Three-phase motor current is too high - LS power generation

Create Date: 2024-8-30 12:03:23|Source: LS/Power Generation

First, the power supply problem

1. The power supply voltage is too high

When the power supply voltage is too high, the motor back electromotive force, magnetic flux and magnetic flux density all increase. Since the magnitude of the iron loss is proportional to the square of the magnetic flux density, the iron loss increases, resulting in overheating of the core. The increase of magnetic flux leads to a sharp increase in the weight of the excitation current, which increases the copper loss of the stator winding and overheats the winding. As a result, when the supply voltage exceeds the rated voltage of the motor, the motor will overheat.

2. The power supply voltage is too low

When the power supply voltage is too low, if the electromagnetic torque of the motor remains unchanged, the magnetic flux will decrease, the rotor current will increase accordingly, and the weight of the load power supply in the stator current will increase accordingly, resulting in the overheating of the stator and rotor windings.

3. The power supply voltage is asymmetrical

When the one-phase power line is broken, the fuse is blown in one phase, or the corner head of the gate knife starting equipment is burned and the one-phase is not connected, the three-phase motor will be formed to go through the single phase, resulting in the running two-phase winding overheating through the high current, and even incineration. Therefore, fuses are generally not suitable for maintenance of three-phase motors.

4. The three-phase power supply is unbalanced

When the three-phase power supply is unbalanced, the three-phase current of the motor will be unbalanced, causing the windings to overheat.

From the above, it can be seen that when the motor overheats, the primary consideration should be the power supply (soft start, frequency converter, servo drive can also be regarded as the power supply). Once you have acknowledged that there is no problem with the power supply, you can consider the other aspects.

                                 Three-phase motor current is too high - LS power generation

Second, the load problem

1. The motor is overloaded

When the equipment is not matched, and the load power of the motor is greater than the rated power of the motor, the motor will be overloaded for a long time (i.e., a small horse-drawn cart), which will lead to overheating of the motor. When repairing an overheated motor, it should be clear whether the load power is consistent with the motor power to prevent blind and purposeless disassembly.

2. The dragging mechanical load operation is abnormal

Although the equipment is matched, the dragged mechanical load is not normal, the load is large and small during operation, and the motor is overloaded and heated.

3. There is something wrong with the dragging machinery

When the dragged machinery has a fault, the rolling is not sensitive or it is stuck, it will overload the motor and cause the motor winding to overheat. Therefore, when overheating the motor, the load factor cannot be ignored.

Third, the motor itself problems

1. The motor winding is broken

When one of the windings of the motor is broken, or one of the branches of the parallel branch is broken, it will cause the three-phase current to be unbalanced and overheat the motor.

2. Short circuit in motor winding

When there is a short-circuit problem in the winding of the motor, the short-circuit current is much larger than the normal operating current, which increases the copper loss of the winding, resulting in overheating of the winding and even incineration.

3. The motor coil connection is wrong

When a coil, coil bank, or one-phase winding is reversed, it can cause a serious imbalance in the three-phase current, which can overheat the winding.

4. Mechanical problems of the motor

When the motor shaft is bent, the device is not good, and the bearing is faulty, etc., the motor current will increase, the copper loss and mechanical conflict loss will increase, and the motor will be overheated.

Fourth, ventilation and heat dissipation problems

1. The ambient temperature is too high, so that the air inlet temperature is high.

2. The air inlet is blocked by debris, which makes the air inlet not smooth and forms a small air intake.

3. There is too much dust inside the motor, which affects the heat dissipation.

4. The fan is damaged or reversed, resulting in no wind or small air volume.

5. The air shield is not installed or the wind shield is not installed in the end cover of the motor, forming a motor without a certain air path.

Excessive motor vibration may also cause high motor current, causes and treatment methods:

Fifth, the motor vibration problem

1. Rotor unbalance - leveling and balancing

2. The pulley is unbalanced or the shaft is stretched and bent - check and proofread

3. The axis of the motor and the load is not aligned - check the axis of the adjustment unit

4. Improper motor device - check the condition of the device and the foot screws

5. The load is suddenly too heavy - reduce the load

More on that
Methods for extending the service life of inverters - LS generates electricity Methods for extending the service life of inverters - LS generates electricity

1. The influence of electromagnetic disturbance on the inverter: In the modern industrial control system, the microcomputer or PLC control technology is mostly selected, and in the process of system planning or transformation, it is necessary to pay attention to the disturbance of the inverter to the microcomputer control board. The inverter is disturbed by the outside world, because the user ...

Communication control of inverter - power inverter Communication control of inverter - power inverter

The communication control of the inverter is more complicated, so it is listed separately. The communication control of the inverter is a control method for the operation, speed regulation and status indication of the inverter through the communication interface of the inverter. ...

Introduction to vector control of inverter and motor - LS power generation Introduction to vector control of inverter and motor - LS power generation

As for the use of vector-operated motors, it can be divided into two categories, namely non-reactive vector control (SVC) and reactive vector control (FVC). Vectorless Handling (SVC): Due to the speed response, additional equipment for the encoder is installed in the motor dragged by the inverter, which is cumbersome. Here...

Introduction of LS PLC programming software Introduction of LS PLC programming software

LS PLC programming software is a professional PLC programming assistant tool, providing excellent interface, which can carry out PLC programming operations such as online modification, debugging and self-diagnosis, packing and debugging, etc., compatible with LG Master-K series and LG MASTER-K series, which can make you in the process of processing in a timely manner.

Models and features of LS Metasol series products Models and features of LS Metasol series products

Metasol series MS (100A and below) products are newly launched and the primary product specifications: contactors, thermal relays, and center relays. Features: The body is small, the internal structure is sealed, and the safety factor is high ...

DC motor troubleshooting - LS power generation DC motor troubleshooting - LS power generation

1. The speed of the motor slows down, and the cause of the problem of sound disorder may occur in the electronic speed stabilization device and the motor itself. If there is no problem with the power supply, most of the motor itself has a problem. It can be repaired by replacing the new motor and dismantling and repairing the motor. Dismantling and repairing the motor ...

The role of the inverter's braking resistor - LS generates electricity The role of the inverter's braking resistor - LS generates electricity

1. Maintain the inverter from the damage of regenerative electricity In the process of rapid shutdown of the motor, because of the inertia, a lot of regenerative electric energy will be generated, if this part of the regenerative electric energy is not consumed in time, it will directly act on the DC circuit part of the inverter.

What is the difference between LS inverter and LG inverter? What is the difference between LS inverter and LG inverter?

LS inverter and LG inverter are the same, there is no difference between the two. LS inverter, the full name of LS AC inverter governor, after supplying a variety of configurations, converts direct current into communication power, and changes the general power supply ...

Wiring of the main circuit of the inverter - LS generates electricity Wiring of the main circuit of the inverter - LS generates electricity

1. The power supply should be connected to the R, S, and T terminals at the input end of the inverter, and must not be connected to the output terminal (U, V, W) of the inverter, otherwise the inverter will be damaged. After wiring, it is necessary to clean the trivial wires, which may cause abnormalities, failures and problems, and it is necessary to always keep ...

Whether the C-type circuit breaker is suitable for the motor circuit - power generation Whether the C-type circuit breaker is suitable for the motor circuit - power generation

Type C micro-break is used for general circuits, such as lighting circuits; D-type circuit breakers are used in power circuits such as electric motors, so can C-type micro-breakers be used in motor circuits? Differences between C-type and D-type discontinuity: C-type micro-disconnect: with ...

Why can't the inverter be equipped with a leakage protector - power generation Why can't the inverter be equipped with a leakage protector - power generation

When using an inverter, a leakage maintainer must not be used. This is a major principle of the use of frequency converters. Some users choose the corresponding leakage maintainer for the inverter when using the inverter. *The result is: the inverter moves together ...

Inverter circuit board repair and drawing-free maintenance method - LS power generation Inverter circuit board repair and drawing-free maintenance method - LS power generation

1. Be "confident" It is necessary to fully understand the principles of some typical circuits and be familiar with them. Guangzhou Kewo Training Center believes that drawings are dead, and the thoughts in the head are alive, able to make analogies, able to reason, and able to touch analogies. For example, switching power supply is always inseparable from ...

The basic method and steps of inverter debugging - power inverter The basic method and steps of inverter debugging - power inverter

1. No-load energizing test of inverter 1. Ground the grounding terminal of the inverter. 2. Connect the power input terminal of the inverter to the power supply through the leakage maintenance switch. 3. Check whether the factory display window of the inverter is normal, if it is incorrect, it should be reset.

Explanation of basic terms of electrician - electricity production Explanation of basic terms of electrician - electricity production

1. Active power - in the process of generating and transmitting alternating current energy, the part of energy used to convert into electromagnetic methods is called active power 2. Reactive power - in the process of AC electric energy generation and transmission, it is used for electromagnetic field AC in the circuit.

Introduction to the working principle of LS electric molded case circuit breaker Introduction to the working principle of LS electric molded case circuit breaker

Molded case circuit breakers are also known as equipment circuit breakers, all parts are sealed in plastic housings, auxiliary contacts, undervoltage trippers and shunt trippers are modular. Because of the very compact structure, the molded case circuit breaker is basically impossible to maintain. It is mostly manually operated, and the large capacity ...

Inverter maintenance fault handling method - LS power generation Inverter maintenance fault handling method - LS power generation

1. Not manifested. This situation is more common, generally in the normal condition of the external three-phase power supply, it is the switching power supply of the inverter burned, and the 24 volt power supply on the output board of the inverter terminal can be measured.

The difference between voltage type and current type inverter - LS generates electricity The difference between voltage type and current type inverter - LS generates electricity

The differences between voltage type and current type inverter are mainly manifested in: (1) the load of the buffer inverter of reactive power is an asynchronous motor, which is an inductive load, and in addition to transmitting active power between the intermediate DC link and the motor, there is also the exchange of reactive power. Because power electronic switches ...

LS power terminal is faulty LS power terminal is faulty

From the perspective of application, the function of the terminal block should be achieved: the contact part should be conducted, and the contact should be reliable. The insulating parts should not be conducted, and it is necessary to insulate them firmly. There are three common forms of fatal failure of terminal blocks: ...

Common faults in terminal blocks - LS generates electricity Common faults in terminal blocks - LS generates electricity

From the point of view of application, the function that should be reached is: it is necessary to conduct the local area where the touch part should be conducted, and the touch is reliable. If the insulating part should not be conducted, it is necessary to insulate it firmly. There are three common types of faults in terminal blocks: ...

The difference between inverter and servo - LS produces electricity The difference between inverter and servo - LS produces electricity

An important difference between servo and frequency conversion is that frequency conversion can be without encoder, while servo must have an encoder for electronic commutation. 1. What the two have in common: The skill of communication servo itself is the learning and application of ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top