Rittal cabinet - distribution cabinet installation method, installation process and precautions

Create Date: 2024-8-30 12:03:23|Source: Rittal/Rittal

First, the construction process

Equipment unpacking inspection→ equipment handling, → cabinet (plate), basic installation, → above the cabinet (plate), bus preparation, → cabinet (plate), secondary circuit wiring, → cabinet (plate) test adjustment, → power transmission operation acceptance

Second, the construction process

1. The equipment is unpacked and inspected, and the installation unit, the supplier or the construction unit jointly carry out the inspection, and make inspection records. According to the equipment list, construction drawings and equipment technical data, check the specifications and models of the equipment body, accessories and spare parts should meet the requirements of the design drawings; Complete accessories and spare parts; The product qualification certificates, technical information and manuals are complete. The appearance inspection of the cabinet (plate) body should be free of damage and deformation, and the paint should be intact and undamaged. The internal inspection of the cabinet (plate) shows that the electrical devices and components, insulating porcelain parts are complete, and there are no defects such as damage and cracks.

2. Equipment transportation is coordinated by lifting workers and electricians. According to the weight and distance of the equipment, it can be transported by car, truck crane, manpower trolley or winch roller. The road should be cleared in advance before transportation to ensure smooth and smooth. Equipment hanging points. If there is a lifting ring on the top of the cabinet (plate), the sling should be worn in the lifting ring, and the sling element without the lifting ring should be hung at the main load-bearing structure at the four corners, and the sling shall not be hoisted on the equipment parts. The rope length of the sling should be consistent to prevent the cabinet from deforming or damaging the parts.

3. Cabinet (plate) installation, straightening section steel. Straighten the curved section steel, and then prefabricate and process the basic steel frame according to the requirements of the drawing, and brush the anti-rust paint. According to the position marked in the construction drawings, the prefabricated basic steel frame is placed on the reserved iron parts, and leveled and aligned with a level or level. During the leveling process, no more than three gaskets should be used. Then, the basic steel frame, embedded iron parts, and gaskets are welded by electric welding. The top of the final foundation steel should be 10mm higher than the trowel ground, and the handcart cabinet should be implemented according to the technical requirements of the product.

4. After the installation of the basic steel, the outdoor ground wire flat steel is introduced into the room (with the transformer installation ground wire) and the two ends of the basic steel are welded firmly, and the welding surface is twice the width of the flat steel, and then the basic steel is brushed with gray paint twice.

5. The verticality (per meter) of the bus bar configuration on the top of the cabinet (plate) is required to be < 1.5mm, the top of the adjacent two plates is < 2mm, the top of the column plate is < 5mm, the side of the adjacent two plates is < 1mm, the surface of the column plate is < 5mm, and the seam of the plate is < 2mm.

6. The cabinet (plate) is connected with the secondary small wire, and all the electrical components on the cabinet (plate) are checked one by one according to the schematic diagram to see if they are consistent, and the rated voltage and the power supply voltage of the control operation must be consistent. Lay the control cable connection between the phase and the cabinet according to the diagram. After the control wire is calibrated, each core wire is simmered into a circle and connected to each terminal board with galvanized screws, eye rings, and spring pads. Generally, one terminal on each side of the terminal board presses one wire, and no more than two, and eye circles are added between the two wires. The multi-strand line should be shabu tin, and no broken strands are allowed.

7. The cabinet (plate) test is adjusted, and the high-voltage test should be carried out by the test unit licensed by the local power supply department. The test standards are in line with the national specifications, the regulations of the local power supply department and the requirements of product technical data. Insulation shake test, use a 500V shake meter to test the resistance of each circuit at the terminal board, and the resistance must be greater than 0.5MΩ. If there are transistors, integrated circuits, and electronic components in the secondary small wire circuit, the inspection of this part is not allowed to use the shake meter and the bell test, and the multimeter is used to test whether the circuit is connected. Turn on the temporary control power supply and the operating power supply; Remove the phase wire at the upper end of the control and operation power circuit fuse in the cabinet (panel) and connect it to the temporary power supply.

8. For the acceptance of power transmission operation, the construction unit shall prepare the electroscope, insulating boots, insulating gloves, temporary grounding braided copper wire, insulating rubber pad, powder fire extinguisher, etc. that have passed the test. Thoroughly clean all equipment, substation and distribution room, and control room dust. Use a vacuum cleaner to clean electrical appliances and instrument components, and in addition, other items should not be stacked indoors except for the equipment and appliances needed for power transmission. Check whether there are tools, metal materials and other objects left on the bus and equipment. Organize the trial operation, and clarify the commander, operator and guardian of the trial operation.

3. Pay attention to the main points

1. Before the installation of the distribution cabinet, the complete set of equipment and its equipment foundation shall be inspected before installation, and the box can be installed only after passing the acceptance.

2. When installing, pull two reference lines at a distance of 200mm from the top and bottom of the cabinet; The panel is in place according to the datum in the order specified in the drawing, and one panel is accurately adjusted, and then the other panels are adjusted one by one; Adjust to the same surface and arrange neatly.

3. The simulated bus is aligned and installed firmly. The plates, cabinets and the equipment in the panels and cabinets are firmly connected with each component.

4. After the installation is completed, the disk signs, the signs are complete, accurate and clear, and the trolley and drawer cabinet are flexible to push and pull. The side-by-side distribution cabinets are arranged neatly, the cabinet joints are smooth, the paint layer is intact and undamaged, and the cabinet body and cabinet door are grounded firmly and reliably.

5. The operation space for overhaul and maintenance before and after the distribution cabinet meets the requirements for the maintenance and use of the distribution cabinet. The insulating carpet is laid completely according to the requirements.
Rittal cabinet - distribution cabinet installation method, installation process and precautions

More on that
Rittal Cables – an introduction to the process characteristics of cables Rittal Cables – an introduction to the process characteristics of cables

1. The impact of large-length continuous superposition combined production mode on the production of wires and cables is global and controllable, which involves and affects: (1) Production process and equipment layout All kinds of equipment in the production workshop must be reasonably discharged according to the process flow required by the product, ...

Rittal cables – the meaning of the first letter in the number of the control cable Rittal cables – the meaning of the first letter in the number of the control cable

First of all, the number of the control cable often starts with the letter "C", which indicates that the control cable is specially designed to connect different sensors and control devices as a medium for signal transmission. This kind of cable can transmit data signals, and has a certain resistance to wear and chemical corrosion, so it is widely ...

What are the application areas of Rittal cabinets – cabinet air conditioners? What are the application areas of Rittal cabinets – cabinet air conditioners?

Indoor unit: suitable for all kinds of control boxes, distribution boxes and electrical cabinets in machinery, electric power, chemical industry, textile machinery, automation equipment, instrumentation and other industries with high requirements for temperature and humidity. It can also be used to regulate temperature and humidity in small spaces. Outdoor unit: suitable for outdoor general base station, outdoor ...

Rittal Cables – the operation of power cable routes Rittal Cables – the operation of power cable routes

The operating voltage of the cable Generally speaking, there is a certain relationship between the operating voltage of the cable and the rated voltage. If some cable lines are not in use, they must be connected to the power grid to ensure that the cable lines are not exposed to moisture. When the neutral point is not grounded ...

Rittal cabinet - judgment and treatment of sudden trip fault in operation of high-voltage switchgear Rittal cabinet - judgment and treatment of sudden trip fault in operation of high-voltage switchgear

1) Fault phenomenon: The cause of this failure is the protection action. The high-voltage cabinet is equipped with protection against overcurrent, quick cut-off, gas and temperature. 2) Judgment method: The cause of the fault can be judged according to the relay card drop, remote signaling information, etc. After the action of gas and temperature protection in the high-voltage cabinet ...

Rittal cabinets – maintenance methods for motor control cabinets Rittal cabinets – maintenance methods for motor control cabinets

1. Disconnect the power supply, check whether the rack of the control cabinet has reliable grounding, and make the grounding resistance not greater than 4Ω. 2. There are voltages of different properties on the control cabinet (DC 110V; Communication single-phase 220V; Three-phase communication), the circuit must be distinguished during maintenance to avoid short-circuit accidents.

Alarm code analysis for Rittal chillers Alarm code analysis for Rittal chillers

1. E1: Temperature sensor failure 2. E2: Humidity sensor malfunction 3. E3: Compressor overload protection 4. E4: Compressor phase loss protection 5. E5: Compressor short circuit protection 6. E6: Compressor switch failure 7. E7: Fan failure ...

How many fault codes does a Rittal cabinet air conditioner have? How many fault codes does a Rittal cabinet air conditioner have?

There are a total of 9 fault codes for Rittal cabinet air conditioners, They are: F1, F2, F3, FF, EH, EP, EL, SF, HC. Among them, F1, F2, and F3 represent improper use or failure of internal components; FF stands for Regulation Circuit Fault; EH stands for High Temperature Fault; E ...

How to set the temperature of the Rittal air conditioner How to set the temperature of the Rittal air conditioner

1. Set the target temperature: the default temperature of the original factory is 35°C, you can press and hold the set button for more than 1 second after starting, the parameters start to flash, complete the temperature adjustment by pressing the UP and DOWN buttons, and after adjusting to the target temperature, press the set button to store the set parameters. 2. High temperature alarm: ...

What are Rittal cabinets used for? What are Rittal cabinets used for?

1. The cabinet is generally made of cold-rolled steel plate or alloy to store the computer and related control equipment, which can provide protection for the storage equipment, shield electromagnetic interference, arrange the equipment in an orderly and neat manner, and facilitate the maintenance of the equipment in the future. Cabinets are generally divided into server cabinets, network machines, etc.

Rittal cabinets – the specifications of server cabinets Rittal cabinets – the specifications of server cabinets

Server cabinets have requirements in terms of depth, height, and load-bearing capacity. There are three heights of 2.0 meters, 1.8 meters and 1.6 meters; The width is 800mm, 700mm or 600mm; There are three depths: 700mm, 800mm and 900mm. Can be configured: special fixed pallet, special ...

Five hidden details you didn't know about Rittal cabinets and common Q&A Five hidden details you didn't know about Rittal cabinets and common Q&A

Five details that are easy to overlook: One of the hidden details: steel The most basic thing of a cabinet is to look at the steel, the Rittal standard cabinet is made of section steel, there are many masters who understand the cabinet to understand, the steel plate must be thick, just knock it with your fingers. General ...

Rittal cables – what are the types of industrial wires and cables commonly used? Rittal cables – what are the types of industrial wires and cables commonly used?

Industrial wires and cables include single-core wires and cables, rubber cables, shielded control cables, flame-retardant cables, fire-resistant cables, etc. Single-core wire and cable It means that there is only one conductor in the insulation layer, the common BV wire, and B represents the wiring; V stands for insulating polyvinyl chloride. Suitable for AC ...

Description of the models of Rittal cabinet air conditioners Description of the models of Rittal cabinet air conditioners

Here are some of the models of Rittal cabinet air conditioners: SK3368220 air conditioner RBT3368220 300 W, 220V SK3368320 air conditioner RBT3368320 500 W, 220V SK3368520 air conditioner RBT3368520 1000W, 220V SK3368620 air conditioning RBT3368620 ...

Rittal rittal stage coating method and function Rittal rittal stage coating method and function

Rittal coating method and function degreasing, nano-ceramic pretreatment, washing, used for anti-rust maintenance, used to improve the adhesion characteristics of lacquer. The conversion coating anodic dip primer of the nano-ceramic is evenly applied to the individual surfaces, edges and cavities. This constitutes a high corrosion protection ...

Rittal cables – the common code for cables Rittal cables – the common code for cables

Usage code - not marked as power cable, K- (control cable), P- (signal cable); Conductor material code - not marked as copper (can also be marked as CU), L- (aluminum); Inner Sheath Code – Q-(Lead Packed), L- (Aluminum Cladding), H- (Rubber Jacket), V-(Polyvinyl Chloride ...

Rittal Cables – the scope of application for wires and cables Rittal Cables – the scope of application for wires and cables

Power system The wire and cable products used in the power system mainly include overhead bare wires, busbars (busbars), power cables (plastic cables, oil-paper power cables, which are basically replaced by plastic power cables), rubber sheathed cables, overhead insulated cables, branch cables (replacing part of the busbars), ...

Rittal cabinets – an introduction to the installation steps and features of the control cabinet Rittal cabinets – an introduction to the installation steps and features of the control cabinet

The control cabinet is according to the requirements of electrical wiring to assemble switchgear, measuring appearance, maintenance appliances and auxiliary equipment in a closed or semi-closed metal cabinet or screen panel, and its arrangement should meet the requirements of the normal operation of the power system, easy to overhaul, and not to endanger the safety of people and surrounding equipment. Normal operation ...

Some advantages of the Rittal compact AE enclosure Some advantages of the Rittal compact AE enclosure

The Rittal compact AE cabinet with its new internal expansion rails –Supplementary internal expansion for machining – Can be done in a time-saving manner in the side, bottom and top cover areas Installation – Two rows of adjustable TS 8 system holes for installation capacity Outer space...

How do two Rittal cabinets fit together? How do two Rittal cabinets fit together?

1. The power cords of the two cabinets are connected to the power socket at the rear of the cabinet. 2. The RS232 interface of the two cabinets is connected together with a communication cable. 3. Lock the door of the main cabinet, and turn on the power from the cabinet and the main cabinet in turn. ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top