OL2 is the inverter overload alarm, check whether it is a real overload or a false overload.
1. Test whether the output current of the inverter exceeds the rated current of the inverter, if it exceeds it, it may be the mechanical reason, if it does not exceed the inverter detection circuit is broken, and the false overload is reported.
2. The OL2 fault code of the Yaskawa G7 inverter indicates that the inverter is overloaded.
The load is too large, and the acceleration and deceleration time is too short. The V/f characteristic voltage is too high. The power of the inverter is too small.
Additional Information:
1. If there is a problem with the load, it is a problem with the motor, such as the lack of oil in the bearing, the damage to the bearing, the burning of the winding, etc., and there is a situation that the power of the motor is small, and it is more difficult to drag the load.
2. It is the problem of the inverter, for example, the output of the inverter is out of phase, or there is a problem with the wiring, resulting in the lack of phase in the motor.
3. It is the false alarm of the inverter, for example, the inverter encounters electromagnetic interference, resulting in its false alarm, at this time, it is necessary to take harmonic suppression measures for the inverter, such as the special filter of the inverter, the special reactor of the inverter, the filter magnetic ring, the isolation transformer, the grounding, etc.
4. The inverter itself is faulty, and it is recommended to find a professional maintenance engineer to detect it.
|
More on that
|
What are the fault codes of Yaskawa inverter
The fault codes of Yaskawa inverters are as follows:
OC overcurrent;
PG wiring is disconnected or wiring is incorrect;
GF output ground fault ground short circuit ;
PUF fuse blowing fuse blowing ;
OV Main circuit overvoltage Main circuit overvoltage ...
|
|
Yaskawa inverter wiring attention
Attention to the wiring of the inverter
1. The inverter itself has strong electromagnetic interference, which will interfere with the work of some equipment, so we can add a cable sleeve to the output cable of the inverter.
2. The control line in the inverter or control cabinet is at least 100mm away from the power cable, etc.
...
|
|
Yaskawa inverter - the selection of high-voltage inverter precautions
1 Disadvantages of choosing too high a voltage level
Choosing too high a voltage level results in too high an investment and a long payback period. With the increase of the voltage level, the insulation of the motor must be improved, so that the price of the motor increases. The increase of the voltage level increases the number of series connections of power semiconductor devices in the inverter, ...
|
|
Parameterization steps of Yaskawa inverter
1. Enter the parameter menu, select the "Motor Current" item, and set the rated current of the motor In
2. Select the "Overload Protection" item to enter a form: select to enter the overload fixed value multiplier. The overload fixed value magnification range is 100-700%, just enter the number between 100 and 700.
|
|
How to wire Yaskawa servo motor B1B2?
1. First of all, connect the terminal block of Yaskawa servo B1B2, in which the B1 terminal receives the power supply and the B2 terminal receives the signal;
2. Then, connect the terminal block of Yaskawa servo B1B2, wherein B1 terminal receives power supply, and B2 terminal receives signal;
3. After the wiring is completed, ...
|
|
Yaskawa manipulator use specification
Yaskawa manipulator specification
It must be trained before the job and can only be operated after qualifying. Untrained personnel are not allowed to operate the manipulator.
BEFORE OPENING, CHECK WHETHER THE AIR SOURCE OF THE MANIPULATOR IS ENERGIZED, ADJUST THE AIR PRESSURE OF THE PRESSURE VALVE BETWEEN 0.6MPA AND 0.8MPA, AND CHECK WHETHER THE VOLTAGE IS NORMAL.
What is ...
|
|
Yaskawa inverter - how to check the mechanical system failure of elevator failure
1. Failure of mechanical system
(1) The common fault phenomena and causes of mechanical systems are as follows
1. Due to poor lubrication or lubrication system failure, the rotating parts of the parts are seriously heated and worn or the shaft is held, resulting in the destruction of the parts of the rolling or sliding parts.
2 ...
|
|
Common faults of Yaskawa inverters
The switching power supply is damaged
Switching power supply damage is the most common fault of many inverters, usually caused by short circuit in the load of switching power supply, in the design of switching power supply circuits of many inverters, Yaskawa inverter is relatively successful.
OH failure
Old...
|
|
Summary of Common Faults and Solutions of Yaskawa Robots and Accessories (9-17)
09. Robot oil leakage?
Cause:
1. Improper maintenance;
2. Corrosive parts damage, etc.
Solution: Check the location of the oil leak and confirm the parts caused by the oil leak. It is possible to accurately determine the parts caused by oil leakage by checking drawings, etc.
10. Robot ...
|
|
Analysis of fault codes of Yaskawa inverter
Analysis of the fault code of Yaskawa inverter, for reference only:
OC Overcurrent The output current of the inverter exceeds the overcurrent detection value ·
GF grornd Favlt Grounding The ground current on the output side of the inverter exceeds 50% of the rated output current of the inverter
...
|
|
How to choose a Yaskawa inverter model
1. Specifications and parameters of the motor
The inverter drives the motor during use, so the inverter can be selected from the perspective of the motor to select the model and specification. First of all, we must first understand the specifications and parameters of the motor. You can use Yaskawa inverter ...
|
|
Analysis of the causes of the alarm of Yaskawa servo drive 300
1, Maybe the connection of the external resistor is bad, falling off and disconnecting will cause an alarm, we can check the wiring.
2. It may be that the jumper wire of the resistor connection terminal B2-B3 falls off, and then check if the jumper wire falls off.
3. It may be that the resistor capacity ...
|
|
What are the applications of Yaskawa inverter?
1. Compressor load
Compressors are also widely used loads. Low-pressure compressors are widely used in various industrial sectors, and high-pressure large-capacity compressors are widely used in steel (such as oxygen generators), mines, fertilizers, and ethylene. The use of frequency conversion speed regulation, all bring small starting current, ...
|
|
Analysis of the causes of Yaskawa servo drive alarm code 040
1. It may be that the capacity of the servo unit does not match the capacity of the servo motor.
2. It may be that the servo unit is faulty.
3. It may be outside the range of parameter settings.
4. It may be that the set value of the electronic gear ratio is outside the set range.
...
|
|
Wiring method of Yaskawa A1000 inverter
First, the wiring of the main circuit
1. The power supply should be connected to the R, S, and T terminals at the input end of the inverter, and must not be connected to the output terminal (U, V, W) of the inverter, otherwise the inverter will be damaged. After wiring, the fragmented wires must be cleaned, and the fragmented wires may cause abnormalities.
...
|
|
Causes and solutions of Yaskawa servo drive fault code R10
1. The acceleration/deceleration time constant is too small. Increase the acceleration/deceleration time constant.
2. The torque limit value set by the controller is too small. Increase the torque limit value.
3. The motor cannot start due to the insufficient torque caused by the drop in power supply voltage.
4. Check the power capacity.
...
|
|
Yaskawa Servo Motor – The difference between a servo motor and a stepper motor
1. Different control methods
Stepper motor: The rotation angle is controlled by controlling the number of pulses, and one pulse corresponds to one step angle.
Servo motor: The angle of rotation is controlled by controlling the length of the pulse time.
2. The workflow is different
Stepper Motor: Stepper ...
|
|
Introduction to Yaskawa servo motor
Yaskawa servo motor, also known as YASKAWA Yaskawa servo motor, is an automatic control system, which can control the position, orientation, status and other outputs of the target, and can change with the change of the target input value (or given value). It can be divided into AC servo motor and DC servo motor ...
|
|
Yaskawa inverter reports Uv1 fault code solution
Yaskawa inverter Uv1 fault name: main circuit undervoltage
If the operation command is not entered (the inverter is stopping), the following conditions occur.
1. The DC voltage of the main circuit is lower than the set value of L2-05 (the detection value of the undervoltage (UV) of the main circuit).
2. 200V class: about 190V ( ...
|
|
Analysis of the reasons for Yaskawa servo drive alarm 410
1. The input power of Yaskawa drive drops, resulting in an internal undervoltage alarm
2. The drive power supply failure causes Yaskawa Drive to detect an undervoltage fault
3. Yaskawa servo unit fuse blows
4. Yaskawa servo unit failure leads to undervoltage failure
5. Servo drive detection circuit ...
|
|