Precautions for installation of Wiener busway

Create Date: 2024-8-30 12:03:23|Source: Woehner/Wiehner

1. Before the bus duct installation, it should be ensured that the electrical shaft, substation and distribution room, the decoration project of the place through which the bus duct passes, and the heating and ventilation project are all completed to ensure that the bus duct is not polluted. The reserved holes and embedded parts of the floor and wall should be embedded and reserved according to the position required by the design. The surface of the copper bar on the connecting parts of each functional unit of the bus duct and the movable joint must be cleaned and cleaned, and the inside of the shell and before the insulator device should also be wiped clean and there should be no residue. The interphase short-circuit plate of the shell should be correctly connected well, the interphase support plate should be strong, the segmented insulated shell should be insulated, the torsion bolts of each joint part of the shell should be fastened by force from the wrench, the contact surface should be closed well, and the fasteners of the bus duct must be hot-dip galvanized products.

                               Precautions for installation of Wiener busway

2. The bus duct and the shell should be concentric, and the error shall not exceed 5mm, and the bus duct section and the bus duct shell should be aligned when the bus duct section is connected with the bus duct section, and the bus duct and the bus duct shell shall not be subjected to mechanical stress after the connection. It is necessary to do an insulation test before the whole device of the bus duct, and use a 1000V megohmmeter to measure the insulation resistance between phases, between phase shells, and each functional unit, and its insulation resistance shall not be less than 20MΩ. The installation personnel should carefully check the system diagram of the bus duct and check the standards and models of all bus ducts to avoid blind devices and rework to affect the quality of the construction device.

3. When the bus duct is installed, the whole structure should be horizontal and vertical, the height from the ground device should not be less than 2.2m when the horizontal symbol is set, and the height should be more than 1.8m from the ground when the vertical laying is laid, and the bend of the bus duct and the connection with the plug box should be bracketed. When the brackets are arranged in a row, the spacing should be uniform, and the spacing between the brackets should not be greater than 2m. When the terminal box and the start box of the bus duct are suspended, the bracket should be fixed, and the bracket on the wall and the top plate must be fixed with two expansion bolts, and the expansion bolts should be flattened and supple spring gaskets.

4. When the bus duct is laid vertically through the roof plate, the channel steel support should be selected to fix it on the bottom plate that passes. When the bus duct crosses the expansion joint or settlement joint of the building, the method of adapting to the movement of the building structure is selected to prevent the horizontal movement of the bus duct junction from forming a fracture and affecting the normal power supply and distribution of the bus duct.
More on that
Advantages of common DC bus - Wiener Advantages of common DC bus - Wiener

1. Energy saving: The energy fed back when the motor brakes can be used, so it is more energy-saving, especially for oilfield kowtow machines, cranes and other lifting equipment. 2. The power element of the equipment is high: because the motor can feed back energy, the reactive power loss is small, so the power of the equipment ...

Precautions for terminal block wiring - Wiener Precautions for terminal block wiring - Wiener

1. The fastening wiring force should be moderate, avoid sliding the bolts and nuts with excessive force, and replace the bolts and nuts that have been slid in time, and prohibit the operation. 2. When tightening or loosening the screws with a screwdriver, it is necessary to force the screws to ...

The content and steps of low-voltage cabinet maintenance - Wiener The content and steps of low-voltage cabinet maintenance - Wiener

1: The overhaul should start from the low voltage side of the transformer. After the power failure of the low-voltage cabinet, clean the dust in the cabinet to check whether the connection between the bus bar and the down conductor is outstanding, whether the connection is heated or discolored, whether the cable head and the terminal pile head are strong and reliable, whether the grounding wire is corroded, and whether the terminal pile head is tightened. Everything secondary ...

Wiener plug-in busway features Wiener plug-in busway features

The plug-in busway has a high overload capacity The overload capacity of the bus duct is strong, depending on the high working temperature of the insulation material it uses, and the working temperature of 105C is selected for the insulation material used in the bus duct, and the radiation cross-linked flame retardant winding tape with a working temperature of more than 140 °C has been developed ( ...

Difference Between Busbar and Cable in Power System – Wiener Difference Between Busbar and Cable in Power System – Wiener

Busbar refers to a product made of copper (copper bar) and aluminum materials with high conductivity to transmit electric energy and have the ability to gather and distribute electricity. The main conductor used by the power station or substation to transmit electrical energy. Through it, the electrical energy output from generators, transformers or rectifiers is delivered to individual users.

Avoidable failures in busbar systems – Wienal Avoidable failures in busbar systems – Wienal

Cause of bus failure 1. The internal network of bus insulators and breaker sleeves caused by surface pollution 2. The voltage transformer installed on the bus and the current transformer between the bus and the circuit breaker are faulty 3. The support of the circuit breaker or isolation switch caused by the reverse operation ...

The main components of the Wiener bus system in the distribution cabinet are composed The main components of the Wiener bus system in the distribution cabinet are composed

(1) Busbar It is the basic element of the bus system, and there are a variety of standards, which can be installed with 5mm or 10mm thick rectangular busbar, double T type and triple T type busbar. The busbar is divided into 1-4 wires, 1 wire can be used with N or PE, 2 wires can be used together with N and PE, 3 wires are two-phase, and 4 wires can be used for three-phase ...

How is the Wiener bus system generally debugged in sections? How is the Wiener bus system generally debugged in sections?

Bus refers to the connection of voltage distribution devices at all levels in the substation, as well as the connection of electrical equipment such as transformers and corresponding distribution devices, most of which use bare wires or stranded wires with rectangular or circular sections. The role of the bus bar is to collect, distribute and transmit electrical energy. According to the structure, the bus bar is divided into hard busbar, soft ...

Features of busway power supply system - Wiener Features of busway power supply system - Wiener

1. Trunk power distribution system, simple wiring and reliable operation. 2. It is convenient to tap, and you can tap without cutting off the main power supply. Large power supply capacity up to 6300A current-carrying capacity. 3. High dielectric strength, strong overload, superior fire performance. Good heat dissipation performance, low impedance ...

The role of the busbar in the excitation system – Wiener The role of the busbar in the excitation system – Wiener

The bus PT is used to measure the bus voltage on the high-voltage side of the main transformer, and is used to assist in grid connection. Before starting the synchronous grid connection, the excitation system actively adjusts the terminal voltage according to the bus voltage measured by the bus PT, so that the voltage on both sides of the grid-connected switch is basically equal, which is convenient for the same period of grid connection. ...

Classification of the use of busway in different places - Vernal Classification of the use of busway in different places - Vernal

(1) General bus duct Non-flame retardant and non-fire-resistant bus duct selected for general load power distribution. In the event of a short circuit, it will be incinerated until it is connected to other busbars, which can easily cause fire accidents. (2) Flame retardant bus duct ...

Operating regulations for the use of busbars - Wiener Operating regulations for the use of busbars - Wiener

1. Charging to the bus should be carried out with a switch (bus tie, bypass or line switch) with snap-action maintenance that reflects various types of faults. Before charging the bus, it should be considered whether the system may be unstable if the charging bus trips, and if necessary, the active power flow of the relevant line can be reduced. ...

Busbar system reverse operation – Wiener Busbar system reverse operation – Wiener

(1) For the charging of the spare bus, when there is a bus tie circuit breaker, the bus tie circuit breaker should be used to charge the spare bus. At this moment, the maintenance device of the bus tie circuit breaker should be fully invested, and the relevant maintenance value and time limit should be changed to a smaller one, so as to facilitate the bus tie circuit breaker when there is a problem, the bus tie circuit breaker can quickly trip, cut ...

Lighting power busway service life - Wienal Lighting power busway service life - Wienal

The system consists of a current box, a bus body, a branch plug and device accessories. When the heat dissipation of conductive copper strip has been effectively improved, the contact between the copper strip and the inner wall of the tube is reduced, and the insulation resistance and anti-aging ability of the tube body are strengthened, so as to prolong the service life of the pipe body. The life of the tube far exceeds ...

What is tubular busbar and dense busbar - Wiener What is tubular busbar and dense busbar - Wiener

What is a tubular busbar Tubular bus bar is a kind of bus bar product with copper tube or aluminum alloy tube as conductor and external insulation. The tubular bus has the characteristics of high current (12000A), high mechanical strength, good insulation, wide application range, etc., ...

Bus load forecasting method and characteristics - Wiener Bus load forecasting method and characteristics - Wiener

Bus load guessing is a kind of power system load guessing, and the bus system load can be defined as the sum of the terminal load supplied by the main transformer of the substation to a relatively small power supply area, which is the refinement of the system load. Bus load guessing generally only carries out short-term load guessing, and the result is ...

Differences and differences between busway and other busbars Differences and differences between busway and other busbars

The busbar and busway are actually one open and one closed, and the other is not closed. The closed busway is referred to as the busway, that is, the busway is sealed The closure of the busbar, the closure of the busbar and the busway all refer to the same east...

Difference Between Fuse and Circuit Breaker – Vernal Difference Between Fuse and Circuit Breaker – Vernal

The principle of the fuse is to use the current to flow through the conductor to heat the conductor, and the conductor is ablated after reaching the melting point of the conductor, so the electrical appliances and circuits used for circuit maintenance are not burned out. It is an accumulation of heat, so it is also able to complete overload maintenance. Once...

Rectangular busbar, trough busbar, and tubular busbar analysis Rectangular busbar, trough busbar, and tubular busbar analysis

The rectangular bus has good heat dissipation performance and is easy to fix and connect. But its skin effect is quite large. In order to reduce the skin effect, the cross-sectional area of a single busbar should not exceed 1250 square millimeters. When the working current exceeds the promised current of a single bus, 2 to 4 rectangular buses can be used. Rectangular conductor a ...

Cooling method for dense busway – Wiener Cooling method for dense busway – Wiener

If the temperature of the dense busway is too high, a fault will occur. For the sake of insurance, it is necessary to know the heat dissipation method of the densely packed busway to prevent the impact of excessive temperature on the busway. Low-voltage transmission line conductors, wires, cables, branch dense busway, exposed conductive poles, punctured ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top