1. Torque control: Torque control is based on external simulation simulation type or direct address assignment to set the output torque of the motor shaft. For example, 10V matches 5Nm. When the external simulation simulation is set to 5V, the output of the motor shaft is 2.5Nm. If the load on the shaft of the motor is less than 2.5 Nm, the motor will not simply roll when the external load is equivalent to 2.5 Nm (beyond 2.5 Nm). When the motor is turned over (generally under force load). This can be done by changing the torque setting by changing the analog amount on the fly, or by changing the value of the relative address depending on the communication.
This application is suitable for winding and unwinding equipment that strictly manages the raw material force, such as hanging wire equipment or fiber optic line driving equipment. The torque setting should be changed anytime and anywhere according to the change of the winding half-warp, so as to ensure that the raw material force is not simple and changes with the change of the winding half-warp.
2. Azimuth control: the general form of azimuth control is based on the frequency of the external input pulse to clarify the speed ratio, according to the number of pulses to clarify the rolling perspective, some servo drives can directly distribute the speed and offset according to the communication. Because the azimuth form can harshly control the speed and bearing, it is generally used to locate the equipment. The main uses are CNC lathes, printing equipment, etc.
3. Speed form: The rolling speed can be controlled according to the simulation simulation type or single pulse frequency. When the outer ring PID control of the control device can be used, the speed form can also be positioned, but the azimuth data signal of the motor or the azimuth data signal of the direct load must be fed back to the top layer for operation. The azimuth form also adapts to the outside of the direct load to check the azimuth data signal. At this time, the servo motor at the shaft end of the motor only checks the speed of the motor, and the azimuth data signal is provided by the direct inspection equipment at the final load end. This advantage is due to the reduction of deviations in the center drive process and the improvement of the positioning accuracy of the full system.
4. Discuss the three-circuit system. Servo motors are generally operated by three circuits. To put it bluntly, the three circuits are three closed-loop control negative feedback PID control systems. The innermost PID loop is the current loop, which is implemented entirely inside the servo controller. The output current from the controller to the motor is checked according to the Hall components, and the negative feedback current is set according to the PID, so that the output current is as close to the set current as possible. The torque of the motor is controlled by the current loop, so that the operator operates in the torque form with minimal operation and daily dynamic response. It should be faster.
The second cycle is the velocity cycle. The negative feedback PID is adjusted by the data signal of the motor servo motor. The output of the PID in the loop is directly the setting of today's loop. Thus, the velocity loop includes a velocity loop and a current loop. In other words, the current loop must be used in full form. The current circuit is the basis of the operation. In addition, the system is now in fact current-controlled. (torque) control to complete the relative speed and azimuth control.
The third ring is the positioning ring, which is the outermost ring. Depending on the situation, it can be set up in the controller and motor servo motor center, as well as in the external controller and motor servo motor or final load center. Since the internal output of the azimuth control loop is the setting of the speed loop, the system operates all three circuits in the azimuth control form. At this time, the measurement volume of the system is quite large, and the daily dynamic response speed is relatively slow.
|
More on that
|
An introduction to the types of data inside the Mitsubishi FX series
A lot of data is used in the internal structure of the PLC and in the user's use program. These data have the following forms in terms of structure or number system.
(1) Decimal number
Decimal numbers are also known as word data in PLC. It is first and foremost ...
|
|
Mitsubishi inverter FR-E700 series is selected
Q: When will I choose the E740 series inverter?
A: E700 is an economical and small inverter with high driving performance, with the function of holding the brake, and can also add options to expand the function, which can be used for transportation, lifting occupations, and has high cost performance.
Q: Mitsubishi inverter E740 should ...
|
|
Mitsubishi FX3u interrupts the location command
The main effect of aborting the positioning instruction is that in some machine tools, when we give the abort signal and can walk to the distance we set, for example, if the mechanical structure needs to use the sensor to determine the position to go, you can use the abort positioning instruction to do, when the induction gives the abort.
|
|
Analysis of the conversion principle of Mitsubishi PLC
1. The digital-to-analog converter is a system that converts digital signals into imitation signals, which can generally be completed by low-pass filtering. The digital signal is decoded in the first line, that is, the digital code is converted into the corresponding level to form a stepped signal, and then the low-pass filter is carried out.
According to the signal and system ...
|
|
How to deal with Mitsubishi PLC failures
01. Base system problem
In Mitsubishi PLC, there are binary, octal, decimal, 10, 2-10 (BCD), etc., we need to master the conversion of 2-8 base.
2-8, remember the binary number from the back, divide every 3 into a group, and each group is converted into octal respectively, such as 1 ...
|
|
The interaction between the PLC and the touch screen is consistent - Mitsubishi
When the contact screen is connected with the PLC, in fact, the memory of the PLC is used, (the contact screen also has a small amount of memory, which is only used to store system data, that is, the screen, controls, etc.), the contact screen and the PLC communication is generally a master/slave relationship, that is, the contact screen reads data from the PLC, and after making a judgment, it is displayed in the display ...
|
|
Troubleshooting methods for Mitsubishi overload
1. Check whether the motor is heated
If the temperature rise of the motor is not high, the first thing to check is whether the electronic thermal protection function of the Mitsubishi inverter is preset reasonably, if the Mitsubishi inverter still has margin, the preset value should be relaxed; For example, the allowable current of Mitsubishi inverter is now out of margin, not ...
|
|
The difference between Mitsubishi PLC source type and leak type
Mitsubishi PLC split source type (PNP) or drain type (NPN), here are their differences
1: Leakage logic: When the current flows out of the signal input terminal, the signal becomes ON, which is leakage logic. The current flows through the terminals and has the output characteristics of an NPN transistor.
2: Source logic: When ...
|
|
The role of Mitsubishi inverters
1. Overvoltage maintenance
The output of the motor inverter has the function of voltage detection, and the inverter can actively adjust the output voltage so that the motor does not bear the overvoltage. Even if the output voltage adjustment fails and the output voltage exceeds 110% of the normal voltage, the inverter will stop to maintain the motor.
|
|
Mitsubishi Electric will introduce the T-series 2.0kV IGBT module for industrial use
Tokyo, June 9, 2021 – Mitsubishi announced the upcoming launch of its industrial T-series 2.0kV insulated gate bipolar transistor (IGBT) module, the world's first IGBT1 with a 2.0kV withstand voltage, June 30. This module is ideally suited to increase the power of renewable energy power converters ...
|
|
Three common communication methods of PLC - Mitsubishi
A PLC network consists of multiple subnets. The communication process of each subnet is determined by the communication protocol. The communication method is the core content of the communication protocol. The means of communication include visit control and data transmission. What are the three common communication methods of PLC?
...
|
|
Which components in the Mitsubishi inverter need to be replaced regularly
Mitsubishi inverter is composed of many electronic parts, such as semiconductor components, etc., in the application and protection involves the replacement of a related component, because of the composition or physical characteristics of the inverter, in a certain period of time will deteriorate, thus reducing the characteristics of the inverter, is ...
|
|
Advantages and disadvantages of Mitsubishi's different output types
The three output types of PLC are: transistor output, thyristor output and relay output, what is the difference between these three different output types?
(1) Transistor output:
The biggest advantage is that it is adapted to high-frequency action, and the echo moment is short, generally about 0.2ms, but it ...
|
|
Mitsubishi PLC ladder programming method
Ladder concept: It is a ladder pattern composed of graphical symbols that indicate the programming elements inside the PLC.
Rules for writing ladders:
Suitable for the left bus, finally the right bus
The contacts should be drawn on the horizontal line, not ...
|
|
OC troubleshooting method reported during inverter operation
1. For the test of the power output capacity of the driving circuit, to detect the pulse terminal signal such as GU\EU, it is not possible to have voltage (or pulse waveform) alone, and the current output capacity should be detected, and then admit whether it is normal;
2. Admit the defects of the current transformer. My solution is to use the ...
|
|
Introduction to the Mitsubishi FX PLC Outage Service
1. What is suspension?
The so-called suspension refers to the fact that in the process of sequentially performing the program scanning, when there is a request to respond immediately, the scanning work performed at that time is immediately suspended, and the service work specified in the request is performed first. When the service job is complete, go back to ...
|
|
Mitsubishi Electric develops satellites for greenhouse gas and water cycle observations
TOKYO, March 30, 2020 – Mitsubishi Electric Corporation (Tokyo: 6503) announced today that it has been appointed by the Japan Aerospace Agency (JAXA) as the contractor for the Global Satellite Observing Satellite for the Greenhouse Gas and Water Cycle (GOSAT-GW), the third satellite in the GOSAT series, ...
|
|
Mitsubishi PLC writes the holding circuit
There is a very common kind of circuit in Mitsubishi PLC - the persistence circuit. The insistence circuit means that when the external input switch is a button, it can be pressed through the insistence circuit to press the button to insist on the output, similar to the self-locking in the electrical diagram. Let's take Mitsubishi PLC as an example to write a sticking circuit.
...
|
|
Mitsubishi A800 series inverter realizes motor self-learning
Set it up as follows:
Press PU/EXT to switch to PU format
Pr.9 = additional current of the motor
Pr.71=3 (ordinary motor) or 13 (constant torque motor)
Pr.80 = motor power
Pr.81 = number of poles of the motor ( ...
|
|
Mitsubishi servo motor method
1. Torque control: Torque control sets the output torque of the motor shaft through external imitation input or direct address assignment. For example, 10V is equivalent to 5Nm. When the external analog is set to 5V, the output of the motor shaft is 2.5 Nm. If the motor shaft load is less than 2.5 Nm, when the external load is 2.5 N...
|
|