The inverter controls the speed of the AC motor - Senland

Create Date: 2024-8-30 12:03:23|Source: Hope Sunland

The rotational speed of an induction AC motor (henceforth referred to as a motor) is approximately determined by the number of poles and frequency of the motor. The number of poles of the motor is fixed by the operating principle of the motor. Since the pole value is not a continuous value (a multiple of 2, e.g. the pole number is 2, 4, 6), it is generally not suitable to adjust the speed of the motor by changing the value.

                               The inverter controls the speed of the AC motor - Senland

In addition, the frequency can be adjusted outside the motor and then supplied to the motor, so that the rotation speed of the motor can be controlled freely.

Therefore, the inverter for the purpose of controlling the frequency is the preferred equipment for motor speed regulation equipment.

Conclusion: Changing the frequency and voltage is the best way to control the motor

If you only change the frequency but not the voltage, the motor may burn out due to overvoltage (overexcitation) when the frequency drops. Therefore, it is necessary to change the voltage of the inverter at the same time as changing the frequency. When the output frequency is above the additional frequency, the voltage cannot be further added, and the maximum voltage can only be equal to the additional voltage of the motor.

Power Frequency Power Supply: Power supply provided by the grid (commercial power supply)

Starting current: The output current of the inverter when the motor is running at the beginning of the operation

The starting torque and maximum torque when driven by the inverter are less than those driven by direct industrial frequency power supply

The starting and acceleration impact of the motor is large when the power frequency power supply is used, and when the power supply is used by the inverter, these shocks are weaker. A large starting current will occur when the power frequency is directly started. When the inverter is used, the output voltage and frequency of the inverter are gradually added to the motor, so the starting current and impact of the motor are smaller.

In general, the torque generated by the motor decreases as the frequency decreases (speed decreases). Practical data for the reduction is illustrated in some inverter manuals.

The lack of torque in the motor at low speeds will be improved by using the inverter operated by magnetic flux vectoring, and the motor can output sufficient torque even at low speeds.

3. When the speed of the inverter is adjusted to a frequency greater than 50Hz, the output torque of the motor will decrease

The general motor is designed and manufactured with a voltage of 50Hz, and its additional torque is also given within this voltage range. Therefore, the speed regulation under the extra frequency is called constant torque speed regulation. (T=Te, P<=Pe)

When the output frequency of the inverter is greater than the frequency of 50Hz, the torque of the motor decreases in a linear relationship inversely proportional to the frequency.

When the motor is running at a frequency speed greater than 50Hz, it is necessary to consider the size of the motor load to avoid the lack of motor output torque.

For example, the torque of a motor at 100 Hz drops to about 1/2 of that at 50 Hz.

Therefore, the speed regulation above the additional frequency is called constant power speed regulation. (P=Ue*Ie)

4. The application of inverter above 50Hz

We know that for a particular motor, the extra voltage and the extra current are constant.

For example, the additional value of the inverter and the motor are: 15kW/380V/30A, and the motor can operate above 50Hz.

When the speed is 50Hz, the output voltage of the inverter is 380V, and the current is 30A. At this time, if the output frequency is increased to 60Hz, the maximum output voltage and current of the inverter can only be 380V/30A. Obviously, the output power remains the same. That's why we call it constant power speed regulation.

What about the torque?

Since P=wT (w: angular velocity, T: torque). Since P does not change, w is added, so the torque decreases accordingly.

Let's look at it from another point of view:

Stator voltage of the motor U = E + I*R (I is the current, R is the electronic resistance, E is the induced potential)

It can be seen that when U,I does not change, E does not change.

E = k*f*X, (k: constant, f: frequency, X: magnetic flux), so when f is from 50 to > 60 Hz, X decreases accordingly

For motors, T=K*I*X, (K: CONSTANT, I: CURRENT, X: MAGNETIC FLUX), SO THE TORQUE T DECREASES WITH THE DECREASE OF MAGNETIC FLUX X.

Together, when it is less than 50Hz, the magnetic flux (X) is constant when U/f=E/f is constant because I*R is small. The torque T is proportional to the current. This is why the overcurrent ability of the inverter is generally used to describe its overload (torque) ability. It is also called constant torque speed regulation (the extra current does not change - > maximum torque does not change)

Conclusion: When the output frequency of the inverter is increased from more than 50Hz, the output torque of the motor will decrease.

5. Other elements related to output torque

Heat generation and heat dissipation can determine the output current of the inverter, and then affect the output torque of the inverter.

Carrier frequency: Generally, the additional current marked by the inverter is the value that can be guaranteed to continue to output at the highest carrier frequency and the highest ambient temperature. Drop the carrier frequency, and the current of the motor will not be affected. However, the heat generation of the components will be reduced.

Ambient temperature: Just like the inverter protection current value will not be increased when the ambient temperature is relatively low.

Altitude: Altitude added, has an impact on heat dissipation and insulation performance. Generally, less than 1000m can be considered. More than 5% reduction per 1000 meters can be done.

6. How does vector control improve the output torque of the motor?

*1: Torque progression

This function adds the output voltage of the inverter (mainly at low frequencies) to compensate for the output torque loss caused by the voltage drop across the stator resistor, and then improves the output torque of the motor.

Improve the skills that the motor lacks in low-speed output torque

Using vector control, the output torque of the motor at low speeds, such as 1 Hz (for a 4-pole motor, the speed is about 30 r/min) can reach the torque of the motor at 50 Hz (up to about 150% of the additional torque).

With conventional V/F control, the voltage drop of the motor increases relative to the decrease in motor speed, which leads to the lack of excitation and the motor cannot obtain sufficient rotational force. In order to compensate for this deficiency, progressive voltages are required in the inverter to compensate for the voltage drop caused by the decrease in motor speed. This function of the inverter is called torque progression (*1).

The torque progress function is the output voltage of the progressive inverter. However, even with many advances in output voltage, motor torque does not correspond to the progress in its current. Since the motor current contains the torque weight and other weights (e.g. excitation weight) incurred by the motor.

Vector control distributes the current value of the motor and then checks the current weight of the motor and other current weights (such as excitation weight) where the torque occurs.

Vector control is optimally compensated in response to the voltage drop on the motor side, allowing the motor to generate large torques without adding current. This function is also effective in improving the temperature rise of the motor at low speeds.

Shenzhen Xingfengyuan Electromechanical specializes in the production and sales of stepper motors, stepper drives, servo motors, servo drives, agent Japan Tamagawa servo, Decos (TKS) planetary reducer and motion control products.

More on that
Inverter control method for motor - Senlan Inverter control method for motor - Senlan

1. U/f stable control U/f control is to change the voltage of the motor power supply together with changing the frequency of the motor power supply, so that the magnetic flux of the motor is kept constant, and the efficiency and power factor of the motor do not decrease within a wide range of speed regulation. Because it is to control the voltage and frequency ...

General technical specifications for Sunland inverter SB200 series General technical specifications for Sunland inverter SB200 series

Input rated voltage, frequency 3 phase: 380V, 50/60Hz allowable scale Voltage: 320-420V; Voltage unbalance: <3%; Frequency: 47 - 63 Hz Output output voltage 3 phases, 0V - input voltage, error less than 5% Output frequency scale ...

The overload capacity of the dry-type transformer - Sunland inverter The overload capacity of the dry-type transformer - Sunland inverter

Dry-type transformer is a kind of power equipment, and under normal circumstances, dry-type transformer also requires a certain amount of overload, that is, the workload beyond its working ability. So what about the overload of dry-type transformers and how to influence them? ...

Causes and treatment methods of inverter inverter module damage - Senlan Causes and treatment methods of inverter inverter module damage - Senlan

Most of the damage of the inverter module is due to the damage of the driving electric, which causes the two switching devices on one bridge arm to be turned on at the same time. Inverter inverter power module damage is a common problem in other inverter equipment such as vector inverter or energy-saving inverter.

Anti-interference measures in the application of Sunland inverter Anti-interference measures in the application of Sunland inverter

The main manifestations of the disturbance of the inverter in the application are: higher harmonics, noise and oscillation, load matching, heat generation and other problems. These disturbances are unavoidable, because the input part of the inverter is a rectifier circuit and the output part is an inverter circuit, both of which are made up of nonlinear components that play a switching effect.

Inverter remote control wiring method - Senlan Inverter remote control wiring method - Senlan

1. Connect X (switching input) drive terminal to control the inverter start-stop/forward and reverse rotation; 2. Connect to the AI (analog input) terminal to control the frequency of the inverter (perhaps made into PID closed-loop control active conditioning frequency) 3. Other DO (switching output) is used for transmission ...

The main circuit of the inverter application - Hope Sunland The main circuit of the inverter application - Hope Sunland

There is a circuit breaker QF and a communication contactor KM between the power supply and the inverter, when the inverter does not need to be used for a long time. or when the equipment is overhauled, the circuit breaker is used as an isolation switch, which can block the power supply and ensure the safety of maintenance. It has maintenance functions such as overcurrent and undervoltage. The main power of the inverter ...

Hope Sunland inverter introduction and common models Hope Sunland inverter introduction and common models

It is hoped that Sunland inverter is mainly used in three-phase asynchronous AC motor to control and adjust the motor speed. Sunland inverter is mainly composed of microprocessor, including rectification, filtering, inverter, brake, drive, detection, etc. In order to achieve the purpose of changing the power supply voltage, according to the actual needs of the motor...

Motor inverter principle and precautions for use - Senlan Motor inverter principle and precautions for use - Senlan

The difference between a voltage converter and a current converter Voltage inverter and current inverter are two different operating principles, for example, the operating principle of voltage inverter is mainly to regulate the voltage source, and the voltage source regulates the current to achieve the effect of conditioning, while the current inverter is a direct ...

The reason why the inverter damaged the motor - Senlan The reason why the inverter damaged the motor - Senlan

The presentation of inverters has brought a revolution to industrial automation control and motor energy saving. Industrial production is simply inseparable from the inverter, even in the daily livelihood, elevators, inverter air conditioning has become a part of the insistence, inverter from the beginning into all corners of production, subsistence. However...

Inverter-related knowledge - Senlan inverter Inverter-related knowledge - Senlan inverter

1. What does open-loop mean in the use of inverters? The speed detector (PG) is installed on the motor equipment in operation, and the speed response of the actual speed is sent to the control equipment, which is called "closed loop", and the speed detector that does not use PG is called "open loop". Most general-purpose drives are open-loop ...

The difference between inverter and inverter power supply - Senland The difference between inverter and inverter power supply - Senland

What is a frequency converter? Variable Frequency Drive (VFD) uses inverter technology and microelectronics to change the operating power frequency of the motor to control the power control unit of the communication motor. The inverter is mainly composed of rectifier (from communication to DC), inverter, inverter (from DC to communication) ...

Inverter parameter setting method - Senlan Inverter parameter setting method - Senlan

1. Control method: i.e. speed control, rotation control, PID control, or other methods. After the control method is adopted, it is generally necessary to carry out static or dynamic identification according to the control accuracy. 2. Minimum operating frequency: That is, the minimum speed of the motor operation, the motor at low speed ...

The manufacturing standard of Sunland inverter cabinet The manufacturing standard of Sunland inverter cabinet

Planning specifications: The planning of inverter cabinets should conform to relevant national norms and industry norms, such as GB/T15576-2018 "Low-voltage Distribution Cabinet", GB7251.1-2017 "Low-voltage Complete Switchgear and Control Equipment", etc. Material specifications: The materials of the control cabinet should conform to the relevant codes and regulations.

About the basic selection of Hope Sunland inverter About the basic selection of Hope Sunland inverter

It is hoped that Sunland low-voltage inverter can be divided into four series: 1.HG1000 high-performance light-load intelligent inverter, the most cost-effective, the new series is widely used in medicine, food, packaging, cable, printing and dyeing, washing, centrifuge ...

Introduction to the classification method of inverter maintenance faults Introduction to the classification method of inverter maintenance faults

1. How to distinguish between heavy faults and light faults According to the occurrence time of inverter faults, we can divide the types of faults into two categories: sudden faults and intermittent faults: (1) The sudden fault of inverter repair refers to the failure of the equipment when it is running, without warning.

Senlan wiring knowledge Senlan wiring knowledge

1. Wiring of fire emergency lighting Generally, the flame retardant wire is used to wear the metal pipe and the thickness of the protective layer is ≥ 30mm, in the decoration project, when the emergency lighting circuit can only be applied to the ceiling, the heat-resistant or fire-resistant wire should be selected and the fire-resistant and heat-resistant matching should be considered.

Inverter maintenance method - hope sunland Inverter maintenance method - hope sunland

1. Look After taking over a faulty inverter, remove the inverter shell and clean it up, and carefully investigate the appearance, shape, and integrity of the relevant components on the circuit board with both eyes according to the type of inverter fault. This method is about charging resistors, filter electrolytic capacitors, IG ...

Inverter overcurrent treatment method - Senlan inverter Inverter overcurrent treatment method - Senlan inverter

Overcurrent or overload of the inverter is a common problem of the inverter, and overcurrent refers to the value of the current flowing through the inverter beyond its additional range. 1. If the power supply of the inverter is out of phase, the circuit at the output end is disconnected or the motor winding ...

The reason for using frequency conversion speed regulation - Senlan The reason for using frequency conversion speed regulation - Senlan

Now, the frequency conversion speed regulation system has been widely used in the industrial production of various small and medium-sized enterprises. This is all due to our ability to provide accurate speed control and complete stepless speed regulation. Therefore, it can easily control the ascent and descent of mechanical transmissions, traverse ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top