Rittal cables – measures to prevent or mitigate electrical interference

Create Date: 2024-8-30 12:03:23|Source: Rittal/Rittal

1. One spare core of the control cable is grounded

It has been proved in practice that when a spare core in the control cable is grounded, the amplitude of the interference voltage can be reduced to 25%-50%, and the implementation is simple, and the cost of the cable is increased very little.

2. For circuits that will have serious consequences in the event of electrical interference, it is not suitable for a control cable

These include: (1) weak current signal control loop and strong current signal control loop; (2) The loop between low-level signal and high-level signal; (3) The same control cable should not be used for each phase weak current control loop operated by AC circuit breaker in phase. However, if each pair of round-trip wires of the weak current circuit belongs to the control cable that is not the same, it is possible to form a ring arrangement when laying, and the electric potential will be induced under the cross-link of the magnet wire of the similar power supply, and its value may have a greater impact on the parameter interference of the low level of the weak current circuit, so it is appropriate to use a control cable for the round-trip wire.

3. Grounding of metal shielding and shielding layer

Metal shielding is an important measure to reduce and prevent electrical interference, including the total shielding of the core, the sub-shield and the double-layer total shielding. The selection of the metal shielding type of the control cable should be included in the comprehensive interference suppression measures according to the strength of the possible electrical interference impact to meet the requirements of reducing interference and overvoltage. The higher the requirements for the anti-interference effect, the greater the corresponding investment, when the use of steel tape armor, steel wire braided total shielding, the price of the cable increases by about 10%-20%.

The control interference in the strong current circuit, due to its own strong signal, can be selected without metal shielding except for the ultra-high voltage distribution device or the control cable without metal shielding in addition to the ultra-high voltage distribution device or the parallel parallel to the high-voltage cable. When the control cable used in the weak signal control loop is located in the environment with interference effects and does not have effective anti-interference measures, it is advisable to choose the control cable with metal shielding to prevent electrical interference from malfunctioning or making insulation breakdown on the low-level signal loop. If the control cable of the weak current circuit can be separated from the power cable sufficiently, or when laid in a steel pipe, the external electrical interference may be reduced to a permissible limit.
Rittal cables – measures to prevent or mitigate electrical interference

More on that
Rittal cabinet - judgment and treatment of energy storage faults in high-voltage switchgear Rittal cabinet - judgment and treatment of energy storage faults in high-voltage switchgear

In the high-voltage cabinet with the spring energy storage operating mechanism, the energy storage must be stored in advance before closing. The energy storage mechanism is driven by an electric motor and the gear mechanism lengthens the spring. There are two types of operation methods: electric and manual. Manual failure to store energy should be due to a mechanical failure of the mechanism. Manual energy storage ...

What is the difference between a control cabinet and a distribution box? What is the difference between a control cabinet and a distribution box?

One. The nature is different Distribution box: There is a large amount of parameter data in the distribution box. It generally constitutes a low-voltage distribution box. Control cabinet: The control cabinet is to assemble the switch cabinet, measuring instruments, protection devices and auxiliary equipment in a closed or semi-enclosed metal cabinet or screen according to the requirements of electrical wiring.

Rittal cabinets – installation steps and rules for cabinet placement Rittal cabinets – installation steps and rules for cabinet placement

Cabinet installation steps: 1. Before installing the cabinet, check whether the exhaust device of the cabinet is stable, whether the number of equipment support plates is complete, and whether the pulleys and support columns are stable. 2. The model, specification and device orientation of the cabinet should meet the planning requirements. 3. Cabinet ...

Rittal cabinets – the difference between racks, cabinets, and servers? Rittal cabinets – the difference between racks, cabinets, and servers?

1. a rack Rack: Installed in a standard cabinet, it is a functional server, so the standard cabinet is also called a "19-inch" rack. Rack is a more professional academic term, and most of the current policy documents mention "rack", and clarify the indicators such as single rack power and average shelf rate ...

What are the advantages of Rittal enclosure processing – sheet metal cabinets? What are the advantages of Rittal enclosure processing – sheet metal cabinets?

1. The cabinet and chassis products provide space for power supplies, motherboards, various expansion boards, floppy disk drives, optical disk drives, hard disk drives and other storage devices, and these spare parts are firmly fixed through the internal supports, brackets, various chassis screws or clips and other connectors inside the cabinet and chassis.

Rittal air conditioner - what to do if the air conditioner has an H1 fault code? Rittal air conditioner - what to do if the air conditioner has an H1 fault code?

1. The air conditioner shows the H1 fault code - the reason When the outdoor temperature is low and the humidity is high, the heat exchanger of the outdoor unit will be frosted after the air conditioner runs for a period of time, and then the automatic defrosting function will be activated, and the heating operation will be temporarily suspended for 5-10 minutes. Air conditioner heating defrost shows H1 which is normal ...

Rittal presents its modular data centre solutions Rittal presents its modular data centre solutions

Now AI has been widely used in many fields, and while we enjoy the convenience brought by AI skills, we should also know that behind these AI skills are a huge amount of data processing and communication by weak servers, and then find the most efficient solutions.

For the first time, the Rittal Rittal and Circle B and Switch data centres have launched the European OCP Experience Centre For the first time, the Rittal Rittal and Circle B and Switch data centres have launched the European OCP Experience Centre

Circle B, Rittal and Switch data centres in Germany launch the first European Open Computing Project (OCP) Experience Centre. The full-featured OCP environment is located at one of the facilities of three switching data centers in the Amsterdam area. (The OCP Experience Center can be used as a demo center, but it is also ...

Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets Rittal cabinets – Q&A on the basics of high and low voltage distribution cabinets

What are the classifications of different electrical experiments according to their roles and requirements? A: It can be divided into insulation test and characteristic test. What are the factors that affect the degree of harm to the human body of electric shock? Answer: The magnitude of the current, the duration of the current, the path of the current, the resistance of the human body, and the ...

What are the main problems in the practical application of Rittal cabinet air conditioners on the client? What are the main problems in the practical application of Rittal cabinet air conditioners on the client?

Through continuous big data analysis of 200,000 cabinet air conditioners installed and operated on the market, Rittal found that the main problems in the actual application of air conditioners on the client are as follows: 1. Lack of maintenance, resulting in clogged air conditioner filters, which in turn causes the air conditioner to stop running or ...

Rittal won the Best Partner Award from Hengxin Software and Yokogawa Automation Rittal won the Best Partner Award from Hengxin Software and Yokogawa Automation

Sincere service, strength and responsibility In 2022, which was full of changes, Rittal and its partners Hengxin Software and Yokogawa Automation (part of the Yokogawa Group) withstood the challenges brought about by the pandemic and moved forward hand in hand. In the cooperation project, Rittal worked with the customer to overcome difficulties and complete the project delivery in a timely manner, ...

Rittal enclosures – what should I consider when choosing a cabinet? Rittal enclosures – what should I consider when choosing a cabinet?

1. Reliable quality assurance Choosing the right server and cabling cabinet is important, and the slightest negligence can lead to huge losses. No matter which brand of product it is, quality is the first thing that users should consider. 2. Load-bearing guarantee With...

The FR IT new product launch event organized by Rittal was held in Beijing The FR IT new product launch event organized by Rittal was held in Beijing

The "Eastern Data and Western Computing" project aims to promote the rational layout of data centers, optimize supply and demand, green intensification and interconnection, so that the computing resources in the west can more fully support the computing of data in the east and better empower the country's digital development.   IT infrastructure is an important ...

Rittal Cables – an introduction to the advantages of industrial control cables Rittal Cables – an introduction to the advantages of industrial control cables

1. It can meet the needs of many electrical appliances, and relatively speaking, in the process of making industrial control cables, the relevant standards of various information in the process of dissemination are fully considered. In this way, it can ensure that the industrial control cable can meet the performance of many electrical appliances in daily work.

When winter arrives, Rittal heaters bring warmth to the cabinets When winter arrives, Rittal heaters bring warmth to the cabinets

We know that electronic and electrical equipment is installed in the electrical cabinet, in fact, there are working temperature requirements, the general storage temperature can not be lower than minus 25 degrees, the working temperature can not be lower than minus 20 degrees, but now the outdoor temperature in the north is very simple to reach the lower limit of this working temperature, this time heating ...

What are the functions on the operation panel of the inverter control cabinet? What are the functions on the operation panel of the inverter control cabinet?

Display parameters: The control panel can display various parameters of the inverter, such as input/output voltage, current, frequency, speed, etc. Parameter setting: The control panel can set various parameters of the inverter, such as operating mode, frequency range, acceleration time, deceleration time, etc. ...

Rittal cables – common faults in industrial control cables Rittal cables – common faults in industrial control cables

1. Flashover fault: The industrial control cable is in a good insulation state at low voltage and will not have a fault. However, as long as the voltage value rises to a certain range, or a certain voltage continues to rise after a period of time, then it will instantly break through the insulator and cause flashover fault. 2. Long-term ...

Rittal Cables – an introduction to the performance of industrial control cables Rittal Cables – an introduction to the performance of industrial control cables

Thermal function: Due to the existence of thermal expansion and contraction, we should also pay attention to the thermal function of industrial control cables, that is, the temperature resistance level of industrial control cables, the heating and heat dissipation characteristics of cables for power transmission at working temperatures, current carrying capacity, short circuit and overload capabilities, the thermal deformation and thermal impulse resistance of the constituent materials.

The solution to the A17 fault reported by the Rittal cabinet air conditioner The solution to the A17 fault reported by the Rittal cabinet air conditioner

1. The Rittal air conditioner does not start when it is turned on, and the A17 is faulty. Check that the power supply voltage is 220V, normal; Detect that the battery voltage of the remote control is 3V, which is normal; Measure the fuse resistance value of the air conditioner compressor with a multimeter as infinity, which is normal. 2. The Rittal air conditioner does not start when it is turned on, and the display is not started.

The Rittal RiEDC series has been named the IT Solution of the Year 168 The Rittal RiEDC series has been named the IT Solution of the Year 168

The Rittal RiEDC series has been awarded Solution of the Year at the IT168 Technical Excellence Awards. The "Technical Excellence Award" is jointly judged by professional users of the big data industry, technical experts and the media, and its criteria are based on innovative solutions recognized by the market and customers, ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top