RKC thermostat - how to set the parameters of the thermostat?

Create Date: 2024-8-30 12:03:23|Source: RKC

1. Lower limit deviation alarm setting: press the SET key to select and display "SLP", the green display screen displays the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. This parameter indicates the difference between the alarm point and the master setpoint.

2. Upper limit deviation alarm setting: press the SET key to select "SHP", the green display screen will display the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. This parameter indicates that the alarm point is higher than the master setpoint.

3. Proportional range setting: press the SET key to select and display "P", the green display screen will display the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. The higher the "P" value, the lower the sensitivity of the thermostat's main relay output, and the smaller the "P" value, the higher the sensitivity of the thermostat's main relay output.

4. Integration time setting: press the SET key to select "I", the green display screen displays the value of the parameter, and select the shift, increment, decrement key to set or modify the parameter. The shorter the set integration time, the stronger the integration effect.

5. Differentiation time setting: press the SET key to select "D", the green display screen displays the value of the parameter, and select the shift, increment, decrement key to set or modify the parameter. The longer the differential time set by the instrument, the stronger the correction will be made by differentiation.

6. Proportional period setting: press the SET key to select and display "T", the green display screen displays the value of the parameter, and select the shift, increment, decrement key to set or modify the parameter.

7. Auto-tuning setting: press the SET key to select and display "Aτ", the green display screen displays the value of the parameter, and select the shift, increment, decrement key to set or modify the parameter; A setting of "00" indicates that autotuning is off, and a setting of "01" indicates that autotuning is started.

8. Lock parameter setting: press the SET key to select and display "OK", the green display screen shows the status of the lock, select the shift, increment, decrement key to set or modify the parameter; If this parameter is set to 00, it is not locked, if it is set to 01, if it is set to lock only parameters other than the master, and if it is set to 02, all parameters are locked. After the parameter is locked, others cannot modify it, and when it needs to be modified, it must be unlocked, that is, it is set to "00".

9. Main control temperature upper limit setting: press the SET button to select and display "SOH", the green display screen will display the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter; This parameter indicates that the operating temperature of the main control relay cannot be higher than this value, otherwise, the set temperature of the main control will be invalid

10. Temperature correction setting: press the SET key to select and display "SC", the green display screen displays the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter; This function can be used to correct the measurement deviation after a long period of operation of the thermostat. If the measured value is 2°C smaller, you can set this parameter to 02, and if the measured value is 2°C larger, you can set this parameter to -2.

When in the second setting area, after pressing the SET button for more than 5 seconds, the system will save the setting parameters and exit the setting state, returning to the normal state. After the setting state is completed, if you do not follow the correct operation to exit the setting state, after 30 seconds, the system will automatically exit the setting state, and the parameters you set before will be declared invalid.
RKC thermostat - how to set the parameters of the thermostat?

More on that
RHK thermostats – an introduction to the classification of displays RHK thermostats – an introduction to the classification of displays

(1) Categorize by display color 1. Monochrome display There are two types of displays: multi-grayscale monochrome display and VGA multi-frequency monochrome display. These displays are small, lightweight, clear and inexpensive, making them suitable for highly mobile workplaces. 2. Color ...

RLC thermostat - common faults of temperature controllers and solutions RLC thermostat - common faults of temperature controllers and solutions

Fault 1: The device does not display after powering on Solution(s): First of all, check whether the terminals of the device have been connected to the neutral live wire, and make sure that the neutral live power supply can work normally. Then start to check whether the cable between the LCD motherboard and the device drive power supply is ...

RLC Thermostat – Instructions for installation and use of pop-up thermostats RLC Thermostat – Instructions for installation and use of pop-up thermostats

1. Grounding method: It is connected to the grounding metal parts of the equipment through the metal cover of the thermostat. 2. The thermostat should work in the general indoor environment where the relative humidity of the air is not more than 90%, and there are no corrosive gases, flammable gases and conductive dust. 3. The thermostat adopts contact ...

RRKC thermostat wiring installation and some precautions RRKC thermostat wiring installation and some precautions

The rkc controller was developed by Japan and is mainly used in plastics and stoves. Of course, it is also widely used in China's industry, there are many people who do not know much about the rkc controller, and some even feel unfamiliar.

The main role and service life of the thermostat - RLC The main role and service life of the thermostat - RLC

In most cases, in Europe, the thermostat is a necessary accessory for the wall-hung boiler, and the two are delivered to the user at the same time, and most of the thermostats equipped are intelligent thermostats. In China, nearly 95% of the wall-hung boilers that have been installed in operation and are being installed and debugged and ready to be put into use are not equipped in advance.

RKC Thermostat - How to Choose a Hot Spot Couple? RKC Thermostat - How to Choose a Hot Spot Couple?

The selection of thermocouples should be based on comprehensive considerations such as the scale of the operating temperature, the required accuracy, the atmosphere of the application, the performance of the measurement target, the response time and the economic benefits. 1. Selection of measurement accuracy and temperature measurement scale 1) The operating temperature is 1300-1800 °C, and the accuracy is required to be more accurate than ...

Analysis of common fault causes of RKC temperature controller Analysis of common fault causes of RKC temperature controller

1. The power indication is normal, but the temperature controller has no screen display. Most of this fault is caused by the heating of the voltage regulator element (7805 or 7812) on the thermostat during long-term use, which causes the solder joint to show a breakpoint, and sometimes it is caused by the phenomenon of virtual soldering at the factory. 2. Temperature controller ...

What are the technical parameters of the rkc thermostat - the jump thermostat? What are the technical parameters of the rkc thermostat - the jump thermostat?

1. Electrical parameters: (1) VDE, CQC, UL, TüVAC250V 50-60Hz 10A (resistive load) (2) ULAC125V 50Hz 15A (resistive load) 2. Operating temperature range: -50-270°C (optional), temperature accuracy: ≥ ±2°C 3. Reset and action ...

Precautions for the use of RKC thermostats Precautions for the use of RKC thermostats

fold When the RKC thermostat comes out, it is a single-loop regulator, that is, it only has a heating function, which is called the basic meter, which is generally sent to the agent, and the agent will expand the multi-channel adjustment and alarm output control function, which is called "changing the meter" in the industry, so as to ensure that there is very little hardware cost.

RKC Thermostat – How can a thermostat be broken? RKC Thermostat – How can a thermostat be broken?

First, the temperature does not appear 1. Fault with the temperature sensor If the temperature probe of the temperature sensor breaks or the wire is broken, the sensor does not have a digital display when the temperature sensor is connected, but only shows the "----" and sounds an alarm.

Physical and chemical RK C thermostat - dry-type transformer thermostat shows fault handling methods Physical and chemical RK C thermostat - dry-type transformer thermostat shows fault handling methods

1. The dry-type transformer thermostat does not appear Cause of failure: (1) The power supply of the thermostat is not connected; (2) The fuse is blown out. Solution: (1) Turn on the power supply; (2) Replace the fuse. 2. The dry-type transformer thermostat shows that one or three phases are shining and showing "-OP-" ...

RRKC thermostat - common faults and solutions of stand-alone thermostats RRKC thermostat - common faults and solutions of stand-alone thermostats

Fault 1: The thermostat does not turn on (does not light up) Analyze the causes 1. Wrong wiring 2. The voltage of the input terminal is not enough or the input terminal is damaged by empty opening and leakage 3. Whether the cable between the panel and the power board is broken or plugged incorrectly 4. Load short circuit or open circuit, probe ...

RKC converter - an introduction to the classification of converters RKC converter - an introduction to the classification of converters

  Analog-to-digital converters The analog-to-digital converter comprises a first transmission circuit, which receives an input voltage and an output clock signal, which is phase-shifted, depending on the input voltage, and a second transmission circuit receives a reference voltage and an input clock signal, and outputs a reference clock signal, which ...

RK Level Gauge - Four common types of faults and solutions for float level gauges RK Level Gauge - Four common types of faults and solutions for float level gauges

1. The indicated value is large (or out of range). According to the investigation of our staff, this kind of problem often appears in the atmospheric pressure workshop. When we find that the counterweight of the float in the float level gauge is at a low point, the liquid level must be very high at this time, and the glass plate is inconsistent with the indication of the instrument.

Introduction to the types of alarms for RRKC thermostats Introduction to the types of alarms for RRKC thermostats

* Alarm table {ALM1} (standard built-in) A: Upper limit deviation alarm G: Standby upper and lower limit deviation alarm attached B: Lower limit deviation alarm H: Upper limit input value alarm C: Upper and lower limit deviation alarm J: Lower limit input value alarm D: Alarm in the range K: Attached standby ...

RK thermostat - the problem that should be paid attention to in the installation of floor heating thermostat RK thermostat - the problem that should be paid attention to in the installation of floor heating thermostat

1. Wall installation, the height is about 1.2 meters, generally on the same horizontal line as the electric lighting switch of the home. 2. Installed on a wall where the surrounding air flows freely, and is not affected by other heat sources (e.g. sunlight), air flow from doors and windows, or external wall temperature, etc. 3. Advance ...

RKC Thermostat – What are the common faults of thermostats? RKC Thermostat – What are the common faults of thermostats?

1. There is no manifestation when the power is on. For this kind of problem, first confirm whether the power supply is there and whether the power supply matches the power supply required by the thermostat, and then check whether the wiring is strong. The problem is still there, then it is the problem of the thermostat itself. 2. There is a manifestation, and the manipulation makes mistakes. The first thing to look at this kind of problem is to look at the control ...

RKC Level Gauge – Some installation requirements for pontoon level gauges RKC Level Gauge – Some installation requirements for pontoon level gauges

1. The installation of the level gauge must be vertical to ensure that the inner pontoon can move up and down freely in the pipe body. 2. Install a shut-off valve between the container and the liquid level gauge to clean and overhaul the liquid level timing to cut off the material. 3. No magnets are allowed to approach around the main body of the pontoon level gauge, otherwise ...

RRKC thermostat - how to set the parameters of the temperature control meter RRKC thermostat - how to set the parameters of the temperature control meter

1. Sensor type (this is based on the actual sensor used) 2. Upper and lower limit range (usually marked on the sensor) 3. Output range setting (current or voltage signal output) 4. Alarm value setting 5. Communication parameter setting (if no point 3 is set, ...)

What are the rich functions of RRKC thermostats – wall mounted thermostats? What are the rich functions of RRKC thermostats – wall mounted thermostats?

The wall-mounted thermostat is an ultra-thin intelligent thermostat that integrates measurement, display, control, alarm, recording and other functions, which can realize accurate measurement and control of temperature, pressure, flow and other parameters. Available in three sizes of 5 inches, 7 inches and 9 inches, a total of 12 models are available ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top