Server cabinets have requirements in terms of depth, height, and load-bearing capacity. There are three heights of 2.0 meters, 1.8 meters and 1.6 meters; The width is 800mm, 700mm or 600mm; There are three depths: 700mm, 800mm and 900mm.
It can be configured: special fixed tray, special sliding tray, power bracket, caster, foot peg, cable management ring, cable management frame, L bracket, extension beam, etc. The main frame, front and rear doors, and left and right side doors can be quickly disassembled and assembled.
Fixed Tray: Used to install various equipment, it has a wide range of sizes and uses, there are 19" standard trays, non-standard fixed trays, etc. The fixed pallet depth of the conventional configuration is 440mm, 480mm, 580mm, 620mm and so on. THE LOAD BEARING OF THE FIXED PALLET IS NOT LESS THAN 50KG.
Sliding tray: used to install keyboards and various other devices, which can be easily pulled out and pushed back; The 19" standard sliding tray fits any 19" standard cabinet. The sliding tray depth is 400mm and 480mm. THE LOAD BEARING CAPACITY OF THE SLIDING PALLET IS NOT LESS THAN 20KG.
Power Distribution Unit: Optional power socket to fit any standard power plug, with 19" mounting bracket, flexible installation methods. Specifications: 6 sockets. Parameters: - 220V, 10Amp.
Cable Management Frame: 19" standard cable management frame. It can be used with any kind of TOPER series cabinet. The 12-hole cable management frame is best used with 12-port, 24-port and 48-port distribution frame.
Cable management ring: Specially designed for TOPER 1800 series and TOPER Server series cabinets, it is very easy to install and disassemble, and the number and position of use can be adjusted arbitrarily.
L-Bracket: L-Bracket can be used with cabinets to install 19" standard equipment in the cabinet, especially the heavier 19" standard equipment, such as rack-mounted servers, etc.
Blind plate: The blind plate is used to block the empty space in the 19" standard cabinet, etc., and there are 1U and 2U ...... and other specifications. There are two types of conventional blind plates: 1U and 2U.
Extension Beam: A device designed for use in TOPER 1800 series and TOPER Server series cabinets to expand the installation space in the cabinet. It is very easy to install and disassemble. At the same time, it can also be installed with the cable management frame and power distribution unit. The format is flexible and diverse.
Mounting nut (square nut): suitable for any TOPER series cabinet, used for the installation of all equipment in the cabinet, including the installation of most of the cabinet accessories.
Keyboard bracket: used to install standard computer keyboards, which can be used with all specifications of computer keyboards on the market; It can be folded 90 degrees. The keyboard tray must be used with a sliding tray.
Speed control fan unit: Installed on the top of the cabinet, the speed of the fan can be adjusted according to the ambient temperature and equipment temperature, which effectively reduces the noise of the equipment room.
Speed regulation: manual, stepless speed regulation.
Rack Fan Unit: 1U in height, can be installed in any height position in a 19" standard cabinet, and can be configured according to the heat source in the cabinet.
Full mesh front door: The front door of the cabinet is all 3 round holes, which improves the heat dissipation performance and shielding performance of the cabinet.
The height can be matched: 2.0 m cabinet, 1.8 m cabinet, 1.6 m cabinet.
Network cabinets include server cabinets, and are also used to combine mounting panels, plug-ins, subracks, electronic components, devices, and mechanical parts and components to form an overall mounting box. The network cabinet is mainly used in the wiring project, storing the router, switch, display, wire rack and so on, and the project is used more. In general, the depth of the network cabinet is less than or equal to 800mm, and the depth of the server cabinet is greater than or equal to 800mm. The network cabinet should be easy to produce, assemble, debug, package and transport. Server cabinets should meet the requirements of standardization, standardization, and serialization. The cabinet is beautiful, applicable and color-coordinated.
|
More on that
|
The FR IT new product launch event organized by Rittal was held in Beijing
The "Eastern Data and Western Computing" project aims to promote the rational layout of data centers, optimize supply and demand, green intensification and interconnection, so that the computing resources in the west can more fully support the computing of data in the east and better empower the country's digital development.
IT infrastructure is an important ...
|
|
Causes and solutions of low-voltage distribution cabinet alarms
1. It is not displayed at that time. Solution: Check whether the sample signal cable is not connected.
2. Whether the fuse core of the controller in the cabinet is burned out. Solution: Remove the burned out fuse core and replace it with a new one.
3. The voltage of the distribution cabinet is too high, and the overvoltage alarm. Workaround: Re...
|
|
Rittal enclosures – operating precautions for low-voltage distribution cabinets
First, set posts and responsibilities. The power department of distribution box equipment should number, register, file, hierarchical management, clear responsibilities, and regularly carry out technical inspection and maintenance of the distribution box.
|
|
How to set the temperature of the Rittal air conditioner
1. Set the target temperature: the default temperature of the original factory is 35°C, you can press and hold the set button for more than 1 second after starting, the parameters start to flash, complete the temperature adjustment by pressing the UP and DOWN buttons, and after adjusting to the target temperature, press the set button to store the set parameters.
2. High temperature alarm: ...
|
|
Rittal enclosures – Q&A on the basics of high- and low-voltage distribution cabinets
What is Arc?
Arc is a physical phenomenon generated during the operation of electrical equipment, which is characterized by very strong light and high temperature.
Classification of electrical loads?
Primary load: those whose power supply interruption will cause personal injury or death; or those that will cause significant losses politically or economically.
...
|
|
How does Rittal do it to help thyssenkrupp build competitiveness by "digital"?
Big data is also a strategic industry related to the future development of the steel industry. In order to remain competitive in the long term, thyssenkrupp Steel in Germany is stepping up modernization and standardization in its production-related IT areas. The Rittal Container Data Centre is essential for the successful implementation of this upgrade.
|
|
Rittal Cables – an introduction to the characteristics of industrial control cables
1. Meet the needs of a variety of electrical appliances
Relatively speaking, in the process of making industrial bus industrial control cables, the relevant standards of various information in the process of dissemination are fully considered. In this way, it can ensure that the industrial control cable can meet the needs of many electrical appliances in daily work.
|
|
Rittal Rittal economy air conditioning, RBT cooling unit
Rittal has an economical air conditioner on the market, and the Rittal RBT cooling unit – is your most economical choice! If a limited budget makes you more interested in the cost
Extremely sensitive, then RBT is the ideal choice for you
Choose. Produced through large-scale assembly lines, as well as cold
But the unit itself is excellent ...
|
|
Rittal cables – measures to prevent or mitigate electrical interference
1. One spare core of the control cable is grounded
It has been proved in practice that when a spare core in the control cable is grounded, the amplitude of the interference voltage can be reduced to 25%-50%, and the implementation is simple, and the cost of the cable is increased very little.
2. Serious consequences will occur when electrical interference is generated.
|
|
Analysis of the interior of the Rittal cabinet TS8 series
RITTAL TS8 cabinet front door door rear sealing plate, a galvanized mounting plate 16-fold profile
ISV-TS 8 cabinets with a maximum current of 1600 A single door
Can be installed in all TS 8 cabinets of the same height and depth
- Can be pre-installed in configurations
- Available in the spirit ...
|
|
Rittal precision power distribution cabinet SPDR - make the data center "feel safe".
The power supply and distribution system of the data center is a system that provides stable and reliable power supply support for all the equipment that needs power supply in the computer room. The power supply and distribution system is like the heart of the human body for the entire data center system, and its importance is self-evident.
With the continuous construction of the network ...
|
|
Rittal cabinet - judgment and treatment of energy storage faults in high-voltage switchgear
In the high-voltage cabinet with the spring energy storage operating mechanism, the energy storage must be stored in advance before closing. The energy storage mechanism is driven by an electric motor and the gear mechanism lengthens the spring. There are two types of operation methods: electric and manual. Manual failure to store energy should be due to a mechanical failure of the mechanism. Manual energy storage ...
|
|
Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets
What are the main technical parameters of the fuse?
Answer: A. Rated voltage, B. Rated current, C. Breaking capacity, D. Melting characteristics, E. Overvoltage.
What are the main products of low-voltage power distribution equipment?
Answer: Low-voltage distribution panels, switch cabinets, switch boards, lighting boxes, power boxes and electrical ...
|
|
The Rittal TS8 system solution is designed to cope with extreme mining conditions
Energy consumption planning continues to grow, and countries around the world have significantly increased the supply of low-carbon power such as nuclear, hydro, wind, and solar energy in order to achieve energy conservation and emission reduction. But now that natural resources are simply being exploited, what are the important developments of green energy that are lacking? The answer is: geothermal energy ...
|
|
Rittal cabinets – daily maintenance methods for high and low voltage distribution cabinets
Complete set of electrical maintenance knowledge:
1. Low-voltage distribution cabinet
1. Regularly check whether there are traces of pest activity in each cabinet, and carry out trapping regularly.
2. Check whether the warning signs and maintenance signs are placed correctly.
3. Check whether the emergency tools and lamps are in order.
|
|
Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets
What are the basic requirements for a high-voltage circuit breaker?
A: A. Reliable work;
B. Have sufficient circuit breaking capacity
C. Have the shortest possible cut-off time;
D. Simple structure and low price.
What is the purpose of the disconnector?
Answer: A. Electrical...
|
|
Rittal enclosures – the details that need to be taken into account for the daily care and maintenance of your enclosures
1. Avoid light
The server is required to operate in a constant temperature environment, and direct sunlight will increase the temperature in the computer room, which will damage the display and shorten its service life. When operating in IDC and ISP data centers, it is impossible to see a ray of sunshine.
So, in ...
|
|
Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets
Power distribution circuits?
Answer: From the regional substation to the substation of the electricity unit or the power supply line of the city and township, it is the line used to distribute electric energy.
Power lines can be divided into according to the erection method?
A: Overhead power lines and cable lines.
...
|
|
Rittal cables support factory assembly and cabling
Imagine you walk into a large, well-maintained room with many cabinets and mounting plates waiting to be machined. Several staff members focus on assembly and wiring work. Another thing that will surprise you is the complete absence of paper – no folders crammed with circuit diagrams, and no work orders. This ...
|
|
How many fault codes does a Rittal cabinet air conditioner have?
There are a total of 9 fault codes for Rittal cabinet air conditioners,
They are: F1, F2, F3, FF, EH, EP, EL, SF, HC.
Among them, F1, F2, and F3 represent improper use or failure of internal components;
FF stands for Regulation Circuit Fault; EH stands for High Temperature Fault;
E ...
|
|