1. The level gauge is adjusted normally, and it is found that the float is "absorbed" for a period of time in a certain position after it is put into use. This is mainly caused by the level gauge passing through the steel platform device and being spaced too close to the steel plate. Therefore, it is necessary to pay special attention to the distance between the wall of the level gauge connecting pipe and the cutting edge of the platform when passing through the steel platform device. According to the field application experience, this spacing of about 100mm can ensure that the magnetic float is not affected.
2. During the on-site adjustment, it will be occasionally found that the float is not sensitive enough to move up and down. This is mostly caused by improper level gauge devices, and it is necessary to pay attention to whether the center of the upper and lower flanges can be in a line and whether it can be perpendicular to the degree surface. Generally speaking, the angle between the plane and the degree plane should not be less than 87 degrees, if the deviation is large, it may affect the smooth movement of the float.
3. When the level gauge is put into use on site, special attention should be paid to opening the upper gate valve first, and then opening the lower gate valve. This is due to the fact that the bottom of the level gauge connecting pipe is equipped with a thrust spring to maintain the float, otherwise, the action of large differential pressure may break the float and cause the level gauge to be inoperable.
4. During the use of the level gauge, if the output signal produces frequent disturbances or interference pulses, it is necessary to check whether the signal cable shield can be firmly grounded, and whether the working connection resistance can meet the requirements. If the interference is still not completely resolved, a signal isolator can be used.
5. After the level gauge is put into use for a period of time, it is difficult for the float to float and the float is not sensitive. This is fundamentally due to the magnetic float being stained with iron filings or other dirt. You can drain the medium first, and then take out the float to eliminate the iron filings or other dirt on the magnetic float.
6. If the closed glass tube for on-site instruction is broken due to transportation or other reasons, the domestic glass tube can be replaced. But it's best to be able to vacuum. Also pay attention to whether the glass tube can be vertical, so as not to affect the indication of the indicator.
7. Pay special attention to the use of the level gauge, do not use a strong magnet to pull the float up and down outside the connecting tube to stop the inspection, otherwise it will cause the magnetization of the magnetic float and change the polarity, so that the magnetism of the float will be weakened, making it difficult to work normally.
|
More on that
|
Technical characteristics of the RKC thermostat
The core control algorithm of the thermostat is PID control, P (Proportional) + I (Integral) integral + D (Differential) differential control. In addition to the traditional PID control algorithm, RKC also has ON-OFF control, self-tuning parameter control, adaptive parameter control and other algorithms, temperature control ...
|
|
Features and technical specifications of RKG thermostats
peculiarity
1. Thermocouple, RTD, analog and other signals are freely input, and the range can be set freely.
2. The software adjusts the full degree, the cold end measures the temperature separately, the amplifier is self-stabilizing, and the display accuracy is better than 0.5%FS.
3. Fuzzy theory combined with traditional PID method, fast control ...
|
|
Steps for the correct adjustment of the thermostat
1. First of all, determine the set temperature of the thermostat and make sure that it is the same as the temperature you need.
2. Recognize the operating form of the thermostat, usually there are two forms of cooling and heating, and choose the corresponding form according to the demand.
3. Acknowledging the operating condition of the thermostat, usually with active ...
|
|
RKC Temperature Control Meter - How to set the temperature control meter
1. Turn on the power supply of the smart thermostat, and the temperature displayed on the screen is the temperature at that time. Because the sensor is not in contact with other devices, but is directly exposed to the air clock, this is the current temperature: 31 degrees Celsius, which is not too hot.
2. At the bottom right of the display screen is the "starting temperature" setting ...
|
|
RKG thermostat - an introduction to the relevant knowledge of temperature controllers
The temperature controller is an electrical switchgear that controls the temperature of an air-conditioned room. The temperature range in the air-conditioned room controlled by the temperature controller is generally 18°C--28°C. The temperature controller commonly used in window air conditioners uses the principle of pressure to push the contacts on and off. Its structure consists of bellows ...
|
|
RLC Thermostat - Fault and Troubleshooting of Vapor Pressure Temperature Controller
Faulting and troubleshooting of vapor pressure temperature controllers
(1) Common faults and common faults of the vapor pressure type temperature controller include contact burning or adhesion, failure of the mechanical transmission mechanism and leakage of temperature sensor in the temperature sensing tube. Its detection method is: put the thermostat knob in a parking position, and use ...
|
|
RLC Thermostat - Introduction to the function of mechanical temperature control
1. The temperature setting is set by the knob, which is convenient and intuitive 2. It can be directly installed on the standard junction box on the wall.
3. Beautiful appearance and reliable performance.
4. The switch adopts toggle type, which feels comfortable and has a long life.
5. It can control two-wire or three-wire electric (ball...
|
|
Physical and chemical RK C thermostat - dry-type transformer thermostat shows fault handling methods
1. The dry-type transformer thermostat does not appear
Cause of failure: (1) The power supply of the thermostat is not connected; (2) The fuse is blown out.
Solution: (1) Turn on the power supply; (2) Replace the fuse.
2. The dry-type transformer thermostat shows that one or three phases are shining and showing "-OP-"
...
|
|
RKC Thermostat - How to Choose a Hot Spot Couple?
The selection of thermocouples should be based on comprehensive considerations such as the scale of the operating temperature, the required accuracy, the atmosphere of the application, the performance of the measurement target, the response time and the economic benefits.
1. Selection of measurement accuracy and temperature measurement scale
1) The operating temperature is 1300-1800 °C, and the accuracy is required to be more accurate than ...
|
|
RRC thermostat - how to adjust the smart thermostat
1. Set temperature: Press the SET button to set or view the temperature set point. Press the SET button digital tube characters to start flashing, indicating that the instrument has entered the setting state, press the △ key to increase the set value, press the ▽ key to decrease the set value, long press the △ key or ▽ key The data will change rapidly, press the SET key again ...
|
|
Common faults and solutions of intelligent temperature controllers - RTC
Master the common problems of several common intelligent temperature controllers, and solve them by yourself when you encounter problems, and you don't need to spend time and effort to find someone to repair, the common problems are as follows:
1. Heating for a period of time, the temperature does not change. Ambient temperature (e.g., room temperature 25°C) is displayed at all times
...
|
|
RKC Thermostats – How to Choose a Thermocouple?
The selection of thermocouples should be based on comprehensive considerations such as the operating temperature range, the required accuracy, the operating atmosphere, the performance of the measured object, the response time and the economic benefits.
1. Selection of measurement accuracy and temperature measurement range
1) The operating temperature is 1300-1800°C, and the accuracy is required to be more accurate than ...
|
|
RKC thermostat - how to set the parameters of the thermostat?
1. Lower limit deviation alarm setting: press the SET key to select and display "SLP", the green display screen displays the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. This parameter indicates the difference between the alarm point and the master setpoint.
2. The upper limit deviation alarm is set ...
|
|
RKC thermostat - what are the anti-interference measures of the instrument?
1. Electromagnetic induction (refers to the coupling of magnetism). There is a strong alternating magnetic field in the surrounding space of high-power transformers, AC motors, high-current power grids, etc., and the closed loop formed by the lines of the control system (detection, transmission, conversion, regulation, calculation, execution, auxiliary, display, etc.) is located in the ...
|
|
What should I pay attention to when setting up my RKC thermostat?
Wiring Warning:
If the instrument fails or an error occurs, which can cause a system failure, an external protection circuit is installed to prevent such accidents:
In order to prevent damage or failure of the instrument, choose an appropriate fuse to protect the power cord and input and output lines from strong power shocks.
Power supply ...
|
|
RKC Thermostat How to properly select and use a pressure sensor
High-temperature melt pressure sensors, transmitters, and high-temperature melt pressure gauges are special equipment in extrusion processing.
On the production line, melt pressure sensors play an important role in improving melt quality, increasing production safety and protecting production equipment.
Use...
|
|
What are the common devices for RKC thermostats – digital displays?
In a variety of electronic control equipment, digital display has become an indispensable and important link. The electronic devices and corresponding driving circuits used for digital display are called digital displays.
Commonly used digital displays include glow digital tube displays, fluorescent digital tube displays, projection ...
|
|
RLC Thermostat – Instructions for installation and use of pop-up thermostats
1. Grounding method: It is connected to the grounding metal parts of the equipment through the metal cover of the thermostat.
2. The thermostat should work in the general indoor environment where the relative humidity of the air is not more than 90%, and there are no corrosive gases, flammable gases and conductive dust.
3. The thermostat adopts contact ...
|
|
RK Level Gauge - Introduction to the characteristics of float level gauge
It is suitable for measuring the level and interface of the liquid medium in the container. In addition to on-site instructions, it can also be equipped with remote transmitters, alarm switches, and detection functions.
The indication is novel, the reading is intuitive, eye-catching, and the direction of the observation indicator can be changed according to the user's needs.
Large measuring range ...
|
|
RKC Level Gauge - Preservation and storage of float level gauges in daily use
1. To avoid damage to the instrument, pay attention to the correct protection method: in order to ensure the accuracy of the instrument and avoid damage to the instrument, try not to use the protection instrument of isolator or other isolation devices. If you have to do it, you should also pay attention to the careful selection, determine the isolation solution, and wash the isolation film correctly, ...
|
|