the instruction is a combination of bit elements, representing Y0-Y7, MOV K0 K2Y0 instructions transmit 0 to K2Y0, the actual transmission is the binary number, the binary number of 0 is B 0000 0000, so it is to reset Y0-Y7, MOV K1 K2Y0 instruction is transmitted to 1 to K2Y0, the binary number of 1 is B 0000 0001, so it is set to 1 for Y0, not to set Y0-Y7.
4. Enter T1K20 in the ladder diagram to show what is going on with the incorrect setting of the soft components
Answer: If you enter T1K20 in the ladder diagram, it shows that the soft component settings are incorrect, because there is no space between T1 and K20, and the number of spaces is not specified, but at least 1 space is required. The correct input method is: OUT T1 K20, note that there should be a space between OUT and T1, T1 and K20, and be careful not to mix the letter O with the number 0 when entering the timer command.
5. For example, X001 controls T5, and the delay of T5 is 50S, does X001 need to be connected to 50S before T5 acts? Or is it just a matter of plugging it in?
Answer: X001 needs to be turned on for 50 seconds before T5 can operate. Because X001 is the driving condition of the timer, and T5 is a general-purpose timer, when the driving condition X001 is disconnected, the timer will reset and no longer time.
|
More on that
|
The inverter completes the multi-speed function - Mitsubishi
The inverter can be preset with a number of different speed points, and then complete the scheduling of multiple speed stages. The specific completion method is as follows:
You can set a number of different speed points in the VFD, and you can generally set the maximum speed, minimum speed, and several center speed points.
According to the needs, choose ...
|
|
Mitsubishi PLC ladder programming method
Ladder concept: It is a ladder pattern composed of graphical symbols that indicate the programming elements inside the PLC.
Rules for writing ladders:
Suitable for the left bus, finally the right bus
The contacts should be drawn on the horizontal line, not ...
|
|
PLC circuit debugging precautions - Mitsubishi
1. For the switching input and output circuits, pay attention to the consistency criterion of maintaining the state; The positive logic criterion is usually used, that is, when the input and output are live, it is in the "ON" state and the data value is "1"; Conversely, when the input and output are powered off, it is in the "OFF" state and the data value is "0". Such...
|
|
Pay attention to the problem when choosing an inverter - Mitsubishi Electric
The current value of the motor is used as the basis for the selection of the inverter, and the rated power of the motor is only for reference.
Compared with the general squirrel cage motor, the winding motor simply has the problem of overcurrent tripping, and the slightly larger capacity than the usual ...
|
|
Mitsubishi servo system common alarms and solutions
The use of Mitsubishi AC servo system is mainly composed of three series: MR-ES, MR-J2S, MR-J3. In general, the cause of the fault can be preliminarily determined based on the code displayed on the servo drive, and then troubleshooting:
1、AL. E6 - Indicates ...
|
|
Mitsubishi PLC selection 5 elements
Mitsubishi PLC selection - element 1: IO points
The number of ZUI IOs that can be accessed by the Mitsubishi PLC control system.
Mitsubishi PLC FX series now commonly used basic unit host is: FX1SFX1N, FX1NC, FX2N, FX2NC, FX3U. FX3UCFX3G, FX5U, 9 series.
...
|
|
Mitsubishi PLC set and reset command use example
1 SET Directive
The SET instruction is called an enthronement instruction. Its function is: to drive the coil, so that it has a self-locking function, and insists on the connection condition. In the diagram, when the moving contact X0 is closed, the SET command is executed to turn on the Y0 coil. After X0 is disconnected, the Y0 coil continues to insist on the ON condition, ...
|
|
Mitsubishi inverter fault detection method
1. The output side of the inverter is short-circuited, such as the connection line between the output end and the motor, or the short circuit inside the motor, etc.;
2. The inverter itself is not working properly, such as the two inverter equipment of the same bridge arm in the inverter bridge are constantly alternating in the working process ...
|
|
Mitsubishi PLC adjusts the built-in time
1. TWR (Time Write) command
Write the time preset value to the built-in real-time clock: Clock information is written to the TWR (Time Write) command. The sequence number of the action instruction is FNC167, [S ·] T, C and D can be used, and only 16-bit operations can be used, accounting for 5 program steps.
The work of the directive ...
|
|
Mitsubishi servo motor one-button adjustment function
In the MR Configurator2 servo commissioning software, Mitsubishi has developed a "one-button adjustment" function to solve the problem of rigid noise of servo motors, as follows:
1. Set PA08 to 0003 and adjust the gain to ...
|
|
Mitsubishi inverter overload fault judgment method
1. Check whether the three-phase electricity of the motor is balanced
(1) If the three-phase voltage of the motor is unbalanced, then check whether the three-phase voltage at the output end of the Mitsubishi inverter is balanced.
(2) If the three-phase voltage of the Mitsubishi inverter is also unbalanced, the problem is inside the Mitsubishi inverter, and it should be investigated.
|
|
What are the main factors of interference in Mitsubishi PLC system?
(1) Radiative dry disturbance from space
The radiated electromagnetic field (EMI) in space is mainly caused by power networks, transient processes of electrical equipment, lightning, radio broadcasting, television, radar, frequency induction heating equipment, etc., generally known as radiation disturbance, and its dispersion is extremely chaotic. ...
|
|
How does Mitsubishi PLC work?
1. A scanning cycle is divided into input sampling, program fulfillment, and output rewriting.
2. Each scan process. The convergence samples the input signal. The convergence rewrites the output signal.
3. The inner ...
|
|
Precautions for the use of Mitsubishi servo motor with brake
1. Occasions with brake servo motors:
The servo motor is mainly loaded by the motor shaft, assuming that the load driven by the motor shaft is vertical, after the whole control system is powered off, the load on the servo motor shaft will be driven to run down under the action of gravity, so that ...
|
|
The role of PLC power module - Mitsubishi
Internal memory programs, logic operations, sequential manipulation, punctuality, counting, arithmetic operations, and other programmable memories are used to manipulate a variety of machinery or production processes with digital or analog inputs/outputs. PLC-related peripherals should be easy to operate with industry to form a whole, easy to expand...
|
|
Manipulator Fault Repair - Mitsubishi Robot
1. Speak before you start
With regard to defective electrical equipment, it is necessary not to rush to start, but to inquire about the passage and defective phenomena that cause defects. For unfamiliar equipment, you should also understand the circuit principle and structural characteristics, and follow the corresponding rules. Before dismantling, it is necessary to fully understand each electrical department ...
|
|
Advantages of Mitsubishi inverter installation reactor
Features of the output reactor:
1. It is suitable for reactive power compensation and harmonic management
2. The primary effect of the output reactor is to compensate for the influence of long-line distributed capacitance, and output harmonic current according to the press; 3. Effectively maintain Mitsubishi inverters and improve the power factor, which can thwart the ...
|
|
Introduction of Mitsubishi PLC series
1. Main substrate
There are a variety of models such as Q32SB, Q33SB, Q35SB, Q33B, Q35B, Q38B, Q312B and other main substrates for Q series PLC, and the meaning of the model is as follows:
In the meantime, the "S" stands for ultra-thin main substrate, and only Q61SP power modules can be used, and they cannot be ...
|
|
Mitsubishi is a method for completing the modification of timer setting outside the PLC
In the process of using the PLC control system, it is often necessary to correct some parameters, and the most common is to correct the set value of the timer. In order to facilitate the operator to correct the set value of the timer, the following methods can be used:
1. The use of man-machine ...
|
|
Mitsubishi Electric instruction format
(1) Arbitrary axis AC command (G140)
G140 Instruction Address = Axis Address Instruction Address = Axis Address ... ;
Command Address: Arbitrary Axis AC Command (G140) After that, specify the 1-character address set by the parameter (#12071-#12078) to be used for moving commands, etc.
|
|