Rittal cabinet - judgment and treatment of energy storage faults in high-voltage switchgear

Create Date: 2024-8-30 12:03:23|Source: Rittal/Rittal

In the high-voltage cabinet with the spring energy storage operating mechanism, the energy storage must be stored in advance before closing. The energy storage mechanism is driven by an electric motor and the gear mechanism lengthens the spring. There are two types of operation methods: electric and manual. Manual failure to store energy should be due to a mechanical failure of the mechanism. Manual energy storage is possible, but electric energy storage is an electrical fault. The mechanism that has been in use for a short time has little mechanical wear and tear, and generally does not have mechanical failure.

1. Improper adjustment of the travel switch: The travel switch is a limit switch that controls the energy storage position of the motor. When the motor energy storage is in place, cut off the power supply of the motor. If the limit is too high, the institutional energy storage is full. The fault phenomenon is: the motor does not stop idling, and the energy storage indicator light does not light up. The motor can only be stopped by turning on the control switch (HK). When the limit adjustment is too low, the motor energy storage is not full and the motor is shut down in advance. Due to the energy storage is not in place, the switch cannot be closed. The way to adjust the limit is to manually and slowly store energy to find the correct position and tighten it.

2. Motor failure: If the motor winding is burned, there will be peculiar smell, smoke, fuse and other phenomena. If there is voltage at both ends of the motor, the motor does not rotate. It may be a fault such as the carbon brush falling off or being heavily worn. The way to determine whether it is a motor fault is to measure the voltage and resistance at both ends of the motor or replace it with another good motor for inspection.

3. Control switch failure or open circuit: When the control switch is damaged so that the circuit cannot be closed and the control loop is broken and the open circuit is caused, the fault is manifested in the form of the motor not rotating and there is no voltage at both ends of the motor. The way to find this is to measure the voltage or resistance with a multimeter. The measurement voltage method is that when the control circuit is energized, the multimeter is adjusted to the voltage level, and if there is a voltage (except for the step-down element), there is an open circuit point between the two points to be measured. Attention should be paid to the on-off of the bypass when using the measurement resistance method, and if there is a bypass parallel circuit, one end of the tested line should be disconnected.
Rittal cabinet - judgment and treatment of energy storage faults in high-voltage switchgear

More on that
Rittal and Epan – the intelligent future of drive cabinet systems Rittal and Epan – the intelligent future of drive cabinet systems

"Promote the deep integration of the Internet, big data, and artificial intelligence with the real economy, and make the digital economy bigger and stronger." The new generation of information technology is accelerating the all-round and in-depth integration with the traditional manufacturing industry. Rittal and Epan, with "digital twins" from virtual to real, help control cabinets and open ...

Introduction to the features of the Rittal electric cabinet air conditioner Introduction to the features of the Rittal electric cabinet air conditioner

1. Energy saving The inverter technology can automatically adjust the refrigeration and heating power according to the indoor temperature change, and the power consumption is only 1/3 of the traditional air conditioner, which can save more than 30% of the electricity cost; At the same time, it has a dehumidification function, and it can also keep the indoor air dry when used in a humid environment. OK...

Rittal Cables – an introduction to the performance of industrial control cables Rittal Cables – an introduction to the performance of industrial control cables

Thermal function: Due to the existence of thermal expansion and contraction, we should also pay attention to the thermal function of industrial control cables, that is, the temperature resistance level of industrial control cables, the heating and heat dissipation characteristics of cables for power transmission at working temperatures, current carrying capacity, short circuit and overload capabilities, the thermal deformation and thermal impulse resistance of the constituent materials.

Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets

What is eddy current? What are the harms of eddy currents? Answer: When an alternating current is passed through a wire, an alternating magnetic field is created around the wire. An induced current is generated inside the whole conductor in an alternating magnetic field, and because this induced current forms a closed loop inside the whole conductor, ...

What factors need to be taken into account when choosing a Rittal cabinet – outdoor enclosure? What factors need to be taken into account when choosing a Rittal cabinet – outdoor enclosure?

1. Safety: As the carrier of electrical equipment, the outdoor cabinet must have excellent structural design, solid materials, and firm bottom fixation to meet the requirements of strong typhoons, strong rainstorms, and even strong earthquakes. At the same time, the cabinet should have anti-leakage, anti-short circuit, anti-cut and other requirements. 2. Rainproof and dustproof ...

Rittal enclosures – how to determine the quality of a sheet metal enclosure cabinet Rittal enclosures – how to determine the quality of a sheet metal enclosure cabinet

1. Look at the material, you should choose a sheet metal chassis cabinet, and the steel plate must be thick, you can feel which ones are thick and which ones are thin when you knock them with your fingers. Its rugged enclosure protects the board, power supply and storage devices, and is resistant to voltage, shock, and dust.

How to set the temperature of the Rittal air conditioner How to set the temperature of the Rittal air conditioner

1. Set the target temperature: the default temperature of the original factory is 35°C, you can press and hold the set button for more than 1 second after starting, the parameters start to flash, complete the temperature adjustment by pressing the UP and DOWN buttons, and after adjusting to the target temperature, press the set button to store the set parameters. 2. High temperature alarm: ...

Rittal enclosures – classification of HVAC functions and system parameters Rittal enclosures – classification of HVAC functions and system parameters

Heating, also known as heating, refers to the supply of heat to a building, insisting on a certain indoor temperature. Ventilation – the process of feeding and removing air into a space by natural or mechanical means. Air conditioning - (referred to as air conditioning) is to meet the requirements of production and life, improve labor ...

Rittal Cables – an introduction to the advantages of industrial control cables Rittal Cables – an introduction to the advantages of industrial control cables

1. It can meet the needs of many electrical appliances, and relatively speaking, in the process of making industrial control cables, the relevant standards of various information in the process of dissemination are fully considered. In this way, it can ensure that the industrial control cable can meet the performance of many electrical appliances in daily work.

Rittal cables – common causes of cable failure Rittal cables – common causes of cable failure

1. External force damage. Judging from the operation analysis in recent years, especially in Haipudong, which is developing rapidly, a considerable number of cable failures are caused by mechanical damage. For example, the cable laying and installation is not standardized, which is easy to cause mechanical damage; Engage in direct burial on cables ...

Rittal enclosures – how do you maintain your robot control cabinet? Rittal enclosures – how do you maintain your robot control cabinet?

1. Maintenance content (1) Check the heat dissipation of the controller It is strictly forbidden to cover the controller with plastic or other materials; Leave enough space behind and on the sides of the controller (> 120mm); It is strictly forbidden to position the controller close to the heat source; It is strictly forbidden to put sundries on the top of the controller; Avoid over-the-top ...

An introduction to the features of Rittal cabinet fans An introduction to the features of Rittal cabinet fans

Wide air volume range: 20-900m3/h Innovative diagonal flow fan and brushless DC EC motor technology for higher air flow and uniform distribution of cold air Comes with an interface module for controlling and monitoring fans The standard degree of protection is IP54, up to IP56 with a water spray cover ...

Running seamlessly, Rittal develops with reliable quality "pulsating" energy storage Running seamlessly, Rittal develops with reliable quality "pulsating" energy storage

Reliable supply wherever you are Tesvolt's large-scale industrial battery storage systems are based on standard products made by Rittal and guarantee a continuous power supply on the top of a mountain, by the sea or in the desert. The mountain peaks rise high above the crystal clear ...

Rittal cabinets – the characteristics of GDD and GCK low-voltage distribution cabinets Rittal cabinets – the characteristics of GDD and GCK low-voltage distribution cabinets

1. GGD AC low-voltage distribution cabinet has the characteristics of high breaking capacity, good dynamic and thermal stability, flexible electrical scheme, convenient combination, seriality, strong practicability, novel structure and high protection level. It can be used as a replacement product for low-voltage switchgear. Structural features ...

Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets

What are the main differences between electronic control equipment and power distribution equipment products? Answer: The function of electronic control equipment is mainly control, and the function of power distribution equipment is mainly transmission. How much is the external design of domestic electronic control equipment products? Answer: Control panel, control cabinet, control box and console ...

Rittal cabinets – judgment and handling of high-voltage switchgear closing faults Rittal cabinets – judgment and handling of high-voltage switchgear closing faults

Closing faults can be divided into electrical faults and mechanical faults. There are two types of closing methods: manual and electric. Failure to close manually is generally a mechanical failure. Manual can be closed, electric can not close is an electrical fault. 1. Protection action: The protection action has been analyzed in front to trip the switch. ...

Rittal Blue e+ cooling unit in the cooling of the Airbus A320 test plant Rittal Blue e+ cooling unit in the cooling of the Airbus A320 test plant

A new A320 Airbus aircraft must pass rigorous testing before it can be put into service, so to ensure a smooth flight, not only the aircraft itself needs to be protected from overheating, but also the test hardware needs to be properly protected. Airbus uses Rittal Blue e+ cooling units to make it ...

Rittal cables – classified according to the purpose of the cable and the environment in which it will be used Rittal cables – classified according to the purpose of the cable and the environment in which it will be used

1. DC cable (1) Tandem cables between components. (2) Parallel cables between strings and between strings and DC distribution boxes (combiner boxes). (3) The cable between the DC distribution box and the inverter. The above cables are all DC cables, outdoor laying ...

Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets

What is Peak Load? What is trough load? What is Average Load? A: Peak load refers to the maximum load that can occur on the grid and the user in a day. The trough load is the hourly average of the least amount of usage that occurs in the grid and the users in a single day.

The difference between imitation Rittal and genuine Rittal The difference between imitation Rittal and genuine Rittal

The quality and brand awareness of Rittal are good, and the application market is also large, but due to various reasons such as price, delivery time, service, etc., many customer groups do not want to use Rittal products, but choose to go to the manufacturer to order imitation Rittal products. ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top