Faulty failure with soft starter - LS generates electricity

Create Date: 2024-8-30 12:03:23|Source: LS/Power Generation

In the use of soft starters, some users often have some wrong concepts:

1. It is believed that whether the motor can be started successfully is related to the function of the soft starter, and a good brand or even a foreign brand should be selected under heavy load.

2. When the motor cannot start the load, it is considered that the capacity of the soft starter is not good, and the capacity of the soft starter should be increased.

3. It is considered that a certain starting method is particularly suitable for "heavy-load" starting.

4. It is believed that the smaller the starting current, the better the function of the soft starter with less voltage reduction in the power grid.

These errors are known because there is no understanding and knowledge of the principle of the soft starter of the motor. Let's analyze the above problems one by one.

                            Faulty failure with soft starter - LS generates electricity

The first error concept: whether the motor can be started successfully or not depends on the function of the soft starter. This problem should be analyzed in two aspects, first of all, it should be seen that the corresponding quality of a good brand is relatively good, so in terms of reliability, the probability of a good brand having a problem will be relatively small. However, in terms of the nature of the load of the starting motor, it is the starting torque of the motor that has a decisive effect, and as far as the motor torque is concerned, it is related to many factors. As a kind of voltage regulator, the motor soft starter can only change the control quantity of the stator voltage of the motor, and the torque of the motor is proportional to the square of the stator voltage, and the stator voltage is changed that is, the torque of the motor is changed, this fundamental principle can not be changed, and the soft starters of various brands are planned according to this principle, and their product function or quality has nothing to do. Therefore, whether it is a domestic brand or a foreign brand, in the starting torque, it is fundamentally the same, as long as it is not a soft starter, if the motor can not start the load, it is useless to use other better brand products.

The second error concept: whether the motor can be started successfully is related to the capacity of the soft starter. In practice, the capacity of the soft starter and the capacity of the motor are clouded, or perhaps the capacity and drive torque are clouded, which are two different concepts in practice. As far as the motor is concerned, the capacity and the driving torque are necessarily the same, and the large capacity of the motor reflects that it can output a larger driving torque. The same cannot be said for soft starters, whose capacity only represents the maximum starting capacity it can accept, and the actual output torque depends entirely on the motor itself. Qualitatively speaking, the soft starter is only a power supply, not a drive organization, and cannot supply drive torque. No matter how large the capacity of the soft starter is, but the motor capacity is too small, it still cannot be started successfully. The demand is that the soft starter, as a step-down starting equipment, will inevitably reduce the starting torque and cannot reach the additional torque, which is determined by the principle of the motor, and has nothing to do with the soft start brand and its own control function. Generally speaking, for loads with torque less than 60%, soft starters should be used, and for loads with soft starting torque greater than 60%, other starting equipment should be used.

The third error concept: a certain starting method is particularly suitable for heavy load starting. It should be said that the ability to cope with "heavy loads" has nothing to do with the soft start method. "Heavy load" requires the motor to produce a large starting torque at low speed, so it is necessary to make the stator windings of the motor flow a large enough current, which has nothing to do with the choice of soft starting method. If the current of the motor is not large, no matter what soft start method is chosen, the soft start will be unsuccessful. On the contrary, as long as the current is large enough, after other control methods, the same can complete the successful start when giving it a better shape of the reference input curve backwards, and has better starting characteristics.

The fourth error concept: the smaller the starting current, the lower the voltage drop in the grid, the better the function of the starter. This question is in practice the same thing as the second one. The size of the starting current of the motor depends entirely on the load, and the starting current of the motor must be greater than the motor current determined by the driving torque of the load demand in order to start successfully. Under the premise that the power grid situation remains unchanged, the size of the power grid voltage drop completely depends on the size of the starting current of the motor. It can be seen that neither of the above indicators has anything to do with the soft starter itself.

More on that
The main functions and functions of LS power production PLC The main functions and functions of LS power production PLC

1. For sequential control: sequential control is based on the current and pre-historical conditions of the input switch, and produces the required switching output, so that the system can work in a certain order. This is the basic manipulation of the system. It is also a common manipulation in discrete production processes. ...

The interference phenomenon of the inverter - LS power generation The interference phenomenon of the inverter - LS power generation

1. As soon as the inverter of the heat exchange station is opened, the pressure transmitter jumps randomly; 2. In the water supply controlled by the inverter, the pressure transformer is used as the signal to collect the pressure, and the pressure transformer is interfered by the inverter; 3. When the inverter starts the motor, the voltage transformer signal is unstable ...

LS Group witnesses the reopening of the "Viet Nam Professional Football League". LS Group witnesses the reopening of the "Viet Nam Professional Football League".

The Viet Nam Professional Football League, sponsored by LS Group, began operations in June and is hosted by Viet Nam Professional Football Joint Stock Company. With the comeback of football events such as the Korea K League and the Bundesliga, more and more football events are also brewing to restart. ...

DC reactor for inverter and design calculation - LS power generation DC reactor for inverter and design calculation - LS power generation

The DC reactor for the inverter is also called the flat wave reactor, which is connected in series in the DC bus (terminals P1 and P+). The main thing is to reduce the higher harmonic component of the input current and improve the power factor of the input power supply (to 0.95). This reactor can be used at the same time as the AC reactor, and the inverter has high power ...

The internal accessories component of the power production circuit breaker The internal accessories component of the power production circuit breaker

1. Auxiliary contact: the contact mechanically linked with the main circuit of the circuit breaker and the closing mechanism is mainly used for the display of the circuit breaker and the closing status, and is connected to the control circuit of the circuit breaker through the opening and closing of the circuit breaker to control or interlock its related electrical appliances. For example, output to signal lights, relays, etc.

Inverter overvoltage fault analysis method - LS power generation Inverter overvoltage fault analysis method - LS power generation

The overvoltage of the inverter is manifested in the tributary voltage of the DC bus. Under normal conditions, the direct current of the inverter is the average value of the three-phase full-wave rectification. If calculated by 380V line voltage, the average DC voltage Ud=1.35U line=513V.

Characteristics of single-phase current converter - LS power generation Characteristics of single-phase current converter - LS power generation

Single-phase current transmitter is a kind of power test substation developed for the power measurement of single-phase AC in motor test on the basis of motor test and test technology research, in accordance with IEC and relevant national specifications for motor test. The selection of advanced filtering technology, reasonable software algorithms, processing ...

Electricity-producing permanent magnet AC contactor structure Electricity-producing permanent magnet AC contactor structure

The contactor is mainly composed of a drive system, a contact system, an arc extinguishing system and other parts. 1. Drive system: The drive system includes electronic modules, soft iron, and permanent magnets, which is an important part of the permanent magnet contactor.

How to use the installation wiring of the LS inverter How to use the installation wiring of the LS inverter

1. Circuit wiring (1) The input (R, S, T) and output (U, V, W) of the inverter cannot be connected incorrectly; (2) Wire diameter selection (1) The wiring of the power supply and the inverter and the wire diameter selection method of the motor of the same capacity are the same; (2) The wiring between the inverter and the motor should consider the line electricity.

The size of the contactor is selected by the type of contactor - LS produces electricity The size of the contactor is selected by the type of contactor - LS produces electricity

1. Select the corresponding category of contactor according to the control object, operation times and application category of the contactor. 2. Select according to the rated voltage of the line at the application location. 3. Select the rated current of the main contact of the contactor according to the load capacity. 4. About the voltage level of the lead coil ...

Dealing with intermittent shutdown fault measures - power generation Dealing with intermittent shutdown fault measures - power generation

Because the touch of the network adapter is not good, perhaps due to disturbance and other problems, the DP network that has been used for a long time may show a "transient disconnection" situation, that is, it will be disconnected by an occasional moment, and it will soon recover normally. If OB86 is not downloaded, the CPU will stop during a transient outage. Now all over the option to download a ...

Selection of AC contactors in the field of building electrical - LS power production Selection of AC contactors in the field of building electrical - LS power production

1. The series and parallel connection application of contactors Many electrical equipment are single-phase loads, so several poles of multi-pole contactors can be used in parallel. Such as resistance furnaces, welding transformers, etc. When using several poles in parallel, a smaller capacity contactor can be used. However, it must be noted that after parallel ...

Introduction of LS electric power contactors Introduction of LS electric power contactors

How LS Contactor Works: Generally, after the contactor coil is energized, the entire coil current will generate a magnetic field, which will make the core inside have electromagnetic attraction to attract the core, and let their communication contactor point action normally closed contact disconnect, or close, which ...

Energy-saving method of ventilator inverter - LS power generation Energy-saving method of ventilator inverter - LS power generation

high-power Although some inverters are fan type inverters, but it is a low-power fan inverter, such an inverter does not have the effect of energy saving, and it is necessary to achieve energy saving must be a high-power inverter, in addition to the high-power fan inverter, it is necessary to meet its ...

Electromagnetic interference caused by the working principle - LS power inverter Electromagnetic interference caused by the working principle - LS power inverter

1. Harmonic disturbance The rectifier circuit will produce harmonic current, which produces a voltage drop on the impedance of the power supply system, resulting in distortion of the voltage wave pattern, and the voltage of this distortion constitutes a disturbance on many appearances, and the common voltage distortion is the flattening of the top of the sine wave. Harmonic wave...

Maintenance and maintenance method of electric motor - LS generates electricity Maintenance and maintenance method of electric motor - LS generates electricity

1. Look: The normal operation of the motor has a great relationship with the surrounding environment. Therefore, during the daily inspection, check the water leakage and dripping conditions around the motor (which will cause the low insulation of the motor to form a breakdown and cause burnout), and check whether the peripheral of the motor affects its ventilation and heat dissipation ring.

The inverter generates electricity through the principle of intermediate DC bus power supply - LS The inverter generates electricity through the principle of intermediate DC bus power supply - LS

Most of the inverter manufacturers produce traditional inverters, and their control systems and other power supplies are directly provided by single-phase or three-phase power grids. However, due to the increasing use of VFDs and servo motor amplifiers, a new power supply may emerge: powered by the central DC bus of the VFD. This electric ...

The difference between low-speed and high-speed centrifuges – LS generates electricity The difference between low-speed and high-speed centrifuges – LS generates electricity

Through the rational planning of the structure of the low-speed centrifuge, the hygienic dead angle can be effectively eliminated. The transition of the structural parts is smooth, and the surface is polished. External structural components, fasteners, and rollers are made of stainless steel. The housing is a clamshell type, which allows for thorough cleaning of the interlayer space of the centrifuge housing without the need for a bowl ...

The Importance of Welding in Inverter Maintenance – LS Generates Electricity The Importance of Welding in Inverter Maintenance – LS Generates Electricity

Whether the welding skills of the inverter repair personnel are excellent is directly related to the quality and results after repair. If the welding quality is not up to standard during repair, the pins of the components will be broken when the components are disassembled, the printed circuits on the PCB will be damaged, the components will not be soldered firmly when the components are installed, and the two components ...

Inverter exception handling method - LS power generation Inverter exception handling method - LS power generation

1. The working temperature of the inverter is high 1. Check whether the ambient temperature of the inverter is too high; 2. Check whether the cooling fan inside the device is working properly; 3. Check whether the ventilation pores and mask grilles are blocked; 4. Check if the load is too heavy. ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top