Inverter selection principle - Schneider

Create Date: 2024-8-30 12:03:23|Source: Schneider/Schneider

1. Select the inverter according to the load characteristics.

                               Inverter selection principle - Schneider

2. When selecting the inverter, the actual motor current value should be used as the basis for the selection of the inverter, and the additional power of the motor can only be used as a reference. Secondly, it should be fully considered that the output of the inverter contains higher harmonics, which will form the power factor and efficiency of the motor.

3. When the inverter wants to work with a long cable, the inverter should be enlarged by one gear or the output reactor should be installed at the output end of the inverter.

4. When the inverter is used to control several motors connected in parallel, it must be considered that the sum of the length of the cable from the inverter to the motor is within the allowable range of the inverter.
  ​
5. For some special applications, such as high ambient temperature, high switching frequency, high altitude, etc., it will cause the derating of the inverter, and the inverter needs to be enlarged and selected.

6. When selecting the inverter for high-speed motors, it should be slightly larger than the inverter of ordinary motors.

7. When the inverter is used in the pole changing motor, sufficient attention should be paid to selecting the capacity of the inverter, so that its maximum additional current is below the additional output current of the inverter.

8. When driving the explosion-proof motor, the inverter does not have an explosion-proof structure, and the inverter should be set outside the risk place.

9. When the inverter is used to drive the gear reducer motor, the application range is limited by the smooth method of the gear rolling part. Do not exceed the maximum speed tolerance.

10. When the inverter drives the winding rotor asynchronous motor, most of the existing motors are used. It is easy to overcurrent tripping due to ripple current, so it is necessary to select an inverter with a slightly larger capacity than usual.

11. When the inverter drives the synchronous motor, the output capacity is reduced by 10%-20% compared with the power frequency power supply.

12. Regarding the load with large torque fluctuation such as compressor and vibrating machine and the peak load condition of hydraulic pump, the working condition of the power frequency should be understood, and the inverter with additional output current greater than its maximum current should be selected.

13. When the inverter controls the roots blower, because its starting current is very large, it is necessary to pay attention to whether the capacity of the inverter is large enough when selecting the inverter.

14. When selecting the inverter, it is necessary to pay attention to whether its protection level matches the situation on site.

15. Single-phase motors are not suitable for inverter drive. If there is only the high reliability of the inverter body, and the inverter selection and capacity matching are not appropriate, the frequency conversion speed regulation system composed of it cannot reach high reliability, or even cannot work, so how to ensure the normal and efficient operation of the frequency conversion adjustment system? We need to ensure that the capacity of the inverter is matched. First of all, according to the nature of the load, the correct selection of the type of inverter.

The general criterion is what the nature of the load characteristics with what characteristics of the inverter.

(1) Constant torque production equipment - within the speed control range, the load torque is basically stable and unchanged. A frequency converter with constant torque performance should be selected. It can only be overloaded to maintain 150% additional current for 1 minute.

(2) Square torque production equipment - within the speed regulation range, the load torque is proportional to the square of the speed, that is, M∝n2, centrifugal fan, water pump is its typical representative. The inverter with M∝n2 characteristics can have a small overload, and the additional current of 110%-120% is overloaded for 1 minute.

(3) Constant power load production equipment - within the speed regulation range, the speed is low and the torque is large; The speed is high and the torque is small, and typical equipment such as machine tools and winding mechanisms.
More on that
Safety PLC is different from ordinary PLC Safety PLC is different from ordinary PLC

A safety PLC differs from conventional PLCs in that it needs to be certified for safety by a third-party professional organization and meet stringent international standards for safety and reliability. There is a need for a thorough systematic approach to the planning and testing of safety PLCs. TUV*** in Germany and FM*** in United States ...

Schneider improves plant performance with automated control Schneider improves plant performance with automated control

1. Engineering planning one by oneWith data at their fingertips and intelligent and sensitive functions, engineers can easily plan and test equipment, improve process availability, and easily complete system integration together – ultimately reducing the planning time by up to 25%. ...

Schneider inverter control circuit Schneider inverter control circuit

1. What is a control loop? The network that supplies the control signal to the main circuit that supplies power to the asynchronous motor (voltage and frequency can be adjusted) is called the control loop. Second, the composition of the control loop The control circuit is controlled by the frequency ...

Introduction to Schneider inverter fault code and maintenance method Introduction to Schneider inverter fault code and maintenance method

1. If the fault code presented on the Schneider inverter is AnF, it means that the load of the inverter has slipped, that is, the speed of the encoder does not match the initial value. First of all, we need to check whether the parameters of the motor are stable and the size of the load, ...

Schneider circuit breakers, contactors, thermal relays selection Schneider circuit breakers, contactors, thermal relays selection

In daily work, the combination of circuit breaker, contactor and thermal relay is the most common combination of motor power supply circuit, and the circuit breaker is generally the short-circuit instantaneous action of magnetic maintenance, the contactor realizes relay logic control, and the thermal relay overload maintenance. The parameter selection method of these three kinds of gas parts is as follows: ( ...

Schneider Electric executive support merger software Saas company Schneider Electric executive support merger software Saas company

MergerWare has raised an undisclosed amount of money ahead of its Series A funding round, an executive told TechCircle. The Company provides software solutions to help integrate mergers and acquisitions-related businesses. The funding came from electrical equipment manufacturer Schneider Electric (Schneider ...

Schneider inverter maintenance inspection steps Schneider inverter maintenance inspection steps

1. Check whether the appearance of the inverter is in good condition, including whether the indicator light is in normal operation, whether the task control function of the operation panel is complete, and carefully observe the appearance of the inverter in operation, and do the corresponding recording operation; When repairing the inverter, check whether the voltage value and current value exceed the promised ...

MiCOM P5 Series Intelligent Relay Protection Device P5 Series New Product: P5T30 MiCOM P5 Series Intelligent Relay Protection Device P5 Series New Product: P5T30

MiCOM P5 Series Intelligent Relay Protection Device P5 Series New Products: P5T30 Schneider Electric Powerlogic P5 Series Transformer Differential Protection New Product P5T30 improves the gap in the differential protection of motor generators in the P5 series, making the P5 series more widely applicable. In appearance, mechanical ...

For the first time, Schneider presents a new lightweight MES in packaging For the first time, Schneider presents a new lightweight MES in packaging

Packaging Lightweight MES is a production line and workshop-level digital management and processing solution created by Schneider Electric based on more than 20 years of experience in packaging machine automation, combined with the digital transformation needs of the FMCG (Consumer Packaged Goods) profession, which can be widely used in food and beverage, life ...

Precautions for motor operation over 60Hz - Schneider Precautions for motor operation over 60Hz - Schneider

What problems should be paid attention to when the motor works beyond 60Hz? The following precautions should be taken when operating beyond 60Hz (1) Machinery and equipment should have sufficient potential to work at this speed (mechanical strength, noise, vibration, etc.). (2) ...

Schneider inverter series at a glance Schneider inverter series at a glance

1. ATV11 series The Schneider ATV11 series is primarily used in three-phase asynchronous motor inverters with a power range of 0.18 to 2.2 kW. 2. ATV12 series ATV12 Schneider inverter for power scale 0.18k...

The reason for the inverter trip - Schneider The reason for the inverter trip - Schneider

Whenever the inverter is down due to a problem, a problem code will appear. The most common causes are overcurrent, overvoltage, inverter temperature, etc. It's a good idea to find an explanatory book with specific questions to be asked about. 1. Overload jump ...

Schneider diode selection experience and substitution method Schneider diode selection experience and substitution method

1. Selection of detection diode Point-contact germanium diodes are generally used for detection diodes, such as 2AP series. When selecting, the detection diode with high operating frequency, small reverse current and large forward current should be selected according to the specific requirements of the circuit. Although the detection and rectification of ...

Motor encoder alarm causes and solutions - Schneider Motor encoder alarm causes and solutions - Schneider

1. The cause of the problem (1) Wiring fault; (2) electromagnetic interference; (3) Encoder hardware damage caused by mechanical vibration; (4) Pollution caused by the on-site environment; 2. Troubleshooting (1) Check the wiring and exclude ...

Input/output pins P0, P1, P2, P3 functions Input/output pins P0, P1, P2, P3 functions

P0.0——P0. 7 : Port P0 is an 8-bit open-drain bidirectional I/O port. When visiting off-chip memory, it is time-shared for a low-8-bit address and an 8-bit bidirectional data bus. When EPROM is programmed, the instruction byte is input by P0, and when the program is verified, it outputs ...

Schneider maintains the UPS power supply to extend the service life Schneider maintains the UPS power supply to extend the service life

Take charge of the basic knowledge of UPS power supply, read the equipment manual attentively, clarify the meaning of various warning signals, warning codes, command lights, and the causes of occurrence and how to deal with them to understand the effects of various switches and buttons of the equipment. Understand the various operations in charge of UPS power supply, understand the connection connection, and understand the method of substitution ...

Schneider inverter external potentiometer connection Schneider inverter external potentiometer connection

The two wires are connected to the resistor, and the other wire is connected to the conditioning terminal. The red thread is attached to the blackhead and inserted in a small hole. Connect both ends of the IR potentiometer to +10V and ACM, and slide the termination to the voltage input terminal AVI. ...

Schneider instrumentation maintenance precautions Schneider instrumentation maintenance precautions

1. When installing and adjusting the appearance, the original status should be recorded for rehabilitation. 2. When repairing the appearance of fine instruments, if you accidentally bounce small parts away, you should first determine the direction where you can fly.

Suppression of higher harmonics of inverter - Schneider Suppression of higher harmonics of inverter - Schneider

1. About the management of higher harmonics on the output side of the inverter The magnetic noise skills brought about by the communication harmonic components contained in the output waveform controlled by PWM control have been increasingly used in various inverters, such as the selection of higher frequency switching components, the installation of filter devices at the output end of the inverter, etc.

Analysis of common problems of Schneider inverter Analysis of common problems of Schneider inverter

1. Use the analog output port to indicate the motor frequency, when the motor frequency is 50Hz, why is the output only 16mA? Because the maximum output frequency parameter of the inverter is "TFR", the factory default value is 60Hz. So when the inverter output is 50Hz, the analog output is 16mA. At this time, only ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top