1. The purpose is to ensure the normal and safe operation of the low-voltage distribution cabinet and the control cabinet of each equipment.
Second, the scope is suitable for the low-voltage distribution room distribution cabinet, and the control cabinet of each equipment shall be implemented with reference to the relevant provisions according to the specific situation.
3. The maintenance team of the mechanical and electrical installation and maintenance engineering department shall conduct a comprehensive inspection and maintenance every six months, and complete the maintenance work with the shortest power outage time.
Fourth, content
1. Preparation:
A. Notify residents of the start and end time of power outage on the day before the power outage maintenance of the distribution cabinet.
B. Make all preparations before the power failure, especially the preparation of tools; And complete maintenance work with minimal power outage time.
2. Maintenance procedures:
A. Implement sectional maintenance, and first maintain the security load section.
B. Shut down the power supply of the security load, and supply the rest of the load to the mains as usual. Disconnect the air switch for the mains of the security load, disconnect the air switch of the development motor, put the generator selector switch in the stop position, disassemble the positive and negative pole wires of the battery, and hang signs to prevent the generator from sending electricity.
C. Check whether there is deformation at the bus joint, whether there are traces of blackening of discharge, tighten the connecting bolts, and replace the bolts if they are rusty to ensure that the joints are tightly connected. Check the insulation on the mother for looseness and damage.
D. Shake the total air out of the distribution cabinet with the handle, check whether the main contact has burn marks, check whether the arc extinguishing cover is burned black and damaged, tighten the wiring screws, clean the dust in the cabinet, and test the closing and opening of the machinery
E. Take out the sub-switch cabinet from the drawer cabinet and fasten the terminals. Check the installation and wiring of current transformers, ammeters, and watt-hour meters, check the flexibility and reliability of the handle operating mechanism, fasten the inlet and outlet wires of the air switch, and clean the dust in the switch cabinet and the outgoing wires behind the distribution cabinet.
F. WHEN MAINTAINING THE CAPACITOR CABINET, YOU SHOULD FIRST DISCONNECT THE CAPACITOR MAIN SWITCH, DISCHARGE THE CAPACITOR TO THE GROUND ONE BY ONE WITH A WIRE OF MORE THAN 10MM2, AND THEN CHECK WHETHER THE CONTACTOR, CAPACITOR WIRING SCREW, AND GROUNDING DEVICE ARE GOOD, CHECK WHETHER THE CAPACITOR HAS A BLOATED BELLY, AND CLEAN THE DUST IN THE CABINET WITH A VACUUM CLEANER.
G. After the maintenance of the security load section is completed, the generator can be started to supply power to it, and the bus section can be maintained by stopping the mains power.
H. Disconnect the air switch on the low-voltage side step by step, then disconnect the vacuum circuit breaker on the high-voltage side of the transformer, close the grounding switch, and hang the "no closing, someone working" sign.
I. After the maintenance of the distribution cabinet according to all the requirements of C, D, E and F, remove the safety device, disconnect the high-voltage side grounding switch, close the vacuum circuit breaker, observe that the transformer is put into operation correctly, send power to the low-voltage distribution cabinet step by step, and transfer the security load from the generator power supply to the mains power supply.
5. Safety precautions
1. The power should be checked after the power failure.
2. When maintaining the distribution cabinet in sections, an isolation device should be installed at the junction of the live and uncharged distribution cabinets.
3. When operating the vacuum circuit breaker on the high-voltage side, you should wear insulated boots, wear insulated gloves, and have a special person to supervise you.
4. When maintaining the capacitor cabinet, it is strictly forbidden to touch the capacitor before the capacitor is discharged to the ground.
5. Before the maintenance is completed, check whether there are any tools left in the distribution cabinet.
6. Relevant documents and records
1. Maintenance work ticket;
2. Annual maintenance records of distribution cabinets and control cabinets;
3. Equipment maintenance records.
|
More on that
|
Introduction to the features of Rittal cabinet air conditioners
1. Extremely high;
2. The appearance is RAL7035 color (gray and white), which is consistent with the cabinet;
3. Ultra-thin design, the installation method can be plug-in and embedded;
4. The power supply range, single-phase and three-phase power supply models can be selected;
5. Control ...
|
|
Rittal cabinet fittings Rittal stainless steel rain cover for AE model 2472.000
Stainless steel rain top cover for AE
Product model 2472.000
Outdoor fixtures are safely and reliably protected with a drain channel at the back. Material: Stainless steel 1.4301 (AISI 304).
Product Description: Safe and reliable protection for outdoor installations, with ...
|
|
Rittal cabinet - judgment and treatment of energy storage faults in high-voltage switchgear
In the high-voltage cabinet with the spring energy storage operating mechanism, the energy storage must be stored in advance before closing. The energy storage mechanism is driven by an electric motor and the gear mechanism lengthens the spring. There are two types of operation methods: electric and manual. Manual failure to store energy should be due to a mechanical failure of the mechanism. Manual energy storage ...
|
|
The customized outdoor cabinet of the Rittal integrated pumping station was successfully delivered to build an ecological water environment
The handover ceremony of the customized outdoor cabinet of the integrated pumping station jointly developed by Rittal and Shu Pengshi was held in Rittal (China) Company. Mr. Tian Ming, General Manager of Shupenshi Environmental Technology (Changzhou) Co., Ltd., and Mr. Xue Boliang, Technical Director, attended the handover ceremony with technical engineers. Power...
|
|
Rittal enclosures – Q&A on the basics of high- and low-voltage distribution cabinets
What is Arc?
Arc is a physical phenomenon generated during the operation of electrical equipment, which is characterized by very strong light and high temperature.
Classification of electrical loads?
Primary load: those whose power supply interruption will cause personal injury or death; or those that will cause significant losses politically or economically.
...
|
|
Rittal cabinets - four tips for the reasonable layout of low-voltage distribution cabinet wiring
1. Site selection. The location of the low-voltage distribution room should be close to the load center, set up in a place with less dust, less corrosive medium, dry and slight vibration, and should appropriately leave room for development;
Second, the layout of power distribution equipment. The layout of the distribution equipment in the low-voltage distribution room must follow the principle of safety, safety, and safety.
|
|
Rittal cabinets – what electrical components are included in the electrical cabinet?
1 Circuit breaker
Low-voltage circuit breakers, also known as automatic air switches, can be switched on and off manually, and can be used to distribute electrical energy, start asynchronous motors infrequently, and protect power lines and motors. In the event of a severe overload, short circuit, or undervoltage fault, the circuit can be automatically shut down.
2 Contactors
...
|
|
Rittal cables – the key point of TPE technology in wire and cable
1. TPE material has soft touch, high elasticity, mild texture, adjustable surface gloss and fog brightness, low smoke and halogen-free, phosphorus-free, excellent oil resistance, weather resistance, aging resistance, flex resistance, ozone resistance and chemical resistance.
2. The old TPE material can be simply recycled and recycled.
|
|
Kongsberg awarded Rittal China the 2022 "Outstanding Contribution Award"
Recently, Rittal participated in the supplier conference held by KONGSBERG China, and KONGSBERG awarded Rittal China the 2022 "Outstanding Contribution Award".
As a global strategic partner of Rittal, Kongsberg Marine is a global leading maritime technology company, providing services for merchant marine, offshore engineering, ...
|
|
The Rittal TS8 system solution is designed to cope with extreme mining conditions
Energy consumption planning continues to grow, and countries around the world have significantly increased the supply of low-carbon power such as nuclear, hydro, wind, and solar energy in order to achieve energy conservation and emission reduction. But now that natural resources are simply being exploited, what are the important developments of green energy that are lacking? The answer is: geothermal energy ...
|
|
What is the difference between a control cabinet and a distribution box?
One. The nature is different
Distribution box: There is a large amount of parameter data in the distribution box. It generally constitutes a low-voltage distribution box.
Control cabinet: The control cabinet is to assemble the switch cabinet, measuring instruments, protection devices and auxiliary equipment in a closed or semi-enclosed metal cabinet or screen according to the requirements of electrical wiring.
|
|
Rittal cables – classified according to the purpose of the cable and the environment in which it will be used
1. DC cable
(1) Tandem cables between components.
(2) Parallel cables between strings and between strings and DC distribution boxes (combiner boxes).
(3) The cable between the DC distribution box and the inverter.
The above cables are all DC cables, outdoor laying ...
|
|
Rittal at the Hannover Messe 2022 in Germany
"In 2022, with all the challenges, especially for small and medium-sized manufacturing companies – we need to think differently: if we want to support our customers and add value in our digital transformation, it's not just a single product innovation that will change. It will combine automation, digital ...
|
|
How many fault codes does a Rittal cabinet air conditioner have?
There are a total of 9 fault codes for Rittal cabinet air conditioners,
They are: F1, F2, F3, FF, EH, EP, EL, SF, HC.
Among them, F1, F2, and F3 represent improper use or failure of internal components;
FF stands for Regulation Circuit Fault; EH stands for High Temperature Fault;
E ...
|
|
Rittal cables – the basic structure of industrial control cables
1. Conductor
It is the main component of the product to play its use function, and it is to transmit electricity or information, that is, to transmit electric current or electromagnetic waves on the conductor. The conductor is the basic and indispensable main component of the product for the transmission of electric current or electromagnetic wave information.
2. Insulation ...
|
|
Rittal cables – the meaning of the first letter in the number of the control cable
First of all, the number of the control cable often starts with the letter "C", which indicates that the control cable is specially designed to connect different sensors and control devices as a medium for signal transmission. This kind of cable can transmit data signals, and has a certain resistance to wear and chemical corrosion, so it is widely ...
|
|
Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets
What is the role of a DC system in a substation?
Answer: The DC system provides reliable DC power supply for control signals, relay protection, automatic devices and accident lighting in the substation, and also provides reliable operating power for operation. The reliability of the DC system has a significant impact on the ...
|
|
For the first time, the Rittal Rittal and Circle B and Switch data centres have launched the European OCP Experience Centre
Circle B, Rittal and Switch data centres in Germany launch the first European Open Computing Project (OCP) Experience Centre. The full-featured OCP environment is located at one of the facilities of three switching data centers in the Amsterdam area. (The OCP Experience Center can be used as a demo center, but it is also ...
|
|
Rittal cables support factory assembly and cabling
Imagine you walk into a large, well-maintained room with many cabinets and mounting plates waiting to be machined. Several staff members focus on assembly and wiring work. Another thing that will surprise you is the complete absence of paper – no folders crammed with circuit diagrams, and no work orders. This ...
|
|
Rittal cabinet air conditioner fault code
The fault codes for Rittal cabinet air conditioners are: F1, F2, F3, FF, EH, EP, EL, SF, HC.
F1, F2, F3 represent improper use or failure of internal components;
FF stands for Regulation Circuit Fault;
EH stands for High Temperature Fault;
EP stands for Actuator Failure; ...
|
|